At a glance
- Nibe heat pump error codes are alarm numbers with a short name, such as alarm 220 High pressure alarm, shown on the indoor module or SMO controller with the red lamp lit and an alarm icon on the display.
- Alarm 220 means the high pressure switch has tripped 5 times within 60 minutes or for 60 minutes continuously; alarm 221 means the low pressure sensor read too low 3 times within 60 minutes.
- Alarm 228 means 10 failed consecutive defrosts and alarm 183 is simply defrosting in progress; alarm 223 means the controller has lost communication with the outdoor unit.
- Information messages, such as 180 anti-freeze or 165 low pressure in the climate system, light the green lamp, reset themselves and are not written to the alarm log.
- Nibe says there is no harm in acknowledging an alarm on the display, but a recurring alarm means there is a fault in the installation.
- Refrigerant-side alarms such as 221, 230, 232, 261 and 266, and inverter alarms in the 262 to 268 and 421 to 461 ranges, all need an engineer.
What do Nibe heat pump error codes mean?
A Nibe heat pump error code is an alarm number with a short name, such as alarm 220 High pressure alarm, that tells you which part of the heat pump has detected a problem. When an alarm appears, the red lamp on the front lights up, an alarm icon shows on the display, and the display suggests a few things to try first. Nibe’s own advice is to go through those suggested actions before anything else.
On systems with a separate outdoor unit, such as the F2040, F2120 and S2125, the outdoor unit passes its fault to the indoor module or the SMO controller, so that is where you read the number. Exhaust air units like the F750 show alarms on their own display. A green lamp with a service technician symbol is different: it marks an information message, which resets itself once the cause is rectified and is not registered in the alarm log.
If your Nibe is not showing a code, or you want to rule out the basics first, our guide to a guide to Heat Pump Not Working walks through the general checks. Owners of other makes will find their codes in the Heat Pump Error Codes explained. Never open the casing or touch wiring inside the unit, as there are live parts and stored energy in the inverter even after the power is off.
This guide is based on three Nibe documents: the SMO 40 alarm list (TIF EN 2042-1), the F2040 service manual (SEM GB 1503-1) and the F750 service manual (SEM EN 1726-2). The same number can mean different things on different models, so check the alarm list for your own indoor module or controller as well.
Is it safe to fix a Nibe heat pump fault yourself?
Only up to a point: you can make basic outside checks, but anything beyond that is engineer work. Look at the display and follow its suggested actions, check the breaker and the outdoor unit’s isolator, clear leaves or snow from around the outdoor unit and check the system pressure gauge if your installation has one. That is about where it stops for most homeowners.
Never remove panels or touch electrics inside the indoor module or outdoor unit. Many Nibe alarms point to the refrigerant circuit, the inverter or the compressor, and work on the refrigerant side is legally restricted to qualified engineers in the UK. Nibe’s F2040 alarm list is explicit that alarm 222 motor protection and 231 phase fault are to be read against the outdoor unit’s own manual by someone qualified.
There is also your warranty to think about. Manufacturer warranties generally expect the unit to be installed and maintained by competent people, so a DIY repair inside the casing could put that cover at risk. If you smell burning, hear hissing at the outdoor unit or see water leaking from the indoor module, isolate the heat pump at the fused spur or isolator and call an engineer.
Which Nibe error codes can you check yourself?
A handful of Nibe alarms and information messages have simple, safe checks you can do from outside the unit: 183, 180, 165, 224, 228, 223, 229, 220, 184, 268, 998, 271 and 272. Everything else in the full list further down needs an engineer.
Alarm 183 is defrosting in progress and needs nothing but patience; call if it shows for hours or the unit is encased in ice. Message 180 is anti-freeze mode below 3°C outdoors, so just check the house is still warming. Message 165 is low pressure in the climate system, which Nibe attributes to a leak or not enough water in the heating system: read the gauge, look for drips and top up only if you have a filling loop and your manual allows it. Our guide to low pressure on a Nibe heat pump explains where the gauge and filling loop usually sit.
