Haier Heat Pump Error Codes: Meanings, Causes, Fixes & What to Do

Haier error codes explained guide tile: a hand holding a smartphone showing the Haier hOn app home screen
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

Haier heat pump error codes are E codes such as E08, E15 or E30 shown on the outdoor unit display and the indoor wired controller. This guide lists every code in Haier's own R290 Super Aqua service manual, explains what triggers each one, which checks are safe for an owner, which codes latch and when to call an engineer.

At a glance

Get a cover plan here >

  • Haier heat pump error codes are short E codes such as E08 or E15 shown on the outdoor unit’s digital display and the indoor wired controller; some carry a suffix, for example E20-0 or E71-1, to show which of two similar parts is affected.
  • E08 is a flow switch abnormality or low water flow: Haier raises it when there is no flow signal 120 seconds after the pump starts, clears it after 5 minutes of normal flow, and confirms the failure if it occurs 3 times in an hour.
  • E15 is anti-freeze protection, triggered when the water inlet or outlet temperature falls to 3°C or below, with recovery after 10 minutes and confirmation after 3 events in an hour.
  • Haier classes every code as resumable or unresumable; an unresumable code such as E30, E34 or E40 stays latched once confirmed and needs an engineer.
  • Haier’s R290 Super Aqua units use propane refrigerant, so refrigerant codes need an engineer trained for flammable refrigerants.
  • Haier publishes no owner reset sequence for latched codes; the safe step is a power restart once the cause is fixed.

What do Haier heat pump error codes mean?

A Haier heat pump error code is a short E code, such as E08 or E15, that the system shows when a sensor, safety switch or board reports a problem. Haier’s service manual lists each code twice: as the number on the outdoor unit’s digital display tube and as the E code on the indoor wired controller, so 8 on the outdoor display is E08 indoors. Some codes have a suffix, for example E20-0 and E20-1 for the two defrost coil sensors, or E71-0 and E71-1 for the upper and lower fan motors.

These codes come from Haier’s service manual for the R290 Super Aqua Hydro Split and Hydro All in One (SYJS-03-2024 Rev.A, March 2024). Super Aqua monobloc units may differ, so check your manual. Every code in the manual is marked resumable, meaning it clears itself once the condition goes, or unresumable, meaning it stays latched once the unit has confirmed it.

If your Haier is not showing a code, or you want to rule out the basics first, our guide to a Heat Pump Not Working guide covers the general checks for any make. If you own another make, the What to know about Heat Pump Error Codes lists its common codes. A quick safety point: switch the unit off at its isolator before you look at it, and never open the casing.

Is it safe to fix a Haier heat pump fault yourself?

Only the basic checks are safe for a homeowner on a Haier heat pump; anything inside the unit needs a qualified engineer. That means reading the pressure gauge, checking valves are open, clearing debris from the outdoor unit and resetting a tripped breaker once.

Do not remove covers or touch wiring, boards or connectors, even when a code points at a sensor plug. Haier’s own troubleshooting for sensor codes starts with checking the connector and measuring the sensor’s resistance characteristic, which is engineer work on a live board.

Refrigerant work is restricted by law to qualified engineers. Haier’s R290 models use propane, a flammable refrigerant, so the engineer also needs specific training for it, and codes such as E30, E39-0, E40 and E49 that involve refrigerant pressure are never DIY. Unqualified work inside the unit can also put your warranty at risk. If you smell gas or hear hissing at the outdoor unit, keep ignition sources away, isolate the heat pump at the fused spur or isolator and call an engineer.

Which Haier error codes can you check yourself?

A few Haier codes have a check you can safely make, mainly the water flow, frost, airflow, fan and power codes: E08, E15, E71-0, E71-1, E81, E112, E06, E07, E114 and E124. Haier’s list has no dedicated water pressure code, so low pressure usually shows up as E08.

For E08, check the pressure gauge and that isolation and radiator valves are open, and top up only if you have a filling loop and the manual allows it. Our guide to low pressure on a Haier heat pump explains the gauge and filling loop. For E15, make sure the heat pump has power and the heating is not switched off during a frost; our guide to the Haier E15 anti-freeze fault covers what to do while you wait. For E71-0 and E71-1, look for snow, ice or leaves blocking the fan and clear around the unit by hand. For E81 and E112, clear anything blocking airflow around the outdoor unit, because both are driver board temperature protections. For E06 and E07, check the heat pump breakers are on, then restart once. For E114 and E124, wait for the supply to settle after a power cut and restart once.

Stop and call an engineer if any of these returns after the check, or if other appliances are flickering, which points to a supply problem rather than the heat pump.

