At a glance
- Hitachi Yutaki heat pump error codes are alarm numbers shown on the wired remote controller, such as 70, 83 or 03; water-side alarms 70, 74 and 83 also carry a P-code (P-70, P-74, P-83).
- Alarm 70 is a hydraulic alarm for low flow or a water pump malfunction, and alarm 83 is a hydraulic alarm for low water pressure; both come from the indoor unit’s water cycle PCB.
- Hitachi’s Yutaki S80 commissioning instructions say an alarm is displayed if the space heating water flow falls below 12 litres per minute.
- Alarm 03 means transmission between the units has failed and the outdoor unit is not detected; Hitachi’s own table says the pumps and heaters are still allowed to run but the compressor is not.
- The PC-ARFH2E controller’s Alarm History menu shows each alarm’s code, origin and description, the unit’s previous status, and options to remove or clear alarms.
- Refrigerant cycle alarms such as 2, 7, 8, 45, 47 and 49 need a qualified engineer; Hitachi publishes no owner reset sequence beyond the controller’s alarm history functions.
What do Hitachi Yutaki heat pump error codes mean?
A Hitachi Yutaki heat pump error code is an alarm number the heat pump shows when one of its safety or monitoring checks fails. It appears on the wired remote control switch with an alarm icon, usually as a plain number such as 03 or 70. Some water-side alarms also carry a P-code, so you may see P-70, P-74 or P-83 alongside the number. Hitachi splits its alarms into two groups: those from the water cycle PCB in the indoor unit (3, 10 to 26, 70 to 85 and the 200 series) and those generated by the refrigerant cycle PCB in the outdoor unit (2 to 8, 20 to 59 and EE).
This guide uses the alarm code tables in Hitachi’s PC-ARFH2E wired remote controller manual (PMEN0597 rev.4, August 2025), which cover the Yutaki S, S Combi, M and the RASM outdoor units, together with the Yutaki S80 installation and operation manual. Not every code applies to every model, and the S80 has further alarms in its own service manual, so check your documentation if a code here does not match.
If your Yutaki is not showing a code, or you want to rule out the basics first, our guide to a What to know about Heat Pump Not Working covers the general checks. For other makes, the Heat Pump Error Codes questions answered explains the common codes by brand. One safety line before anything else: switch the unit off at its isolator before you go near it, and never open the casing.
Is it safe to fix a Hitachi heat pump fault yourself?
Only up to a point: basic outside checks are fine on a Yutaki, but anything inside the unit is a job for a qualified engineer. You can read the pressure gauge, check valves are open, clear leaves or snow from the outdoor unit and reset a tripped breaker once.
Never remove panels or touch the electrics inside either unit. Hitachi’s alarm table shows that several codes come from the inverter PCB (51, 53, 54 and 55) and the compressor (EE), which run at mains voltage and can hold a charge.
Refrigerant work is restricted by law to qualified engineers, so any code pointing at refrigerant pressure, discharge temperature or gas shortage (2, 7, 8, 45, 47 and 49) is not a DIY job. Unauthorised work inside the unit can also affect your manufacturer warranty, so check your paperwork before anyone else touches it. If you hear hissing at the outdoor unit or smell burning, isolate the heat pump at the fused spur or isolator and call an engineer.
Which Hitachi error codes can you check yourself?
A handful of Hitachi codes have a realistic homeowner check, mostly the water pressure, flow, freeze protection, airflow and communication alarms: 83, 70, 75, 03, 77, 78, 80 and 57. Everything else needs an engineer.
For alarm 83 (P-83), read the gauge; if you have a filling loop and your manual allows it, top up to the figure your installer gave you. Our guide to the Hitachi alarm 70 and low water pressure faults explains the gauge and filling loop on the Yutaki indoor unit. For alarm 70 (P-70), check the isolation valves near the unit and the radiator valves are open, and keep in mind Hitachi’s 12 litres per minute minimum flow on the S80. For alarm 75, freeze protection by cold water inlet, make sure the heating has not been switched off during a frost. For alarm 03, check the heat pump breakers at the consumer unit are on; Hitachi’s table says the outdoor unit is not detected. For 77 and 78, check the wireless thermostat has power or fresh batteries. For 80, switch off at the isolator, wait a few minutes and restart once. For 57, the fan motor protection, look for ice, leaves or debris around the fan from outside without reaching in; our guide to a Hitachi heat pump with a frozen outdoor unit covers the winter version.