For alarm 224, clear leaves, snow or ice from around the fan guard without reaching inside. For alarm 228, clear snow and ice from around and under the outdoor unit and check the particle filter is not due a clean. For alarm 223, check the outdoor unit’s isolator is on and no breaker has tripped. For alarm 229, open radiator valves and turn up room thermostats that are closed down. For alarm 220, check radiator and zone valves are open and the pressure is in range. For 184, clean the filter as your user manual shows, then acknowledge. For 268 or 998 after a power cut, acknowledge once. For 271 and 272, wait for the weather to change; if either shows in mild weather, Nibe lists a sensor fault as a cause.
What are the most common Nibe heat pump error codes?
The Nibe alarms we see most often relate to defrosting, pressure, flow, communication and sensors. Below, causes listed by Nibe come first, and anything marked as general engineering knowledge is our own experience rather than the manual.
Alarm 228 and 83: defrost failed
Alarm 228 means 10 failed consecutive defrosts on an outdoor unit controlled by an SMO 40, and 83 on the F750 means the defrosting stop conditions have not been met for 3 hours. Nibe’s causes for 228 are a system temperature too low or poor flow, insufficient available system volume, significant wind effect and a clogged particle filter. Alarm 183 on its own is just defrosting in progress and needs no action.
General engineering knowledge: an iced or blocked evaporator, poor airflow round the unit and a frozen condensate drain often sit behind repeat defrost faults. Clear snow and ice from around the unit, then call us if it returns. Our guide to Nibe alarm 228 and 83 defrost faults covers what is safe to do.
Alarm 220 and 50: high pressure
These mean the high pressure switch has tripped: 220 on the outdoor unit when the switch deploys 5 times within 60 minutes or for 60 minutes continuously, and 50 on the F750 when it triggers 3 times within 150 minutes or for 300 minutes continuously. Nibe lists insufficient air circulation or a blocked heat exchanger, a faulty switch or its wiring, a wrongly connected expansion valve, a closed service valve, a faulty outdoor control board, low or no flow in heating, a faulty circulation pump and a blown 4 A fuse. The F2040 manual also says that if the supply to the outdoor unit is switched off and on too quickly, 220 may show and this is normal.
General engineering knowledge: low system pressure, closed isolation or zone valves, an air lock and a blocked strainer all starve the condenser of flow, and sludge or limescale in the plate heat exchanger does the same. Check valves are open, then book an engineer if it repeats.
Alarm 221 and 51: low pressure
This is low pressure in the refrigerant circuit, not the heating water. Alarm 221 means the low pressure sensor has read too low 3 times within 60 minutes, with a faulty sensor or its input, a faulty outdoor control board or the suction gas sensor among Nibe’s causes. Alarm 51 on the F750 means the low pressure switch has tripped and needs a manual reset.
General engineering knowledge: on an air source unit, a frozen evaporator or clogged fins can cause it. There is no homeowner fix beyond clearing the unit, and refrigerant checks need an engineer.
Alarm 223: communication with the outdoor unit
Alarm 223 means communication between the control board and the communication board is interrupted. Nibe lists any circuit breakers for the outdoor unit being in the off position and incorrect cable routing, and says there must be 22 V DC at connector CNW2 on the outdoor control board. Check the isolator and breaker, and leave the cabling to an engineer.
Alarms 301 to 308 are the same type of fault with slave heat pumps in a cascade, where communication has been missing for 15 seconds; Nibe’s action is to check the communication cables.
Alarm 224: fan alarm
Alarm 224 means deviations in the fan speed of the outdoor unit. Nibe lists a fan that is blocked or not connected, a faulty fan motor and a blown fuse, and the F2040 manual adds a dirty control board and the F2 fuse. Clear anything blocking the guard from outside; if the fan still sounds rough or will not spin, book an engineer.
Alarm 229: short run times
Alarm 229 means operation was stopped from the indoor section after less than 5 minutes. Nibe’s causes are poor flow or poor heat transfer and incorrect settings for heating or hot water. General engineering knowledge: low system volume, an oversized unit or an air lock are common causes of short cycling, and it wears the compressor if left.
