At a glance
- Mitsubishi Electric Ecodan error codes are two-character codes such as L9, L6 or E6 shown on the main remote controller, together with which unit raised them.
- L3, L6 and L9 are water-side protection codes (overheat, freeze protection and low flow) and Mitsubishi’s checks for all three are a water leak, a blocked strainer and the circulation pump.
- E0 to E5, E6 to EF and E9 are communication faults; the first check Mitsubishi lists for E6 to EF is that the outdoor unit has not been switched off.
- An Ecodan is reset from the main remote controller by pressing F4 (RESET) then F3 (Yes); “Please Wait” can show for up to 6 minutes after power-up and is normal.
- Codes beginning U, F or A come from the outdoor unit and Mitsubishi refers them to the outdoor unit service manual, so they always need an engineer.
What do Mitsubishi Ecodan heat pump error codes mean?
A Mitsubishi Electric Ecodan error code means the flow temperature controller (FTC) or the outdoor unit has detected a condition outside its limits. The code is a short letter and number pair, such as L9 or E6, and on Ecodan systems with the FTC6 controller the main remote controller shows the code, the unit and address that raised it, and a telephone number if one has been registered. Most Ecodan error codes point to the water circuit, a sensor or a lost connection.
Some have simple causes you can check yourself, like a wireless remote with a flat battery or an outdoor unit that has been switched off at the isolator. Others need an engineer with the right tools and qualifications. Any code beginning U, F or A comes from the outdoor unit and always needs a professional.
If your Ecodan is not showing a code at all, or you want to rule out the basics first, our guide to a Heat Pump Not Working walks through the general checks. For other makes, the Guide to Heat Pump Error Codes covers the common codes brand by brand.
This guide uses the self-check table in the Ecodan FTC6 (PAC-IF071B-E to PAC-IF073B-E) installation manual. Other FTC versions use the same two-character format, but check the installation manual for your own controller if a code here does not match what you see.
Is it safe to fix a Mitsubishi Ecodan fault yourself?
Only basic checks are safe unless you are a competent heating engineer. Reading the pressure gauge on the cylinder or hydrobox, changing remote batteries, checking the isolator and clearing debris from outside the outdoor unit are fine. Mitsubishi’s own operation manual says that users should not try to service or replace parts of the cylinder unit or hydrobox themselves, and that doing so can invalidate the product warranty.
Never remove covers to test thermistors, cables or circuit boards. Those checks mean working near mains voltage, and the actions the FTC6 manual gives for most codes, such as checking resistance across a thermistor, are written for installers rather than homeowners.
Anything involving refrigerant, including checking the charge for a P6 code, is legally restricted to qualified engineers. If you smell burning, hear a loud bang or see water coming from a relief valve in quantity, Mitsubishi’s advice is to switch off power to the heat pump and any immersion heaters and contact your installer; isolate at the fused spur or isolator and do not open anything.
Which Ecodan error codes can you check yourself?
A homeowner can safely check the Ecodan codes linked to power, remote controls and water pressure: J1 to J8, E0 to E5, E6 to EF, E9, L3, L6, L9 and LE. The rest of the list need an engineer.
For J1 to J8, fit fresh batteries in the wireless remote controller and use it closer to the receiver; Mitsubishi’s first check is that the battery is not flat. For E6 to EF and E9, check the outdoor unit’s isolator and breaker are on, because the manual’s first step is to confirm the outdoor unit has not been turned off. For E0 to E5, switch the system off and on once. For L3, L6 and L9, read the pressure gauge, check any valves you closed are open again, and top up only if you have a filling loop and your manual allows it. Our guide to low pressure on a Mitsubishi Ecodan explains what the gauge should read and where the filling loop usually is. For LE on a hybrid system, look at the boiler for its own fault or lockout.
A blank controller screen has no code, but it often means no power. Check the breaker at your consumer unit before calling. If a breaker trips again after one reset, leave it off and book an engineer.
What are the most common Ecodan error codes?
The Ecodan codes we see most are freeze protection, low flow, overheating, high pressure, sensor and communication faults. Mitsubishi’s FTC6 manual does not rank codes by how often they appear. Causes labelled general engineering knowledge come from our experience, not the manual.
L6 and P6: freeze protection
L6 means the circulating water got cold enough to trigger freeze protection. P6 is anti-freeze protection for the plate heat exchanger, where heat passes from refrigerant to water. The manual’s checks for L6 are the same as for L3: a water leak, a blocked strainer and the circulation pump. For P6 it adds checking for the correct amount of refrigerant.
As general engineering knowledge, low flow on a cold night is the usual trigger. Our guide to the Ecodan L6 and P6 freeze protection codes goes into the detail. If either repeats, call us, as P6 may need an engineer.