What are the most common Hitachi heat pump error codes?
The Hitachi codes we see most are the water flow and pressure alarms (70 and 83), followed by sensor faults and refrigerant pressure trips. Under each code, the Hitachi meaning comes first. Causes marked general come from engineering experience, not the manual.
70 / P70: water flow or pump alarm
Hitachi calls alarm 70 a hydraulic alarm for low flow and water pump malfunction, originating from the indoor unit, with pumps, heaters and compressor all blocked while it is active. General causes include a blocked strainer, a closed valve, an air lock or sludge in the circuit, and scale inside the plate heat exchanger can restrict flow too.
What to do: check the valves are open and look at the pressure gauge. If it returns, an engineer will clean the strainer, bleed the system and test the pump.
83 / P83: water pressure alarm
Hitachi calls alarm 83 a hydraulic alarm for low pressure, and alarm 84 is the opposite, a high water pressure alarm. Alarm 26 is a water pressure sensor abnormality, which is the sensor itself rather than the pressure. In general, 83 means pressure has dropped through a leak or a failing expansion vessel.
What to do: top up only if you have a filling loop and the manual allows it. If the pressure falls again, there is a leak to find.
74 / P74 and 73: over-temperature protection
Alarm 74 is the unit over-temperature limit protection, and 73 is the mixing over-temperature limit for a mixed second circuit. Generally these follow poor flow or a stuck mixing valve, and they are an engineer fix.
72: thermostat heater alarm
Alarm 72 is the thermostat heater alarm, which Hitachi’s table shows still allows the pumps to run but blocks the heaters and compressor. The general cause is low flow or an air lock around the electric backup heater, so an engineer should bleed the circuit and check flow.
75 and 76: freeze protection
Alarm 75 is freeze protection triggered by the cold water inlet temperature, and 76 is a freeze protection stop triggered by the indoor liquid or gas pipe thermistor. Both keep the pumps and heaters running and stop the compressor. Keep the system powered in cold weather; a repeat needs a flow check.
10 to 19 and 25: thermistor (sensor) faults
These codes mean a temperature sensor is reading abnormally: the second DHW thermistor (10), water inlet (11), water outlet (12), indoor liquid pipe (13), indoor gas pipe (14), water outlet 2 for the mixed circuit (15), DHW tank (16), auxiliary sensors 2, 1 and 3 (17, 18, 25) and the water outlet plate heat exchanger pipe (19). An engineer will check the plug and measure the sensor’s resistance before replacing anything.
03, 04, 80 and 61: communication faults
Alarm 03 means transmission between the units has failed and the outdoor unit is not detected. Alarm 04 is a transmission abnormality between the inverter PCB and the outdoor unit PCB. Alarm 80 is an H-LINK communication failure between the indoor unit and the controller, and 61 means cascade messages have stopped. Check your breakers once, then leave the cabling to an engineer.
2, 45 and 47: refrigerant pressure protection
Alarm 2 means the high pressure cut protection has triggered, 45 is very high discharge pressure protection and 47 is excessively low suction pressure, which Hitachi attributes to multiple origins. General causes are poor water flow or a scaled heat exchanger on the high side and refrigerant loss or an iced coil on the low side. All need an engineer.
7, 8 and 49: discharge gas and gas shortage
Alarm 7 is a decrease in discharge gas superheat and alarm 8 is high discharge gas temperature on the compressor top; both have a retry code, meaning the unit tries again before locking out. Alarm 49 is gas shortage anomaly detection. These are engineer jobs.
Inverter and fan alarms: 51 to 57, 5b and 5C
Alarms 51, 53, 54 and 55 cover the current sensor, inverter PCB protection, excessive inverter PCB temperature and abnormal inverter operation. Alarm 57 is the fan motor protection, and 5b and 5C are outdoor fan over-current and current detection faults. Clear the outdoor unit if the fan is blocked; the rest is engineer work.