Alarm 162 and 163: high condenser temperature
Alarm 162 means the condenser outlet has reached its maximum permitted temperature, and 163 the condenser inlet. Nibe lists an incorrectly set heating curve, low heating medium flow and an undersized heating system, and the F2040 manual adds high set temperatures and heat from another source; both self-reset. General engineering knowledge: closed radiator valves and sludge are frequent culprits, so check valves before calling.
Alarm 230 and 261: hot gas and high heat exchanger temperature
Both point to the refrigerant side running too hot. Alarm 230 is a temperature deviation on the discharge sensor, from a disruption in the refrigerant circuit or a lack of refrigerant. Alarm 261 is a temperature deviation on the heat exchanger sensor, from a faulty sensor, insufficient air circulation or a blocked heat exchanger, a faulty control board or too much refrigerant. Keep the unit clear outside; everything else needs an engineer.
Alarms 262 to 268: inverter faults
These cover a power transistor that is too hot (262), inverter voltage outside its parameters (263), a lost link between the inverter and control board (264), a continuous deviation on the power transistor (265), insufficient refrigerant detected at start-up in cooling (266) and a failed compressor start (267). Alarm 268 is overcurrent from a sudden power failure. Apart from acknowledging 268 once after a power cut, these are engineer jobs, and Nibe’s causes for 263 and 267 include supply interference, a closed service valve and a faulty inverter board as well as the compressor.
Sensor alarms: 1, 3, 12 and 277 to 281
A sensor reading is missing, out of range or implausible. Examples are BT1 outdoor (1), BT3 return (3), BT12 supply (12) and the outdoor unit’s Tho-R, Tho-A, Tho-D, Tho-S and low pressure sensors (277 to 281), where the input has received an unreasonably high or low value 3 times within 40 minutes. Nibe’s causes are an open or short circuit on the sensor input and a defective sensor. That is engineer work.
Which error code might you see in common situations?
The situation you are in often narrows down the alarm. This table matches everyday problems to the Nibe codes most likely to appear.
| Scenario | Nibe codes you may see | First check |
|---|---|---|
| Cold snap and iced outdoor unit | 183, 180, 228, 83, 221, 271, 341 | Clear snow and ice from around the unit and let a defrost finish. Our guide to Guide to Do Heat Pumps Work in Cold Weather shows what is normal |
| Losing pressure or low pressure | 165, 220, 50, 55 | Look at the pressure gauge, if fitted, and for drips at valves |
| Radiators lukewarm | 162, 229, 182, 274 | Make sure radiator valves and room thermostats are open |
| No hot water | 6, 340, 64, 273 | Check the display for a hot water block and note the alarm number |
| After a power cut | 268, 998, 223, 437 | Check the breaker and isolator, then acknowledge once |
| Unit noisy or fan not spinning | 224, 222, 218 | Clear the fan guard from outside and listen for scraping |
| After a service or filter clean | 184, 223, 220 | Acknowledge the filter reminder and confirm the isolator is back on |
How do I reset a Nibe heat pump?
You reset most Nibe alarms by acknowledging them on the display, using the option shown on the alarm screen. Nibe’s F2040 manual says there is no harm in acknowledging an alarm, and that if the cause remains the alarm recurs; it adds that recurring alarms mean there is a fault in the installation.
- Note the alarm number and the text, or photograph the display.
- Go through the suggested actions shown on the display, which is Nibe’s first step for any alarm.
- Deal with any owner-level cause: clear the outdoor unit, reopen valves, restore the pressure or switch the outdoor isolator back on.
- Acknowledge the alarm on the display.
- If it returns, leave it and book an engineer.
Nibe’s alarm lists mark each alarm as automatic reset, which clears by itself once the cause has gone, or manual reset, which needs acknowledging on the display. Information messages with the green lamp reset automatically and need no action from you. The exact menu steps vary by model, so follow your user manual rather than guessing.
Avoid switching the power off and on repeatedly to clear a code. On the F2040, quick power cycling can itself trigger alarm 220, and resetting over and over hides the real cause while the unit keeps straining. If an alarm returns after one acknowledgement, that is your cue to book an engineer.
Nibe error code list
This list covers the SMO 40 alarm list, the F2040 and the F750 service manuals. Some numbers mean different things on different models (3, 12 and 254, for example), and the F2120 and S2125 outdoor units share the 220 to 281 range with the F2040 through the SMO controller, so check your own manual too.
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| 1, 3, 6, 12, 14, 15, 16 | Sensor faults: BT1 outdoor, BT3 return, BT6 hot water, BT12 supply, BT14 hot gas, BT15 fluid line, BT16 evaporator | Open or short circuit on the sensor input; defective sensor | Nothing owner-side | Engineer |
| 40 to 42, 43 | Compressor phase 1, 2 or 3 missing for 30 minutes; incorrect phase sequence (F750) | Phase not connected to the soft-start card; wrong phase order | Nothing owner-side | Engineer |
| 44 | Fault in the soft-start fuses (F750) | Defective fuses on the soft-start card | Nothing owner-side | Engineer |
| 50, 150 | High pressure alarm (3 trips in 150 minutes or 300 minutes continuous) and temporary high pressure alarm (F750) | As 220 | Valves open, pressure in range | Homeowner check, then engineer |
| 51 | Low pressure switch triggered (F750), manual reset | Refrigerant circuit | Nothing owner-side | Engineer |
| 52 | Temperature limiter open for more than 30 seconds (F750) | Handled by hardware | Nothing owner-side | Engineer |
| 54 | Motor protection breaker tripped (F750) | Overloaded compressor, mechanical compressor fault, defective switch | Nothing owner-side | Engineer |
| 55, 155 | Hot gas alarm (3 stops in 240 minutes); high hot gas temperature, BT14 above 120°C (F750) | Flow interruption: closed valves, air, pressure too low | Valves open, pressure | Homeowner check, then engineer |
| 56, 57 | Incorrect serial number; serial number and program do not match | Software or commissioning error | Nothing owner-side | Engineer |
| 64 | Exhaust air temperature 16°C or lower for one hour (F750) | Low exhaust air temperature | Ventilation not blocked | Homeowner check, then engineer |
| 70 to 72 | Communication fault with the input, base or soft-start card | Defective communication cables | Nothing owner-side | Engineer |
| 73 to 91, 96 to 99 | Communication fault with an accessory board or a room unit | Cables, DIP switch, accessory activated but not connected, no supply to the board | Nothing owner-side | Engineer |
| 83 | Defrosting stop conditions not met for 3 hours (F750) | Ventilation flow, exhaust air temperature | Filter and vents clear | Homeowner check, then engineer |
| 100 | Communication with the inverter missing for 15 seconds (F750), manual reset | Cables or inverter | Nothing owner-side | Engineer |
| 162, 163 | Condenser out or condenser in at maximum permitted temperature | Heating curve, low flow, undersized system, another heat source | Radiator valves open | Homeowner check, then engineer |
| 165 | Low pressure in the climate system (information) | Leak or not enough water in the heating system | Gauge, visible drips | Homeowner check, then engineer |
| 180 | Anti-freeze active below 3°C outdoors (information) | Cold weather with heating not permitted | House still warming | Information only |
| 182, 274, 275 | Load monitor active or limiting the compressor | Phase loading; main fuse too small | Nothing owner-side | Engineer or electrician |
| 183 | Defrosting in progress (information) | Normal operation | Nothing | No action |
| 184 | Filter alarm: time set in the filter menu has expired (information) | Filter due for cleaning | Clean the filter as the user manual shows | Homeowner check |
| 203 to 205 | Inverter alarm types I to III (F750) | Inverter alarms 213 to 215 repeated or active for 60 minutes | Nothing owner-side | Engineer |
| 218 | Compressor rotor blocked | Defective compressor | Nothing owner-side | Engineer |
| 220 | High pressure switch deployed 5 times in 60 minutes or for 60 minutes continuously | Blocked airflow or exchanger, switch or wiring, closed service valve, low flow, pump, 4 A fuse | Valves open, pressure, airflow | Homeowner check, then engineer |