What are the most common Haier heat pump error codes?

The Haier codes we come across most are E08 for low water flow and E15 for frost protection, followed by sensor, communication and refrigerant pressure faults. Haier’s service manual gives the trigger for each code and, for some, a troubleshooting flow; where we add causes the manual does not state, they are general engineering knowledge.

E08: flow switch fault or low water flow

Haier raises E08 when there is no water flow signal after the pump has run for 120 seconds, either because the flow switch is off or the flow is below the set value, and clears it once flow has been normal for 5 minutes. If it occurs 3 times in an hour the failure is confirmed. General causes are a blocked strainer, closed valves, a failing pump, an air lock or sludge in an old radiator circuit.

What to do: check the valves and pressure gauge, then call an engineer to clean the strainer, bleed the system and check the pump.

E15: anti-freeze fault

Haier lists E15 as anti-freeze protection: the hydro unit reports it when the water inlet or outlet temperature is 3°C or below, or when the outlet is 3°C warmer than the inlet with the lower of the two at 10°C or below, for 1 minute. It recovers after 10 minutes and is confirmed after 3 events in an hour. In general, low flow, very cold water or an unheated property triggers it, and scale on the plate heat exchanger adds to the risk.

What to do: keep the system powered through cold weather and check valves are open. A repeat E15 needs a flow check by an engineer.

E87: defrosting with water temperature too low

Haier’s description is that after the defrost electric heater is switched on, if the water outlet temperature is still more than 5°C below the target after 30 minutes, the unit reports E87 and switches the auxiliary heater off. Generally it points to low flow or a very low setpoint, because a defrost needs warm water to work.

E01 to E04, E10, E12, E17 to E19, E20 to E24 and E32: sensor faults

These are indoor and outdoor temperature sensor faults, from the water inlet, outlet, liquid pipe and gas pipe sensors to the tank, zone, pool, defrost coil, ambient, suction, discharge, oil and subcooling sensors. Haier’s trigger is a reading outside the valid range for 60 seconds (30 seconds for the tank and zone sensors), and all are resumable. A loose plug, damaged cable or failed sensor is the usual cause, and Haier’s troubleshooting is to reconnect the sensor, test its resistance and then replace the sensor or the board.

E06 and E07: communication faults

E06 means the indoor unit cannot receive the outdoor unit’s communication signal for 2 minutes. E07 means the wired controller’s data cannot be received for 4 consecutive minutes, and it clears as soon as correct data arrives. General causes are a loose terminal, a damaged cable or electrical interference, and Haier’s flow starts with the communication cable and the DIP switch settings, which are an engineer’s job.

E30, E38 and E40: high pressure faults

E30 is the high pressure switch opening, E40 is high pressure over-high protection, triggered at a discharge pressure of 41.5 bar or an equivalent temperature for 5 minutes, and E38 is the opposite case where the high-side pressure is too low. All three are confirmed after 3 events in an hour and then unresumable. General causes include a blocked heat exchanger, poor water flow, scale on the water side or an incorrect refrigerant charge, so these need a refrigerant engineer.

E39-0 and E49: low pressure faults

E39-0 means suction pressure has dropped too far, with different thresholds in heating and cooling, and E49 is the low pressure switch opening for 5 seconds. Both become unresumable once confirmed. General causes are refrigerant loss, a faulty expansion valve or an outdoor coil iced up after failed defrosts.

E71-0 and E71-1: fan motor faults

These are DC fan motor faults on the upper (E71-0) and lower (E71-1) fan, reported when the fan runs below 20 rpm or below 20 percent of its target for 40 seconds, and confirmed after 3 events in an hour. In general, ice, debris or a seized blade stops the fan, though the motor itself can fail. Clear around the unit by hand, then leave the fan to an engineer.

Which error code might you see in common situations?

What is happening around the house is often the quickest clue to the code. This table matches common situations to codes from Haier’s service manual.

Situation Codes you may see on a Haier First check
Cold snap and iced outdoor unit E15, E87, E39-0, E49, E71-0 Let any defrost finish, then clear snow from around the unit. Never chip at ice on the fins. Our guide to Do Heat Pumps Work in Cold Weather guide shows what is normal
Losing pressure or low pressure E08 Read the gauge and look for drips at radiators and pipework
Radiators lukewarm E08, E12, E16 Check radiator and isolation valves are open
No hot water E10, E68, E69 Check the hot water schedule on the controller, then note the code
After a power cut E114, E121, E124, E06 Wait for the supply to settle, then restart once at the isolator
Unit noisy or fan not spinning E71-0, E71-1, E111-4, E117-4 Look for ice or debris around the fan without reaching inside
After a service or filter clean E08, E06, E07 Check valves were reopened and pressure was restored

How do I reset a Haier heat pump?

It depends on the type of code, because Haier splits its faults into resumable and unresumable. A resumable fault clears itself once the condition behind it goes away, so there is nothing to reset: E08 clears after 5 minutes of normal flow and E15 after 10 minutes. An unresumable fault stays latched once the unit has confirmed it, usually after 3 occurrences within an hour, or 4 for E110.

Haier’s manual does not give a homeowner reset sequence for latched faults, so the safe general approach is:

  1. Write down the full code with any suffix, and where it showed.
  2. Deal with any owner-level cause: restore the pressure, reopen valves, clear the outdoor unit or reset a tripped breaker once.
  3. Switch off at the isolator, wait a few minutes and switch back on.
  4. Give the unit time to restart and check the controller.
  5. If the code returns, leave it and call an engineer.

Resetting again and again without fixing the cause is a bad idea. Latched codes such as E30, E34 and E39-0 are there to protect the compressor, and forcing it to keep running can turn a small fault into an expensive one.

Haier error code list

This list covers every code in Haier’s service manual for the R290 Super Aqua Hydro Split and Hydro All in One. Other Haier models may differ, so check your manual.

Code Meaning Likely cause What to check Who should act
E01 to E04 Hydro unit water inlet, water outlet 2, liquid pipe or gas pipe temperature sensor abnormality (resumable) Open or short circuit for 60 seconds Nothing owner-side Engineer
E05, E33 Indoor or outdoor EEPROM abnormality (unresumable) Board memory or DIP switch setting Nothing owner-side Engineer
E06, E07 Communication error with the outdoor unit (2 minutes) or the wired controller (4 minutes) Cable, terminals, interference, DIP switches Breakers on, one restart Homeowner check, then engineer
E08 Flow switch abnormality or low water flow (no flow signal 120 seconds after pump start) Strainer, closed valves, pump, air, sludge Gauge and valves Homeowner check, then engineer
E09, E11 Indoor unit address duplication; I/O PCB communication abnormality Configuration or wiring Nothing owner-side Engineer
E10, E12, E17, E18, E19 DHW tank, zone 2 mixing valve, zone 1 ambient, zone 2 ambient or pool sensor abnormality Open or short circuit for 30 seconds Nothing owner-side Engineer
E13, E14 Water leakage (reserved); low pressure switch abnormality (reserved) Micro switch; LP switch open 5 seconds Nothing owner-side Engineer
E15 Anti-freeze abnormality (water at 3°C or below) Low flow, cold water, unheated property Power on, heating on, valves open Homeowner check, then engineer
E16 Water inlet or outlet temperature over high (82°C or more for 5 seconds) Control or sensor fault Nothing owner-side Engineer
E20-0, E20-1, E21 to E24, E32-0, E32-1, E65 Outdoor defrost coil, ambient, suction, discharge, oil, subcooling and control box temperature sensor abnormality Open or short circuit for 60 seconds Nothing owner-side Engineer
E27, E34 Oil temperature over high (110°C); discharge temperature over high (115°C) Refrigerant charge, expansion valve Nothing owner-side Engineer
E28, E29 Discharge or suction pressure sensor abnormality Sensor or wiring Nothing owner-side Engineer
E30, E38, E40 High pressure switch abnormality; high pressure over low; high pressure over high (41.5 bar) Blocked exchanger, poor flow, scale, charge Valves open Engineer
E35, E36 Four-way valve reversing abnormality; oil temperature over low Valve or refrigerant circuit Nothing owner-side Engineer
E39-0, E49 Low pressure over low protection; low pressure switch abnormality Refrigerant loss, expansion valve, iced coil Coil clear of ice Engineer
E39-1 Compression ratio over high (10 or more for 1 minute) Refrigerant circuit or airflow Airflow clear Homeowner check, then engineer
E43 Discharge temperature sensor over low protection Sensor or refrigerant circuit Nothing owner-side Engineer
E46, E116, E119, E122 Driver PCB communication, current detection circuit or heat sink sensor abnormality Inverter electronics Nothing owner-side Engineer
E51-0, E51-2, E52-0, E52-2 Expansion valve a or b overcurrent or disconnection Valve coil or wiring Nothing owner-side Engineer
E53, E64, E82, E110, E117 CT current over low or sensor abnormality; CT current over high; compressor current protection; compressor hardware overcurrent; compressor software overcurrent Supply, overload, compressor Nothing owner-side Engineer
E54, E57 to E59 Subcooling module communication and Tc1 or Tc2 sensor errors Module wiring or sensors Nothing owner-side Engineer
E60 to E62, E70 Reserved subcooling module and DHW I/O board codes Reserved Nothing owner-side Engineer
E63, E83 Subcooling module DIP switch error; incorrect outdoor unit DIP switch setting Configuration Nothing owner-side Engineer
E68, E69 Communication error with the DHW I/O PCB; DHW I/O PCB tank temperature abnormality Wiring or sensor Nothing owner-side Engineer
E71-0, E71-1 Upper or lower DC fan motor abnormality (below 20 rpm or 20 percent of target for 40 seconds) Ice, debris, seized blade, motor Fan clear from outside Homeowner check, then engineer
E74 System emergency stop (external interface) External control input Nothing owner-side Engineer
E81, E112, E112-4 Compressor driver PCB temperature over high (85°C); compressor or fan driver heat sink over high (95°C) Blocked airflow, hot conditions Airflow clear Homeowner check, then engineer
E87 Defrosting with water temperature too low Low flow or low setpoint Valves open Engineer
E111, E111-4, E117-4, E118 Compressor or fan motor loss of synchronism; fan motor software overcurrent; compressor start-up abnormality (5 failed starts) Inverter, motor or compressor Nothing owner-side Engineer
E114, E121, E124 Inverter input voltage abnormal (DC bus below 160 V or above 430 V); control board power supply; three-phase power supply abnormality Mains supply Supply stable, one restart Homeowner check, then engineer

Where do I find the Haier fault code list?

Haier HVAC Europe lists the user and installation manual for the R290 Hydro Split and All in One on its product page, under User Manuals. The service manual with the full error code table and troubleshooting flows is published by Haier’s official distributor in Portugal as a direct PDF.

If your controller shows a code that is not in this guide, check the manual for your exact model before acting on it.

When to call an engineer

Call an engineer for a Haier heat pump when E08 or E15 returns after you have checked the pressure, valves and power, when any unresumable code such as E30, E34, E39-0, E40 or E49 appears, or when E06 or E07 stays after one restart. For a suspected refrigerant leak on an R290 unit, keep ignition sources away, isolate the heat pump at the fused spur or isolator and wait for an engineer trained for flammable refrigerants.

UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. A Our repair service begins with reading the code and its trigger from Haier’s table, testing the part behind it and agreeing a quote before any part is fitted.

A lot of the codes above, especially E08, E15 and the pressure faults, are less likely on a well-maintained system, and Why Heat Pump Servicing Is So Important guide explains what the annual visit covers. Our cover plans bundle that service with callouts, and the areas we cover page confirms we reach you. To decide whether a plan suits an R290 system, read Is Heat Pump Cover Worth It guide.

Frequently asked questions

Does a Haier error code void my warranty?

No, a code by itself does not affect your warranty. Problems arise when someone unqualified works inside the unit, or when required servicing has been missed. Check your warranty terms before anyone opens the casing, and keep a note of each code and when it appeared, because Haier’s confirmation rules mean the pattern matters as much as the code.

Does a Haier Super Aqua monobloc use the same codes?

Not necessarily. The published list covers the R290 Super Aqua Hydro Split and Hydro All in One, and we have not verified a code list for the monobloc models. If a code on your unit does not match, use your own manual or send us a photo of the display and the model label.

Does E110 or E82 mean the compressor has failed?

Not always. Haier describes E110 as a hardware overcurrent on the compressor’s rectifier side and E82 as the compressor current exceeding a specified value, and both can come from a poor electrical supply or an overload rather than a failing compressor. An engineer checks the supply, the DC bus voltage and the current sensors before condemning the compressor.

What is the difference between a resumable and an unresumable Haier code?

A resumable code clears on its own once the condition goes, as E08 does after 5 minutes of normal flow. An unresumable code stays latched once the unit has confirmed it, usually after 3 occurrences in an hour, and will not clear until an engineer has dealt with the cause. The remarks column in Haier’s table shows which is which for every code.

What should I note before calling an engineer?

Write down the full code with any suffix, such as -0 or -1, where it showed and when it started. A photo of the model label saves time on the day, and the number on the outdoor unit’s display is worth noting too, because it matches the E code indoors.

Sources and further reading: Haier, R290 Super Aqua Hydro Split and Hydro All in One service manual SYJS-03-2024 Rev.A (March 2024), section 7.1 error codes and 7.2 troubleshooting (distributor-hosted copy); Haier HVAC Europe, R290 Hydro Split product page and user manual. Checked October 2026.