Which error code might you see in common situations?
What is happening around the house is often the best clue. These codes are from the PC-ARFH2E controller manual’s tables.
| Situation | Codes you may see on a Hitachi | First check |
|---|---|---|
| Cold snap and iced outdoor unit | 75, 76, 47, 57 | Let a defrost finish, then clear snow from around the unit. Never chip at ice on the fins. Our guide to Do heat pumps work in cold weather in detail shows what is normal |
| Losing pressure or low pressure | 83 / P83, 26 | Read the gauge and look for drips under the indoor unit and radiators |
| Radiators lukewarm | 70 / P70, 73, 74 | Check radiator and isolation valves are open and the pressure is normal |
| No hot water | 16, 10, 72 | Check the hot water schedule on the controller, then note the code |
| After a power cut | 03, 05, 06, 80 | Wait until the supply is stable, then restart once at the isolator |
| Unit noisy or fan not spinning | 57, 5b, 5C, 8 | Look for ice, leaves or debris around the fan without reaching inside |
| After a service or filter clean | 70 / P70, 83 / P83 | Confirm valves were reopened and the pressure was restored |
How do I reset a Hitachi heat pump?
Hitachi does not publish a homeowner reset sequence for the Yutaki range, so the safe option is a simple power restart once the cause has been dealt with. The PC-ARFH2E controller does, however, let you look at what happened: the Alarm History menu inside the Operation Information menu lists the alarms, and pressing OK on one shows the alarm description, the unit’s previous status and the options to remove that alarm or clear all alarms.
- Note the alarm number and any P-code on the controller, and open the Alarm History to read the description and origin.
- Deal with any owner-level cause: top up the pressure, reopen valves, clear the outdoor unit or replace thermostat batteries.
- Switch off at the isolator or breaker, wait a few minutes, then switch back on.
- Check the controller; if the alarm icon is gone, let the unit run and watch for a repeat.
- If the code returns, write it down and call an engineer.
Resetting over and over without fixing the cause is a bad idea. Protection alarms such as 2, 45 and 47 exist to stop the compressor running in conditions that damage it, and the retry codes on alarms 6, 7 and 8 mean the unit has already tried again before showing the alarm. Forcing restarts can turn a small repair into a big one.
Hitachi error code list
This list covers the alarm codes in Hitachi’s PC-ARFH2E wired remote controller manual for the Yutaki S, S Combi, M and RASM outdoor units. Codes specific to the Yutaki S80 service manual are not included, so check your own documentation if a code is missing.
Alarms from the water cycle PCB (indoor unit)
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| 3 | Transmission: outdoor unit not detected | Outdoor unit off, fuse or cable | Breakers at the consumer unit | Homeowner check, then engineer |
| 10 | DHW top thermistor (TDHW2) abnormality | Sensor or connector | Nothing owner-side | Engineer |
| 11, 12 | Water inlet (Twi) or water outlet (Two) thermistor abnormality | Sensor or connector | Nothing owner-side | Engineer |
| 13, 14 | Indoor liquid pipe (Tl) or gas pipe (Tg) thermistor abnormality | Sensor or connector | Nothing owner-side | Engineer |
| 15, 16 | Water outlet 2 (mixed circuit) or DHW tank thermistor abnormality | Sensor or connector | Nothing owner-side | Engineer |
| 17, 18, 25 | Auxiliary temperature sensor 2, 1 or 3 abnormality | Sensor or connector | Nothing owner-side | Engineer |
| 19 | Water outlet plate heat exchanger pipe thermistor abnormality | Sensor or connector | Nothing owner-side | Engineer |
| 26 | Water pressure sensor (WPS) abnormality | Sensor or wiring | Gauge reading | Engineer |
| 33, 34 | Twi or Two thermistor alarm at the mirror module | Sensor or connector | Nothing owner-side | Engineer |
| 40 | Incorrect unit controller (LCD) setting | Configuration | Nothing owner-side | Engineer |
| 60, 61 | Slave units in alarm; no cascade messages | Cascade communication | Nothing owner-side | Engineer |
| 70 (P-70) | Hydraulic alarm: low flow and water pump malfunction | Strainer, closed valve, air, pump | Valves open, pressure normal | Homeowner check, then engineer |