| 221 | Low pressure sensor too low 3 times within 60 minutes | Sensor, outdoor control board, suction gas sensor | Unit clear of ice | Engineer |
| 222, 231 | Motor protection alarm (alarm 7 from outdoor unit); phase fault (alarm 18 from outdoor unit) | See the outdoor unit manual | Nothing owner-side | Engineer |
| 223 | Communication fault from the heat pump (22 V DC missing at CNW2) | Outdoor breakers off; incorrect cable routing | Isolator and breaker on | Homeowner check, then engineer |
| 224 | Fan alarm: deviations in fan speed | Fan blocked or not connected, faulty motor, blown fuse | Fan guard clear from outside | Homeowner check, then engineer |
| 225 | Return hotter than supply: flow and return mixed up | Pipe connections swapped | Nothing owner-side | Engineer |
| 227 | Sensor fault from heat pump | Sensor not connected or defective | Nothing owner-side | Engineer |
| 228 | 10 failed consecutive defrosts | Low system temperature or poor flow, low system volume, wind, clogged particle filter | Unit clear of snow and ice | Homeowner check, then engineer |
| 229 | Operation stopped from the indoor section after less than 5 minutes | Poor flow or heat transfer; incorrect settings | Radiator valves and thermostats open | Homeowner check, then engineer |
| 230, 261 | Hot gas alarm; high heat exchanger temperature | Refrigerant circuit disruption, lack of or too much refrigerant, blocked exchanger, sensor, board | Unit clear outside | Engineer |
| 232 | 5 low evaporation temperature alarms within 4 hours | Lack of refrigerant, blocked expansion valve, wind | Nothing owner-side | Engineer |
| 250, 251 | Communication with the SMS or Modbus accessory missing for 15 seconds | Accessory communication | Nothing owner-side | Engineer |
| 254 | Communication fault with the accessory card (F2040) | Outdoor unit unpowered; communication cable | Isolator on | Engineer |
| 262 to 265, 267 | Inverter faults: power transistor too hot, voltage outside parameters, lost communication, continuous deviation, failed compressor start | Unstable 15 V supply, supply interference, closed service valve, refrigerant, inverter or control board, compressor | Nothing owner-side | Engineer |
| 266 | Insufficient refrigerant detected at start-up in cooling | Closed service valve, loose or faulty BT15 or BT3, low refrigerant | Nothing owner-side | Engineer |
| 268 | Overcurrent in the inverter after a sudden power failure | Power cut | Acknowledge once after the power is back | Homeowner check, then engineer |
| 271, 272 | Outdoor air too cold or too warm for the outdoor unit’s working range | Weather; sensor fault if it shows in mild weather | Wait for the weather to change | Homeowner check |
| 277 to 281 | Outdoor unit sensor faults: Tho-R, Tho-A, Tho-D, Tho-S, low pressure sensor (3 times in 40 minutes) | Open or short circuit; defective sensor | Nothing owner-side | Engineer |
| 294 | Incompatible outdoor unit | Failed upgrade, no software, DIP switches, wrong combination | Nothing owner-side | Engineer |
| 301 to 308 | Communication with slave heat pump 1 to 8 missing for 15 seconds | Communication cables | Nothing owner-side | Engineer |
| 340 | Supply air sensor BT22 below 11°C, hot water blocked (F750) | Low supply air temperature | Nothing owner-side | Information only |
| 341, 344, 346 | Recurring safety defrost; recurring low pressure; recurring high pressure (alarms from the outdoor unit) | Iced outdoor unit, sensor, refrigerant circuit | Unit clear of ice | Engineer |
| 404 | Sensor fault BP4, high pressure heating or low pressure cooling (F2040) | Open or short circuit; defective sensor or board | Nothing owner-side | Engineer |
| 421 to 461 | Inverter alarms: communication, triggered pressure switch, safety stops, high or low mains voltage, missing phase, mains disturbance, overheated inverter, high current, phase drop, failed starts, high current or power load | Main and group fuses and cable connections, supply voltage, inverter cooling, compressor | Breakers after a power cut | Engineer |
| 900 | