At a glance
- CTC heat pump error codes are alarms written as an E and three digits, such as E135 or E035, shown on the controller the heat pump is paired with, for example a CTC EcoZenith i255, EcoLogic or EcoVent display.
- E135 Risk of freezing is raised when the water leaving the heat pump is below 15°C during a defrost, or when HP in and HP out differ by more than 15°C for over 20 seconds; CTC’s action is to keep the heating return at a minimum of 25°C during defrost.
- E135, E211, E216 and E217 are critical alarms: they can be acknowledged three times with code 4005 in the installer’s coded settings, and after four alarms the heat pump is blocked until the installer attends.
- E035 means the refrigerant high pressure switch has triggered, and E163 means a defrost did not complete within its maximum time.
- Most alarms are reset by pressing the Reset Alarm button on the display once the fault has been rectified, and sensor alarms reset automatically when the sensor is corrected.
- Refrigerant alarms such as E035, E044 to E050 and E152 need a qualified engineer; phase alarms E052 to E055 need an electrician or engineer.
What do CTC heat pump error codes mean?
A CTC heat pump error code is an alarm, written as an E followed by three digits such as E135 or E035, that tells you which part of the system has stopped working as it should. On recent CTC air source systems you will not see it on the outdoor unit. It appears on the controller the heat pump is paired with, such as a CTC EcoZenith i255, EcoLogic or EcoVent display, and CTC’s manual says a message appears with information about the fault. If several alarms are triggered, they are displayed one after the other.
This guide uses the alarm messages and critical alarms chapters of the CTC EcoZenith i255 installation and maintenance manual (CR01164, May 2026), which also cover the alarms from a connected CTC EcoAir outdoor unit. Older EcoAir 105 to 111 units with their own built-in display use shorter two-digit codes that we have not verified, so owners of those should check their own manual.
If your CTC is not showing a code, or you want to rule out the basics first, our guide to a What to know about Heat Pump Not Working walks through the general checks. For codes from other makes, the Guide to Heat Pump Error Codes covers the wider picture. One safety point before you start: never open the casing of the indoor or outdoor unit, because both contain mains voltage and pressurised refrigerant.
Is it safe to fix a CTC heat pump fault yourself?
Only up to a point: you can safely make basic outside checks, but anything inside the units is a job for a qualified engineer. That means looking at the pressure gauge, checking valves are open, clearing leaves or loose snow from around the outdoor unit, checking your consumer unit for a tripped breaker and pressing Reset Alarm once.
Do not remove panels or touch wiring, fuses or circuit boards. CTC’s own text for E055, the phase sequence alarm, says the power supply must be shut off when the fault is rectified, and for E061 the max thermostat reset button sits on the electrical switchboard behind the front panel, which is installer territory. Several CTC alarms point to the refrigerant circuit, and in the UK only qualified engineers are legally allowed to work on it.
There is also your warranty to think about. Unqualified work on the unit can affect manufacturer or installer cover, so if in doubt, stop and call someone. If you smell burning or hear hissing at the outdoor unit, isolate the heat pump at the fused spur or isolator and call an engineer.
Which CTC error codes can you check yourself?
A handful of CTC codes have a realistic first check you can do from outside the unit: E135, E211, E163, E216, E217, E052 to E054, E026 and E074 or E075. The rest need an engineer, so if your code is not here, skip straight to booking one.
For E135 and E211, check the pressure gauge is in the range your installer set, that radiator and isolation valves are open and that the outdoor unit is not blocked by snow or leaves; CTC’s listed actions are the circulation pump, dirt filter, pipe system and pipe size, so a filter clean is the likely engineer fix. Our guide to low pressure on a CTC heat pump explains the gauge and filling loop. For E163, look at the outdoor coil from outside and brush away loose snow or leaves by hand, but never chip or scrape ice; CTC’s instruction is to make sure any ice on the evaporator has disappeared. For E216 and E217, check the system pressure and that radiator valves are open, because both are flow alarms. For E052, E053 and E054, check your consumer unit for a tripped breaker and whether there is a local power problem. For E026, read the controller for the heat pump’s own alarm and write it down. For E074 and E075, check the wall-mounted room sensor is still in place and not damaged.
Stop and call an engineer if E135 or E211 returns after a reset, because low flow in defrost risks freezing the heat exchanger, or if any code comes back after one Reset Alarm press. Our guide to the CTC E135 risk of freezing alarm goes into that code in detail.
What are the most common CTC heat pump error codes?
The most common CTC codes relate to freezing risk in defrost, poor water flow and high pressure. Where we add causes the CTC manual does not mention, we label them as general engineering knowledge.
E135 and E211: risk of freezing
E135 means the temperature of the water leaving the heat pump (HP out) is too low for defrosting; CTC’s conditions are HP out below 15°C during a defrost period, or more than 15°C between HP in and HP out for more than 20 seconds. E211 applies to the EcoAir 600M, 700M and C100 with the flow sensor accessory and means the flow was below 10 litres per minute (610M, 614M, 708M, 712M) or 15 litres per minute (622M, 720M) for more than 30 seconds during defrost. CTC’s possible cause for both is a circuit temperature or flow rate that is too low, and for E135 it adds sensors that do not read correctly.
CTC’s actions are to ensure the heating return is at a minimum of 25°C during a defrost period, to supplement with a volume tank, to check the circulation pump, dirt filter, pipe system and pipe size, and to check the HP in and HP out sensors. From general engineering knowledge, sludge in radiators, a blocked strainer, an air lock or a pump set too low are the usual reasons the flow falls short. Make the pressure and valve checks above, then call us.
E163: defrost not completed
E163 means the heat pump has not had time to complete defrosting within the maximum time. CTC says to make sure that any ice on the evaporator has disappeared. General engineering knowledge adds that a blocked or frozen condensate route can stop the coil clearing, so if ice keeps building, an engineer should check the drain and defrost control.
E216 and E217: flow temperature difference and charge pump flow
E216 applies to the EcoAir 600M, 700M and C100 and means the difference between HP in and HP out exceeded 12°C in heating for more than 15 minutes. E217 applies to the EcoAir 400 and means the charge pump speed exceeded 70 percent in heating for more than 30 minutes. CTC’s cause for both is a circuit temperature or flow rate that is too low, and its action is to check the dirt filter, pipe system and circulation pump speed settings, plus the sensors for E216. After four alarms these become E220 and E221 and the heat pump is blocked.
E035: high pressure switch
E035 means the refrigerant’s high pressure switch has been triggered. CTC’s instruction is to press reset and check whether the alarm recurs, and to contact your installer if it does. General engineering knowledge: the switch trips when the refrigerant side cannot shed its heat into the water, so low or stopped flow, air in the pipes, closed valves, limescale or magnetite sludge in the condenser are the usual reasons. Check valves are open, then leave the rest to an engineer.
E152: four-way valve
E152 is displayed if a fault occurs with the EcoAir’s 4-way valve or if the connection pipes to the EcoAir are incorrectly connected. CTC says to press reset and, if the alarm recurs, check that the charge pump is pumping water to the heat pump’s lower connection, then contact the installer. It is an installer check, especially after recent pipework changes.
E040 and E041: brine alarms (ground source)
E040 is low brine flow, which CTC says is often caused by air in the collector system, especially immediately after installation, or by collectors that are too long; it also says to check the brine pump is on its fastest speed and to check the brine filter. E041 means the incoming brine from the borehole or ground loop is too cold, and CTC asks the installer to check the dimensions of the cold side. Both need an engineer.
E052 to E055: phase faults
E052, E053 and E054 mean one of the three supply phases is missing. E055 means an incorrect phase sequence: the compressor motor must rotate in the right direction, so two of the phases into the product must be swapped with the power shut off, a fault CTC says generally only occurs during installation. You can check for a tripped breaker, but swapping phases is electrical work for a qualified electrician or engineer only.
E057, E058 and E044 to E050: motor protection and compressor stops
E057 and E058 report high or low current into the compressor. E044 is a stop on high compressor temperature, E045 and E046 are stops on low or high evaporation temperature, and E047 to E050 are stops linked to the expansion valve’s suction gas, evaporation and superheat temperatures. For every one of these CTC’s instruction is the same: press reset, check whether the alarm recurs, and contact your installer if it does. Repeated trips can point to supply, flow or refrigerant problems that an engineer tests before suspecting the compressor.
Sensor alarms
A sensor alarm means a sensor is not connected, has short-circuited or is reading outside its range. If the sensor is important to the system’s operation the compressor stops and the alarm needs a manual reset after the fault is rectified; for the sensors CTC lists, including E003, E005, E028 to E032, E036, E037, E043, E074, E075, E080 and E137 to E139, the alarm resets automatically after correction. That correction is an engineer’s job.
Communication, driver and electrical alarms
E027, E063, E021 and E086 mean the display card, HP control card, relay card, motor protection or expansion card cannot communicate with each other. E024 means the F1 or F2 fuse has blown, E087, E088 and E109 are driver faults, and E117 Driver: Offline means the heat pump and driver are not communicating. General engineering knowledge says a loose or damaged cable is a common cause of the communication codes. Reset once, and if it returns, quote the exact code when you call us, as CTC asks.
Which error code might you see in common situations?
The situation often narrows down the code, and the first check is usually simple. CTC has no dedicated water pressure code in the i255 alarm list, so low pressure tends to show up as a flow alarm.
| Scenario | CTC codes you may see | First check |
|---|---|---|
| Cold snap, iced outdoor unit | E135, E211, E163, then E218 or E219 if they repeat | Clear loose snow from around the unit; our guide to do heat pumps work in cold weather in detail shows what is normal |
| Losing pressure or low pressure | E211, E216, E217, E035 | Read the gauge and look for drips at valves and joints |
| Radiators lukewarm | E216, E217, E035 | Radiator valves open, pressure normal |
| No hot water | E137, E138, E139 (EcoTank sensors), E026 | Note the exact code shown |
| After a power cut | E052 to E055, E117; information messages are not faults | Check breakers, then wait |
| Unit noisy or fan not spinning | No code for a rasping noise; E163 if ice is not clearing | Look for ice or debris round the fan |
| After a service or filter clean | E216, E217, E211, E035, E152 | Check valves were reopened and pressure restored |
How do I reset a CTC heat pump?
You reset a CTC alarm by pressing the Reset Alarm button on the display. CTC’s manual says a persisting fault must first be rectified before it can be reset, and that some alarms are reset automatically if the fault ceases. Sensor alarms for the sensors CTC lists reset automatically after correction.
- Note the alarm code and text on the display; if several are shown, note them all.
- Deal with any owner-level cause: reopen valves, restore the pressure, clear snow from the outdoor unit or reset a tripped breaker once.
- Press Reset Alarm on the display.
- Check whether the alarm recurs, which is CTC’s own test for E035, E040, E041, E044 to E050, E057, E058 and E152.
- If it recurs, contact an engineer rather than resetting again.
Critical freezing and flow alarms are different. E135, E211, E216 and E217 are confirmed by entering code 4005 in Advanced, Service, Coded settings, and CTC says they can be acknowledged three times this way; after four alarms the heat pump is blocked and the installer must attend. After one year of operation without any alarms the critical alarm count is reset. Resetting again and again without fixing the cause leads to exactly that lock-out, so one reset is enough before you call for help.
CTC error code list
This list covers the alarm messages and critical alarms in CTC’s EcoZenith i255 installation and maintenance manual, including the alarms it carries for a connected CTC EcoAir. Code meanings can differ between controllers and software versions, so check your own manual too.
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| E003, E005 | Sensor brine in or brine out (ground source) | Sensor not connected, shorted or out of range | Nothing owner-side | Engineer |
| E010 | Compressor type unknown | No compressor type information | Nothing owner-side | Engineer |
| E013 | EVO off: fault with the expansion valve control | Expansion valve control | Nothing owner-side | Engineer |
| E021, E027, E063, E086 | Communication error between the display, HP control, relay, motor protection or expansion cards | Cable or card | One reset | Engineer |
| E024 | Fuse F1 or F2 blown | Internal fuse | Nothing owner-side | Engineer |
| E026 | Heat pump in alarm mode | Underlying heat pump alarm | Read and note the heat pump’s own alarm | Homeowner check, then engineer |
| E028 to E032 | Sensors HP in, HP out, outdoor (B15), primary flow 1 (B1) and 2 (B2) | Sensor fault | Nothing owner-side | Engineer |
| E035 | High pressure switch triggered | Low flow, air, closed valves, scaled condenser | Valves open; one reset | Homeowner check, then engineer |
| E036, E037, E043, E080 | Sensors high pressure, discharge, low pressure, suction gas | Sensor fault | Nothing owner-side | Engineer |
| E040, E041 | Low brine flow; low brine temperature (ground source) | Air in the collector, long collectors, pump speed, filter; cold side undersized | Nothing owner-side | Engineer |
| E044 to E050 | Compressor stops: high compressor temperature, low or high evaporation, low suction gas, low or high evaporation at the expansion valve, low superheat | Refrigerant circuit or expansion valve | One reset | Engineer |
| E052, E053, E054 | Supply phase 1, 2 or 3 missing | Phase failure | Breaker and local supply | Homeowner check, then electrician or engineer |
| E055 | Incorrect phase sequence | Two phases need swapping, usually at installation | Nothing owner-side | Electrician or engineer |
| E057, E058 | Motor protection: high or low current into the compressor | Supply, flow or compressor | One reset | Engineer |
| E061 | Max thermostat (F10) tripped, product too hot | Overheating; cold storage before installation | Nothing owner-side | Engineer |
| E074, E075 | Sensor room 1 (B11) or room 2 (B12) | Room sensor disconnected or damaged | Sensor in place and undamaged | Homeowner check, then engineer |
| E087, E088, E109 | Driver fault (with a number where applicable) | Compressor driver | One reset; note the number | Engineer |
| E117 | Driver: Offline, heat pump and driver not communicating | Communication | Breaker on; one reset | Engineer |
| E135 | Risk of freezing: HP out too low for defrosting | Low circuit temperature or flow; low system volume; sensors | Pressure, valves, outdoor unit clear | Homeowner check, then engineer |
| E137 to E139 | Sensors differential thermostat (B46), EcoTank lower (B42) and upper (B41) | Sensor fault | Nothing owner-side | Engineer |
| E152 | 4-way valve fault or incorrect EcoAir pipe connections | Valve or pipework | One reset | Engineer |
| E163 | Defrost maximum time exceeded | Ice remaining on the evaporator | Snow and leaves cleared; never chip ice | Homeowner check, then engineer |
| E211 | Risk of freezing, low flow in defrost (EcoAir 600M, 700M, C100 with flow sensor) | Flow below 10 or 15 litres per minute | Pressure, valves | Homeowner check, then engineer |
| E216 | HP flow temperature difference over 12°C for 15 minutes (EcoAir 600M, 700M, C100) | Low flow: dirt filter, pipework, pump speed, sensors | Pressure, valves | Homeowner check, then engineer |
| E217 | HP charge pump flow: pump above 70 percent for 30 minutes (EcoAir 400) | Low flow: dirt filter, pipework, pump speed | Pressure, valves | Homeowner check, then engineer |
| E218 to E221 | Fourth occurrence of E135, E211, E216 or E217; heat pump blocked | Unresolved freezing or flow alarm | Nothing owner-side | Engineer |
Where do I find the CTC fault code list?
CTC publishes its manuals as PDFs in the download documents section of its website, and alarm lists sit in the controller manual rather than the outdoor unit manual. Filter the download page by product, for example CTC EcoZenith i255, and by document type, User Manual, to reach the installation and maintenance manual this guide draws on.
- CTC download documents page (filter by product and document type)
- CTC EcoZenith i255 installation and maintenance manual, CR01164 (PDF)
If your controller shows a code that is not in this guide, including the two-digit codes on older EcoAir units, check the manual for your exact model before acting on it.
When to call an engineer
Call an engineer for a CTC heat pump when E135, E211, E216 or E217 recurs after one reset, because the fourth occurrence blocks the heat pump, when E035, E152 or any E044 to E050 compressor stop appears more than once, when a phase alarm stays with the supply confirmed on, or when a communication or driver alarm returns. If you hear hissing at the outdoor unit or smell burning, isolate the heat pump at the fused spur or isolator and wait for an engineer.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. A repair engineer visit starts with reading the alarm list on the controller and a quote before any part is fitted.
Many of the codes in this guide, especially the flow and freezing alarms, come down to dirty filters, low pressure or sludge, which is the case made in Why heat pump servicing is so important in detail. Our a heat pump service plan build the annual service in alongside callouts, and you can check our local heat pump engineers for your area. If you are weighing up a plan for a CTC system, read what to know about Is Heat Pump Cover Worth It.
Frequently asked questions
Does a CTC error code void my warranty?
No, a code on its own does not affect your warranty. What can affect it is unqualified work on the unit or missed servicing, depending on the terms your installer gave you. CTC’s own manual directs most recurring alarms to the installer, so check those terms before booking anyone and keep records of every repair.
What is the difference between an E code and an I code on a CTC controller?
E codes are alarms that point to a fault. I codes are information messages, for example I050, which indicates that power limitation is activated. Information messages describe a state rather than a fault, need no action from you and clear on their own, whereas an E code stays until it is reset or the fault ceases.
Can I see CTC error codes on my phone?
The codes always show on the controller display, which is the most reliable place to read them. CTC’s myUplink service can show the system remotely where it is connected and set up, so whether you also see alarms on your phone depends on your controller model and how it was installed. Your installer or the controller manual will confirm this.
Does a motor protection or high temperature code mean the compressor has failed?
Not usually. CTC’s instruction for E057, E058 and E044 is simply to press reset and see whether the alarm recurs, because a supply problem, a lost phase or poor water flow can make the compressor draw the wrong current or run hot. An engineer will test the supply and flow before looking at the compressor itself.
Why has my CTC heat pump locked out after a freezing alarm?
Because E135, E211, E216 and E217 are critical alarms. CTC allows them to be acknowledged three times with the installer code 4005, and after four alarms the heat pump is blocked and shows E218 to E221 until the installer attends. The count resets after one year without alarms, so a lock-out means the flow or temperature problem behind the alarm has not been fixed.
Sources and further reading: CTC, CTC EcoZenith i255 installation and maintenance manual, CR01164 (10 May 2026), sections 14.1 information messages, 14.2 alarm messages and 14.3 critical alarms; CTC download documents. Checked October 2026.