| 72 | Thermostat heater alarm | Low flow or air around the backup heater | Nothing owner-side | Engineer |
| 73, 74 (P-74) | Mixing over-temperature limit (circuit 2); unit over-temperature limit protection | Poor flow, mixing valve | Valves open | Engineer |
| 75, 76 | Freeze protection by cold water inlet; freeze protection stop by indoor liquid or gas thermistor | Cold weather with low flow or heating off | Heating left on in frost | Homeowner check, then engineer |
| 77, 78 | Intelligent wireless receiver failure; RF communication failure (intelligent thermostat) | Thermostat power or batteries | Batteries, receiver powered | Homeowner check |
| 79 | Incorrect capacity setting (not triggered at 3 HP or below) | Configuration | Nothing owner-side | Engineer |
| 80 | H-LINK communication failure between indoor unit and controller | Wiring | One restart | Homeowner check, then engineer |
| 83 (P-83) | Hydraulic alarm: low pressure | Leak, expansion vessel | Gauge, filling loop if permitted | Homeowner check, then engineer |
| 84 | High water pressure alarm | Over-filled system or expansion vessel | Gauge reading | Engineer |
| 85 | Float switch alarm (drain pump error) | Condensate drain | Nothing owner-side | Engineer |
| 202 to 205 | Wrong controller settings; sub room controller or indoor unit stops answering; no central message | Configuration or communication | Nothing owner-side | Engineer |
| 208 to 218 | Repeated H-LINK address, sub DHW on a missing module, alarm on module 1 to 8 (cascade) | Cascade configuration | Nothing owner-side | Engineer |
Alarms generated by the refrigerant cycle PCB (outdoor unit)
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| 2 | Triggering protection of high pressure cut | Poor water flow, scaled exchanger, refrigerant fault | Valves open, pressure normal | Engineer |
| 3, 4 | Transmission abnormality between indoor units; between inverter PCB and outdoor unit PCB | Cable or boards | Breakers on | Engineer |
| 5, 6 | Wrong operation code of power source phase (also wrong compressor connection on Yutaki M); wrong voltage for the inverter | Supply or wiring | Breakers on after a power cut | Engineer |
| 7, 8 | Decrease in discharge gas superheat; high discharge gas temperature on compressor top | Refrigerant charge, expansion valve, fan | Nothing owner-side | Engineer |
| 20, 22, 24 | Thermistor for discharge gas, outdoor ambient or evaporation temperature | Sensor or connector | Nothing owner-side | Engineer |
| 21, 29 | High pressure sensor; low pressure sensor | Sensor or wiring | Nothing owner-side | Engineer |
| 26, 27, 28, 59 | Second evaporation thermistor; economizer thermistor; suction gas thermistor; condensation temperature thermistor | Sensor or connector | Nothing owner-side | Engineer |
| 31, 35, 36 | Incorrect capacity setting; incorrect indoor unit address setting; incorrect indoor unit combination | Configuration | Nothing owner-side | Engineer |
| 38 | Abnormality in the pick-up circuit for protection | Outdoor PCB | Nothing owner-side | Engineer |
| 42, 43, 44 | Pressure ratio decrease; pressure ratio increase; low pressure increase abnormality | Refrigerant circuit | Nothing owner-side | Engineer |
| 45 | Very high discharge pressure protection | Poor flow or refrigerant fault | Valves open | Engineer |
| 47 | Excessively low suction pressure (multiple origins) | Refrigerant loss, iced coil | Coil clear of ice | Engineer |
| 48 | Activation of overcurrent protection (multiple origins) | Supply, compressor or inverter | Nothing owner-side | Engineer |
| 49 | Gas shortage anomaly detection | Refrigerant leak | Nothing owner-side | Engineer |
| 51, 53, 54, 55 | Current sensor abnormality; inverter PCB protection; excessive inverter PCB temperature; abnormal inverter PCB operation | Inverter electronics or cooling | Airflow around the unit | Engineer |
| 57 | Activating the protection of the fan motor | Obstruction, ice or motor | Fan clear from outside | Homeowner check, then engineer |
| 5b, 5C | Outdoor fan over-current protection; abnormality in the fan current detection circuit | Fan motor or board | Fan clear from outside | Engineer |
| EE | Compressor protection | Compressor | Nothing owner-side | Engineer |
Where do I find the Hitachi Yutaki fault code list?
Hitachi publishes its Yutaki manuals and technical catalogues on its official documentation site, with a page for each range, and the alarm code tables sit in the wired remote controller manual (PC-ARFH2E) rather than the outdoor unit manual. Use the page for your model, as alarm lists differ between ranges and the S80 has its own service manual.
- Hitachi Yutaki S manuals, including the PC-ARFH2E controller manual PMEN0597
- Hitachi Yutaki S80 manuals and technical catalogues
- Hitachi Yutaki S Combi manuals and technical catalogues
- Hitachi Yutaki M R32 manuals and technical catalogues
If your controller shows a code that is not in this guide, check the manual for your exact model before acting on it.
When to call an engineer
Call an engineer for a Hitachi Yutaki when alarm 70 or 83 returns after you have checked the valves and pressure, when any refrigerant cycle alarm from the outdoor unit appears, when 72, 73 or 74 shows, or when 03 or 80 stays after one restart with the power confirmed on. For alarm 49, gas shortage, or hissing at the outdoor unit, isolate the heat pump at the fused spur or isolator and wait for an engineer rather than looking for the leak yourself.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We look after Hitachi heat pumps from the Yutaki S and S Combi to the S80 and M, and a Fault diagnosis and repair starts with reading the controller’s alarm history and a quote before any part is fitted.
Many of the codes above, especially the flow, pressure and coil alarms, are less likely on a unit that is looked after, which is the case made in Why heat pump servicing is so important in detail. Our a heat pump service plan include the annual service and cover callouts, and the local heat pump engineers page confirms we reach your postcode. If you are deciding on a plan, our guide to what to know about Is Heat Pump Cover Worth It sets out the trade-offs.
Frequently asked questions
Does a Hitachi error code void my warranty?
No, an alarm number by itself does not touch your warranty. What can affect it is work inside the unit by someone unqualified, or missed servicing if your terms require it. Check your warranty documents before booking anyone, and keep the alarm history on the controller rather than clearing it, because it shows an engineer what happened.
Does a refrigerant pressure code mean the compressor has failed?
Not usually. Alarms such as 2, 45 and 47 are triggered by poor water flow, an iced coil or refrigerant loss, with the compressor shutting down to protect itself, and Hitachi lists 47 and 48 as having multiple origins. Only alarm EE is named compressor protection. An engineer will measure pressures and temperatures before blaming the compressor.
What should I note down before calling an engineer?
Write down the exact code, including any P-code, and when it appeared. Open the Alarm History on the controller and note the origin and description it shows. Add a photo of the controller and the model label, as code lists differ between the Yutaki S, S Combi, S80 and M, and the S80 uses a separate service manual.
Why does my Hitachi show alarm 70 on cold mornings?
Alarm 70 is a flow alarm, and Hitachi’s S80 instructions say the alarm appears if the space heating flow drops below 12 litres per minute. On a cold morning every radiator valve opens at once and a part-blocked strainer or a tired pump may not keep the flow above that line. An engineer will measure the flow, clean the strainer and check the pump setting.
Can a Hitachi code clear itself?
It can, depending on the alarm and what caused it. Hitachi’s refrigerant cycle table gives retry codes for alarms 6, 7, 8, 45, 47 and 48, which means the unit retries before the alarm is shown, and the water cycle table shows which alarms still allow the pumps and heaters to run. A code that disappears after power returns or flow recovers has not necessarily been fixed, so book a visit if it shows more than once in a week.
Sources and further reading: Hitachi (Bosch Home Comfort), PC-ARFH2E wired remote controller installation and operation manual PMEN0597 rev.4 (August 2025), troubleshooting chapter: alarm history menu and alarm codes description; Hitachi, Yutaki S80 installation and operation manual PMEN0648 rev.1 (August 2025), commissioning procedure (12 litres per minute minimum flow); Hitachi UK air source heat pump documentation. Checked October 2026.