L9 and LP: low flow
L9 means the flow sensor or a flow switch has detected low flow in the primary circuit. LP means the flow rate is outside the range the outdoor heat pump unit needs. The manual points to the L3 checks for L9 and adds that a flow sensor or switch that does not work itself should be replaced; for LP it points to the installation table and the heat pump flow rate range in the service menu.
As general engineering knowledge, a clogged strainer, trapped air, scale or sludge are the usual causes. An engineer will clean the strainer and test the pump, and a heavily sludged system may need a chemical clean before the code stays away. Mitsubishi warns that the pump valves may be hot, which is one reason strainer cleaning is not an owner job.
L3: water overheating
L3 means the circulating water temperature overheat protection has operated, which the manual says may come from reduced flow. It can also appear while the primary circuit is being filled, in which case the installer finishes filling and resets the code.
As general engineering knowledge, sludge, an air lock or closed zone valves are common causes. If L3 appears out of the blue, book an engineer.
LB: high pressure protection
LB means the refrigerant high pressure protection has operated. The manual lists reduced flow in the heating circuit, a clogged plate heat exchanger or an outdoor unit fault, referring the last to the outdoor unit service manual.
Scale and debris in the plate heat exchanger are typical underlying causes, from general engineering knowledge. This needs an engineer.
L5, L8, P1 and P2: sensor faults
L5 means one of the indoor unit temperature thermistors (THW1, THW2, THW5B, THW6, THW7, THW8 or THW9) has failed. P1 and P2 are the room (TH1) and refrigerant liquid (TH2) thermistors, and L8 is a heating operation error that the manual links to a thermistor that has become dislodged. The engineer’s fix is to check resistance across the thermistor or refit it.
Water in a connector or a damaged cable is a common cause, as general engineering knowledge. There is no safe homeowner check here.
E6 to EF and E9: outdoor unit communication
These mean the FTC and the outdoor unit have lost contact. E9 means the outdoor unit is receiving no signal from the indoor unit. The manual’s first check is that the outdoor unit has not been turned off, then the connection cable for damage or loose connections.
Check the isolator and breaker. If both are on, an engineer needs to test the cable between the two units and may need the outdoor unit service manual.
E0 to E5 and J codes: controller communication
E0 to E5 mean the main remote controller has lost contact with the FTC. J1 to J8 are between a wireless receiver and a wireless remote controller, and the manual’s checks are the battery, the pairing and a wireless test. J0 is between the FTC and the wireless receiver, and J9 is between a main FTC and a sub FTC, both cable faults.
Change the remote batteries first. For E codes or J0 and J9, book an engineer to check the cables.
L4: hot water tank overheating
L4 means the domestic hot water tank temperature overheat protection has operated. The manual’s check is the immersion heater and its contactor, the switch that powers it.
A stuck contactor or a failed thermostat is a likely cause, from general engineering knowledge. Leave this to an engineer, as it involves mains-powered heater controls.
U, F and A codes: outdoor unit faults
Any code beginning U, F or A means an outdoor unit failure. The FTC6 manual does not list these individually and refers engineers to the service manual for your outdoor model.
Note the full code and your outdoor unit model, then book an engineer. Many of these involve the refrigerant circuit or compressor electronics.
Which error code might you see in common situations?
What was happening when the code appeared is often the best clue. These are the Ecodan codes most likely in everyday situations, with the first thing to check.
| Scenario | Codes you may see on an Ecodan | First check |
|---|---|---|
| Cold snap, outdoor unit iced up | L6, P6, or an outdoor U, F or A code | Power is on and snow is clear of the unit. Our guide to Do Heat Pumps Work in Cold Weather explains normal frost and defrost |
| Losing pressure or low pressure | L9, L3, LA | Gauge reading, and whether a relief valve pipe outside is dripping |
| Radiators lukewarm | L9, LP, L3, LB | Timer, holiday or prohibit mode on the controller, then valves |
| No hot water | L4, LJ | Breaker for the immersion heater, and the hot water timer settings |
| After a power cut | E0 to E5, E6 to EF, E9 | Wait: “Please Wait” for up to 6 minutes is normal |
| Unit noisy or fan not spinning | Outdoor U, F or A code | Debris or ice around the fan, with power isolated first |
| After a service or filter clean | L3, L9, L8, LL | Pressure restored and every valve reopened |
A few things are normal and not faults, according to Mitsubishi’s cylinder and hydrobox operation manual. The pump may run for a short time without an obvious reason, which is the pump jam prevention mechanism that inhibits scale build-up. The 3-way valve makes a mechanical noise as it changes between hot water and heating, and the heaters click as they switch. After a power failure all settings are saved for one week.
How do I reset a Mitsubishi Ecodan heat pump?
On an FTC6 Ecodan, you reset the current error from the main remote controller by pressing the F4 (RESET) button and then the F3 (Yes) button. The manual also notes that switching the system off with F4 (RESET) on the main remote controller will cancel error codes.
- Write down the code and the unit it refers to, or photograph the screen.
- Deal with any owner-level cause first: replace remote batteries, switch the outdoor isolator back on, reopen a closed valve or restore the water pressure.
- Press F4 (RESET) on the main remote controller.
- Press F3 (Yes) to confirm.
- Give the system a few minutes to restart. “Please Wait” can show for up to 6 minutes and is normal operation.
If the buttons do nothing, switching the system off and on again at the isolator is the fallback. Do not keep resetting a code that returns. Each restart puts the compressor through another start, and it hides the pattern an engineer needs to see. If “Please Wait” shows a percentage below it and never clears, the manual says that points to a communication error between the controller and the FTC board or between the FTC and the outdoor unit, which is an engineer job.
Ecodan error code list
This list covers every code in the self-check table of the Ecodan FTC6 installation manual (BH79D843H06). Outdoor unit codes are listed by their first letter only, so check the service manual for your outdoor model.
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| L3 | Circulation water temperature overheat protection | Reduced flow: leak, strainer blockage, pump; can show during filling | Pressure gauge, valves open | Homeowner check, then engineer |
| L4 | DHW tank water temperature overheat protection | Immersion heater or its contactor | Nothing owner-side | Engineer |
| L5 | Indoor unit temperature thermistor failure (THW1 to THW9) | Thermistor resistance out of range | Nothing owner-side | Engineer |
| L6 | Circulation water freeze protection | As L3: leak, strainer, pump | Pressure gauge, valves open | Homeowner check, then engineer |
| L8 | Heating operation error | Dislodged thermistor | Nothing owner-side | Engineer |
| L9 | Low primary circuit flow rate detected by flow sensor or flow switch | As L3; faulty flow sensor or switch | Pressure gauge, valves open | Homeowner check, then engineer |
| LA | Pressure sensor failure | Damaged cable or loose connection | Nothing owner-side | Engineer |
| LB | High pressure protection | Reduced heating circuit flow, clogged plate heat exchanger, outdoor unit failure | Valves open | Engineer |
| LC | Boiler circulation water temperature overheat protection (hybrid) | Boiler set point above restriction; reduced flow | Nothing owner-side | Engineer |
| LD | Boiler temperature thermistor (THWB1) failure (hybrid) | Thermistor resistance out of range | Nothing owner-side | Engineer |
| LE | Boiler operation error (hybrid) | As L8; boiler status | Boiler display for its own fault | Homeowner check, then engineer |
| LF | Flow sensor failure | Damaged cable or loose connection | Nothing owner-side | Engineer |
| LH | Boiler circulation water freeze protection (hybrid) | Reduced flow from the boiler: leak, strainer, pump | Nothing owner-side | Engineer |
| LJ | DHW operation error (external plate heat exchanger type) | Disconnected tank thermistor THW5B; reduced sanitary flow; pump | Nothing owner-side | Engineer |
| LL | DIP switch setting error on the FTC control board | SW1-1, SW2-6 or SW2-7 not set for boiler, mixing tank or 2-zone | Nothing owner-side | Engineer |
| LP | Out of water flow rate range for the outdoor heat pump unit | Installation table or service menu flow range; as L3 | Nothing owner-side | Engineer |
| P1, P2 | Room (TH1) or refrigerant liquid (TH2) thermistor failure | Thermistor resistance out of range | Nothing owner-side | Engineer |
| P6 | Anti-freeze protection of plate heat exchanger | As L3, plus refrigerant amount | Pressure gauge, valves open | Engineer |
| J0 | Communication failure between FTC and wireless receiver | Damaged cable or loose connection | Nothing owner-side | Engineer |
| J1 to J8 | Communication failure between wireless receiver and wireless remote controller | Flat battery, pairing, wireless range | Fresh batteries, use the remote nearer the receiver | Homeowner check, then engineer |
| J9 | Communication failure between FTC (Main) and FTC (Sub) | Damaged cable or loose connection | Nothing owner-side | Engineer |
| E0 to E5 | Communication failure between main remote controller and FTC | Damaged cable or loose connection | One restart | Homeowner check, then engineer |
| E6 to EF | Communication failure between FTC and outdoor unit | Outdoor unit turned off; cable damage | Outdoor isolator and breaker on | Homeowner check, then engineer |
| E9 | Outdoor unit receives no signal from indoor unit | A unit switched off; cable damage | Both units switched on | Homeowner check, then engineer |
| EE | Combination error between FTC and outdoor unit | FTC and outdoor unit not a valid combination | Nothing owner-side | Engineer |
| U*, F*, A* | Outdoor unit failure | See outdoor unit service manual | Note the full code and outdoor model | Engineer |
Where do I find the Mitsubishi Ecodan fault code list?
Mitsubishi Electric publishes its Ecodan manuals free in its UK document library. The FTC6 installation manual holds the full self-check code table used in this guide, the FTC7 manual covers the newer PAC-IF08 controllers, and outdoor unit codes are in the service manual for your outdoor model. The cylinder and hydrobox operation manual has the owner troubleshooting table for noises, drips and power cuts.
- Ecodan FTC6 PAC-IF07(1-3)B-E installation manual BH79D843H06
- Ecodan cylinder unit and hydrobox operation manual RG79D942H04
- Mitsubishi Electric UK library: Ecodan controls installation manuals
If your controller shows a code that is not in this guide, check the installation manual for your FTC version and the service manual for your outdoor unit before acting on it.
When to call an engineer
Call an engineer for an Ecodan when a code comes back after one F4 and F3 reset, when L3, L6 or L9 appears with normal pressure and open valves, when any sensor, LB, P6 or outdoor U, F or A code shows, or when water is discharging from a relief valve rather than dripping. Mitsubishi’s instruction for a discharging relief valve is to switch off power to the heat pump and any immersion heaters and contact your installer, so isolate at the fused spur and leave the unit alone.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We repair Mitsubishi Electric heat pumps of every age, from FTC2 cylinders to current FTC7 systems. Every Fault diagnosis and repair starts with fault diagnosis and an agreed quote.
Mitsubishi’s operation manual says maintenance of the cylinder unit and hydrobox should be carried out annually by a competent person, and lists the pressure relief valve, air vents, drain cocks and manometer as parts to replace every six years. That annual visit is where strainers are cleaned and pressure is restored, which heads off L9, L3 and LB before they stop the system. Our annual cover with servicing included include that service, and our engineers across England, Scotland and Wales shows the areas we reach. For a wider view of why the annual visit matters, read Why Heat Pump Servicing Is So Important.
Frequently asked questions
Does an Ecodan error code void my warranty?
No, a code by itself does not affect your warranty. Mitsubishi’s operation manual is clear that users should not service or replace parts of the cylinder unit or hydrobox themselves and that doing so can make the product warranty invalid, so the risk comes from unqualified repairs and gaps in annual servicing, not from the code. Keep your service records and use a certified engineer.
Can I see Ecodan error codes on my phone?
If your system is connected to Mitsubishi Electric’s MELCloud service through a Wi-Fi interface, faults can also appear as alerts in the app. The main remote controller is still the most reliable place to read the full code and which unit raised it, because that is what an engineer will ask for. Our Mitsubishi Ecodan Heat Pump Review guide covers the controls and app in more depth.
Does an outdoor unit code mean the compressor has failed?
Not necessarily. U, F and A codes cover the whole range of outdoor unit faults, and Mitsubishi refers every one of them to the outdoor unit service manual rather than naming a single cause. In our experience many turn out to be a sensor, wiring, the fan or the power supply. An engineer reads the outdoor unit’s own fault history before condemning the compressor.
Why is my Ecodan dripping from the relief valve with no error code?
Mitsubishi’s operation manual says small drips from a relief valve are usually dirt stopping the valve sealing. Its advice is to twist the valve cap until it clicks to flush the dirt, taking care because the water is hot, and to contact your installer if it keeps dripping because the rubber seal may need replacing. A steady discharge means the system has overheated or overpressurised, so switch off and call an engineer.
Why is my Ecodan pipework noisy?
Mitsubishi lists air trapped in the system as the cause of noisy pipework and suggests bleeding radiators where fitted, then contacting your installer if the noise continues. Loose pipework is the other listed cause. Mechanical noise from inside the cylinder unit is usually the heaters switching or the 3-way valve moving between hot water and heating, both of which are normal operation.
Is cover worth having for an Ecodan?
Many Ecodan faults are water-side problems that an annual service prevents, and the rest need an engineer with Mitsubishi diagnostic knowledge. A plan that bundles the annual service with callouts suits owners who want one call when a code appears. Our guide to Is Heat Pump Cover Worth It sets out the trade-offs so you can decide.
Sources and further reading: Mitsubishi Electric, Ecodan FTC6 PAC-IF071B-E to PAC-IF073B-E installation manual BH79D843H06, section 6.2 self-check and section 8 troubleshooting; Mitsubishi Electric, Ecodan cylinder unit and hydrobox operation manual RG79D942H04, troubleshooting and maintenance pages; Mitsubishi Electric UK residential heating document library. Checked October 2026.