Daikin Altherma Heat Pump Error Codes: Meanings, Causes, Fixes & What to Do

Daikin Altherma error codes explained guide tile: the Daikin Madoka wired room controller showing 21 degrees
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

Daikin Altherma heat pump error codes are two-part codes such as 7H-01 or 89-02 shown on the indoor unit's user interface. This guide lists the codes from Daikin's own Altherma 3 R W installer reference guides, explains what each means, which checks are safe for an owner, how resets work and when to call an engineer.

At a glance

Get a cover plan here >

  • Daikin Altherma error codes are two-part codes such as 7H-01: the main code names the fault and the detail code after the dash says which version of it happened.
  • 7H-01 is a water flow problem; Daikin says the unit stops when flow falls below the 12 litres per minute minimum, shows 7H-01, then resets itself and resumes once flow recovers.
  • 89-01, 89-02 and 89-03 mean the plate heat exchanger has frozen or its freeze-up protection has activated, and HJ-10 is a water pressure sensor abnormality.
  • Daikin’s troubleshooting checks for poor heating start with open shut-off valves, a clean water filter, no air in the circuit and water pressure above 1 bar.
  • Daikin says the cause should be understood and dealt with before an error code is reset, and that this should be done by a licensed installer or dealer.
  • Codes beginning E, F, H, J, L, P and U0 to U2 come from the outdoor unit and involve the inverter or refrigerant circuit, so they need an engineer.

What do Daikin Altherma heat pump error codes mean?

A Daikin Altherma error code means the heat pump has stopped or limited itself because of a fault, and the code tells you which fault. The code has two parts, such as 7H-01: the first part is the main code and the second is a detail code that says which version of the fault happened. Always note both, because 7H-04 and 7H-05 point to different situations even though both are flow problems.

Codes show on the indoor unit’s user interface and come from either the indoor unit or the outdoor unit, which Daikin marks “OU” in its tables. Some have simple causes such as a closed valve or a lost Wi-Fi link. Others involve the refrigerant circuit or the inverter, and Daikin says errors should be dealt with by a licensed installer or dealer before they are reset.

If your Daikin Altherma is not showing a code, or you want to rule out the basics first, our guide to a Heat Pump Not Working explained covers the general checks that apply to every make. For codes on other brands, the Heat Pump Error Codes explained lists the common ones by manufacturer.

This guide is based on the Daikin Altherma 3 R W installer reference guides for the ERGA outdoor unit with EHBH or EHBX indoor unit, both the 2017 D-series and the 2024 E-series editions. Other Altherma models, including the monobloc and high temperature ranges, share many codes but not all, so check your own manual.

Is it safe to fix a Daikin Altherma fault yourself?

Only simple outside checks are safe for most homeowners on a Daikin Altherma. You can read the pressure gauge, check that valves you know about are open, clear snow or leaves from around the outdoor unit and check breakers. Daikin’s own troubleshooting for a unit that is not heating as expected lists exactly these items: shut-off valves fully open, a clean water filter, no air in the system and water pressure above 1 bar.

Never open either unit to test sensors, circuit boards or wiring. The outdoor unit contains inverter electronics at mains voltage, and Daikin’s installer guide refers engineers to the service manual for the detailed troubleshooting of every code.

Refrigerant work, including any code linked to refrigerant pressure or charge, is legally restricted to qualified engineers. DIY repairs inside the unit can also affect your manufacturer warranty, so check your paperwork first. If you smell burning or see water running from the unit, isolate it at the fused spur or isolator and call an engineer rather than investigating.

Which Daikin error codes can you check yourself?

You can safely check the Daikin codes tied to water flow, pressure, airflow, hot water use and connections: 7H-01, 7H-04, 7H-05, HJ-10, E7-00, A5-00, U8-01 to U8-03, AJ-03, U4-00 and U5-00. Everything else needs an engineer.

For the 7H flow codes, check any valves you closed are open and that the pressure gauge reads above 1 bar, which is the figure Daikin gives in its own checks. Clean the water filter only if it is easy to reach and your manual says you can. For HJ-10, read the gauge; if you have a filling loop and your manual allows it, top up to just above 1 bar. Our guide to the Daikin 7H-01 and 7H-05 low flow and pressure faults covers where the gauge and filling loop sit on the EHBH and EHBX indoor units.

For E7-00 and A5-00, isolate the power, then clear leaves, snow or ice from the fan grille and coil. For U8-01, restart your router and check the LAN adapter has power. For U8-02 and U8-03, replace the room thermostat batteries if it has them. AJ-03 resets itself after a normal hot water heat-up, so wait for the next one. For U4-00 and U5-00, check the breakers for both units and restart once. Stop and call an engineer if any of these returns after the check.

What are the most common Daikin Altherma error codes?

The Daikin codes we see most often are flow, freezing, pressure, communication and hot water faults. Daikin’s installer guide describes each code but leaves the detailed fixes to its service manual, so causes labelled general engineering knowledge come from our own experience rather than from Daikin.

7H: water flow problem

7H is the most important indoor code family on an Altherma. Daikin says that when the water flow falls below the minimum in its table, 12 litres per minute for the ERGA04 to 08 outdoor units, the unit temporarily stops, shows 7H-01, then resets the error automatically after some time and resumes. The detail code tells you when it happened: 7H-04 during domestic hot water production, 7H-05 during heating or sampling, 7H-06 during cooling or defrost and, on the D-series, 7H-07 while pump deblocking is active.

As general engineering knowledge, closed valves, a blocked filter, air in the circuit or the wrong pump speed are typical, with sludge, scale or low pressure underneath. Daikin’s own list for low flow adds a broken expansion vessel, a closed valve towards the expansion vessel and a water circuit whose resistance is too high for the pump. Check valves and pressure first, then book an engineer if the unit keeps stopping and starting.

89-01, 89-02 and 89-03: heat exchanger frozen

On the 2017 guide all three simply mean “heat exchanger frozen”, the plate heat exchanger where refrigerant passes heat to the water. The 2024 E-series guide is more specific: 89-01 is freeze-up protection activated during defrost as an error, 89-02 is the same protection during heating or hot water as a warning, and 89-03 is during defrost as a warning; 89-05 and 89-06 cover cooling. As general engineering knowledge, low flow in cold weather is the usual suspect.

Our guide to the Daikin 89-01, 89-02 and 89-03 frozen heat exchanger codes explains the difference between a warning and an error. An engineer will check for air, sludge or a blocked filter and confirm the freeze protection settings.

HJ-10: water pressure sensor

HJ-10 means a water pressure sensor abnormality. It can be a wiring or sensor fault, but genuinely low pressure from a leak or a failed expansion vessel will also trigger it, as general engineering knowledge. Daikin’s symptom table for a pump making noise lists a broken water pressure sensor alongside a broken expansion vessel and pressure below 1 bar.

Check the gauge and top up only if you are allowed to. If the pressure keeps falling, an engineer will test the sensor, the expansion vessel pre-pressure and the circuit for leaks.

E3-00, FA-00 and A5-00: high pressure

E3-00 means the outdoor high-pressure switch (HPS) has actuated, and FA-00 is abnormal high pressure with actuation of the HPS. A5-00 is an outdoor high-pressure peak cut or freeze protection problem. On the E-series, E3-24 is a high pressure sensor abnormality.

As general engineering knowledge, poor flow on the water side pushes refrigerant pressure up, so low flow is ruled out before the outdoor unit is blamed. These need an engineer if the water side checks out.

U4-00, U5-00 and U8: communication faults

U4-00 is an indoor to outdoor unit communication problem, and U5-00 is a user interface communication problem. U8-01 means the connection with the LAN adapter has been lost, U8-02 means the connection with the room thermostat has been lost, and U8-03 means there is no connection with the room thermostat. The E-series adds U8-04 (unknown USB device), U8-05 (file malfunction) and U8-07 (P1P2 communication error).

For U4 and U5, an engineer checks the cabling and terminals. The U8 codes often have simple causes like a router restart or flat thermostat batteries.

E7-00: outdoor fan motor

E7-00 means a malfunction of the outdoor unit fan motor. As general engineering knowledge, debris, ice or a wiring fault are the likely causes.

Isolate the power and clear anything around the fan. If the code returns, the motor or its wiring needs an engineer.

Sensor faults

Several codes mean a temperature or pressure sensor has failed or is reading abnormally. These include 80-00 (returning water, 80-01 on the E-series) and 81-00 (leaving water), H9-00 (outdoor air thermistor), C4-00 (heat exchanger temperature sensor), CJ-02 (room temperature sensor), H1-00 (external temperature sensor), HC-00 (tank temperature sensor), J3-00 (discharge pipe thermistor), J6-00 and J6-07 (heat exchanger thermistor), P4-00 (radiating fin temperature sensor), JA-00 (high pressure sensor) and JA-17 (refrigerant pressure sensor).

The usual fix is testing or replacing the sensor and its cable. There is no safe homeowner check.

AA, AC, AH and AJ: heater and hot water codes

AA-01 means the backup heater has overheated (or, on the E-series, that its power cable is not connected), AA-02 is an overheated external backup heater and AC-00 is an overheated booster heater. AH-00 means the tank disinfection function did not complete correctly; Daikin recommends programming it to start at least 4 hours after the last expected large hot water draw, or an eco preheat 3 hours before on scheduled-only systems. AJ-03 means the hot water heat-up took too long, and Daikin says it resets automatically after a normal tank heat-up.

Daikin also notes that if the booster heater overheats and is disabled by its thermostatic safety, the unit does not give an error directly; instead you may see a very long powerful heat-up with AJ-03, or AH-00 during the weekly anti-legionella run. So if hot water takes ages or those codes keep appearing, ask an engineer to check the booster heater.

U0-00: refrigerant shortage

U0-00 means the outdoor unit has detected a shortage of refrigerant. As general engineering knowledge, that usually means a leak or an undercharge at installation.

This is a job for an engineer only. Do not keep resetting it, as running short of refrigerant can damage the compressor.

Which error code might you see in common situations?

What was happening when the code appeared narrows things down quickly. These are the Daikin Altherma codes most likely in everyday situations.

Scenario Codes you may see on a Daikin First check
Cold snap, outdoor unit iced up 89-01 to 89-03, A5-00, 7H-06, E7-00 Allow time for a defrost, then clear snow. Our guide to Do Heat Pumps Work in Cold Weather explained shows what is normal
Losing pressure or low pressure HJ-10, 7H-01 Gauge above 1 bar, and drips from the relief valve pipe
Radiators lukewarm 7H-05, E3-00, FA-00 Valves open, then gurgling that suggests air
No hot water 7H-04, AJ-03, AC-00 Breakers for the backup and booster heaters
After a power cut U2-00, E8-00, A1-00, U4-00, U5-00 Breakers for both units, then one restart
Unit noisy or fan not spinning E7-00, L4-00 Debris or ice around the fan, with power isolated
After a service or filter clean 7H-01, 7H-05, HJ-10 Valves reopened, air purged and pressure above 1 bar

How do I reset a Daikin Altherma heat pump?

Daikin says it is important to understand the problem and take measures before resetting an error code, and that this should be done by a licensed installer or your local dealer, so a reset is a short-term step rather than a fix. Some codes clear on their own: 7H-01 resets automatically once flow recovers, and AJ-03 clears after a normal hot water heat-up. Daikin also says the user interface itself displays how an error code can be reset.

For other codes, a homeowner can read the error and try one restart:

  1. Write down the full code, including the detail number after the dash.
  2. On the user interface, press the left dial to open the main menu and go to Malfunctioning, which shows a short description of the error; press again in the error screen for the long description.
  3. Deal with any owner-level cause: open a closed valve, restore the pressure to above 1 bar, clear the outdoor unit or replace thermostat batteries.
  4. Follow the reset instruction shown on the user interface, or switch the heat pump off at its breaker or isolator, wait a few minutes and switch it back on.
  5. If the code comes back, leave it there and book an engineer.

Resetting again and again without fixing the cause can put strain on the compressor and hides the pattern an engineer needs to see. A code that keeps clearing and returning, such as repeated 7H-01, is itself useful information for the visit.

Daikin Altherma error code list

These are the codes listed in Daikin’s Altherma 3 R W installer reference guides (4P496758-1 for the 2017 D-series and 4P629085-1E for the 2024 E-series), grouped where they share a cause. Codes marked E-series appear only in the newer guide. Check your own manual for any code not shown here.

Outdoor unit codes

Code Meaning Likely cause What to check Who should act
A1-00 Zero cross detection problem Power supply or outdoor PCB Breakers on after a power cut Engineer
A5-00 OU: high pressure peak cut or freeze protection problem Poor heat rejection or airflow Coil clear of ice and debris Homeowner check, then engineer
E1-00 OU: PCB defect Outdoor control board Nothing owner-side Engineer
E3-00, FA-00 OU: actuation of high pressure switch; abnormal high pressure with HPS actuation Low water flow or refrigerant-side fault Valves open, pressure above 1 bar Engineer
E5-00, E6-00 OU: overheat of inverter compressor motor; compressor start-up defect Compressor, inverter or supply Nothing owner-side Engineer
E7-00 OU: malfunction of outdoor unit fan motor Debris, ice or wiring Isolate, then clear the fan grille Homeowner check, then engineer
E8-00, U2-00 OU: power input overvoltage; defect of power supply voltage Mains supply Breakers on after a power cut Engineer
EA-00 OU: cool/heat switchover problem Four-way valve Nothing owner-side Engineer
F3-00, F6-00 OU: malfunction of discharge pipe temperature; abnormal high pressure in cooling Refrigerant circuit Nothing owner-side Engineer
H0-00, H8-00 OU: voltage/current sensor problem; compressor input (CT) system Outdoor electronics Nothing owner-side Engineer
H3-00 OU: malfunction of high pressure switch Switch or wiring Nothing owner-side Engineer
H6-00 OU: malfunction of position detection sensor Compressor drive electronics Nothing owner-side Engineer
H9-00, J3-00, J6-00, J6-07, P4-00 OU: outdoor air, discharge pipe, heat exchanger or radiating fin thermistor malfunction Sensor or cable Nothing owner-side Engineer
JA-00 OU: malfunction of high pressure sensor Sensor or cable Nothing owner-side Engineer
L3-00 OU: electrical box temperature rise problem Blocked airflow or electronics Nothing owner-side Engineer
L4-00 OU: inverter radiating fin temperature rise Blocked airflow around the unit Clear airflow, let it cool Homeowner check, then engineer
L5-00 OU: inverter instantaneous overcurrent (DC) Inverter or compressor Nothing owner-side Engineer
U0-00 OU: shortage of refrigerant Leak or undercharge Nothing owner-side Engineer
U7-00 OU: transmission malfunction between main CPU and inverter CPU Outdoor electronics Nothing owner-side Engineer
E2-00, E4-00, E9-00, H5-00, L1-00, L8-00, L9-00, LC-00, P1-00, P3-00, PJ-00, U1-00, UF-00 (E-series) Leakage current, abnormal suction pressure, expansion valve, compressor overload, inverter PCB, inverter thermal protection, compressor lock prevention, outdoor communication, open-phase imbalance, abnormal direct current, capacity mismatch, reverse or open phase, reversed piping or wiring Outdoor electronics, supply or refrigerant circuit Nothing owner-side Engineer

Indoor unit codes

Code Meaning Likely cause What to check Who should act
7H-01, 7H-04 to 7H-07 Water flow problem (during DHW, heating, cooling or defrost, or pump deblocking) Flow below 12 l/min: valves, filter, air, pressure Valves open, pressure above 1 bar Homeowner check, then engineer
80-00 (80-01 E-series), 81-00 Returning or leaving water temperature sensor problem Sensor or cable Nothing owner-side Engineer
89-01 to 89-03 Heat exchanger frozen or freeze-up protection activated Low flow in cold weather Pressure and valves Engineer
8F-00, 8H-00, 8H-03 Abnormal increase in outlet water temperature (DHW or heating); water circuit overheating (thermostat) Low flow or control fault Nothing owner-side Engineer
AA-01, AA-02, AC-00 Backup, external backup or booster heater overheated Heater thermal protector or wiring Nothing owner-side Engineer
AH-00 Tank disinfection function not completed correctly Hot water drawn during the cycle; booster heater Disinfection timing Homeowner check, then engineer
AJ-03 Too long DHW heat-up time required Booster heater disabled; resets after normal heat-up Wait for the next heat-up Homeowner check, then engineer
C0-00, C0-01, C0-02 Water flow detected while pump is off; flow switch malfunction (flow sensor malfunction on E-series) Flow switch or sensor Nothing owner-side Engineer
C4-00, C5-00, CJ-02, H1-00, HC-00, HC-01 Heat exchanger, room, external or tank temperature sensor problem Sensor or cable Nothing owner-side Engineer
EC-00, EC-04 Abnormal increase in tank temperature; tank preheating Control or sensor Nothing owner-side Engineer if it persists
HJ-10 Water pressure sensor abnormality Low pressure, leak, expansion vessel or sensor Gauge above 1 bar Homeowner check, then engineer
JA-17 Refrigerant pressure sensor abnormality Sensor or cable Nothing owner-side Engineer
U3-00 Underfloor heating screed dry-out function not completed correctly Dry-out programme interrupted Nothing owner-side Engineer
U4-00, U5-00 Indoor/outdoor unit, or user interface, communication problem Cable, terminals or a unit without power Breakers for both units, one restart Homeowner check, then engineer
U8-01 to U8-03 Connection with LAN adapter lost; connection with room thermostat lost or absent Router, adapter power, thermostat batteries Router restart, fresh batteries Homeowner check, then engineer
UA-17, UA-21, UA-22 Tank type problem; extension/hydro mismatch; control box to option box communication Configuration or wiring Nothing owner-side Engineer

Where do I find the Daikin Altherma fault code list?

Daikin publishes its installer reference guides as free PDFs, and the error code overview sits in the troubleshooting chapter (section 12.4 in the 2017 guide and 14.4 in the 2024 guide). Check the model numbers on your units first, because the E-series Altherma 3 R W has its own guide with extra codes.

If your interface shows a code that is not in this guide, check the installer reference guide for your exact model before acting on it.

When to call an engineer

Call an engineer for a Daikin Altherma when a code returns after one reset, when 7H codes keep appearing with open valves and pressure above 1 bar, when any sensor, heater, high pressure or outdoor unit code shows, or when U0-00 appears at all. If water is running from the pressure relief valve rather than dripping, Daikin’s advice is to close the water inlet and outlet shut-off valves and contact your dealer; if you smell burning, isolate the unit at the fused spur or isolator first.

UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We look after Daikin heat pumps including the Altherma 3 range, and a Book a repair begins with diagnosis and an agreed quote before any parts are fitted.

A large share of Daikin codes, 7H flow faults above all, start with a blocked filter, air or low pressure. Daikin’s own maintenance list includes emptying the magnetic filter and dirt separator and checking the water pressure relief valve yearly, which is what an annual service covers. Our service and cover plans bundle that service with callouts, and you can confirm we reach you on our the towns and cities we cover. If you are unsure whether a plan makes sense, our guide to Is Heat Pump Cover Worth It explained weighs it up, and Why Heat Pump Servicing Is So Important explained explains what the yearly visit prevents.

Frequently asked questions

Does a Daikin error code void my warranty?

No. A code by itself is the unit protecting itself and has no bearing on your warranty. What can cause problems is unqualified work inside the unit or a patchy service history, as manufacturer warranties usually depend on both. Daikin expects errors to be investigated by a licensed installer or dealer, so keep your records and use a certified engineer for anything beyond the owner checks here.

Can I see Daikin error codes in an app?

If your system has a LAN or Wi-Fi adapter, faults may also show as alerts in the Daikin app. A U8-01 code means that adapter has lost its connection, so the app may go quiet even when the heat pump is fine, and the user interface on the indoor unit is still the place to read the full code. Our Daikin Altherma Heat Pump Review looks at the range and its controls in more detail.

Does a compressor code mean the compressor has failed?

Not usually. Codes such as E5-00, E6-00 and L5-00 describe an overheated compressor motor, a start-up defect or an inverter overcurrent, and in our experience these can trace back to supply voltage, poor flow or the inverter board rather than the compressor itself. An engineer with the Daikin service manual tests the inverter output and windings before condemning the compressor.

Why won’t my Daikin compressor start when there is no error code?

Daikin’s symptom table lists three causes: the water temperature is below the unit’s operating range, so the backup heater must first bring it to 15°C; the preferential kWh rate settings and wiring do not match; or the electricity company has sent a preferential rate signal, in which case Daikin says to wait for power to return, up to 2 hours. If none of these fits, book a diagnosis.

Why is water coming from the pressure relief valve?

Daikin’s guide links a relief valve that opens to a broken expansion vessel, a closed valve towards the expansion vessel, too much water volume in the installation or a water circuit head above 10 metres. A valve that leaks is usually dirt blocking its outlet; Daikin says to turn the red knob anticlockwise and contact your dealer if there is no clacking sound or the water keeps running.

Sources and further reading: Daikin, Daikin Altherma 3 R W installer reference guide 4P496758-1 (December 2017), chapter 12 troubleshooting; Daikin, Daikin Altherma 3 R W installer reference guide 4P629085-1E (April 2024), chapter 14 troubleshooting. Checked October 2026.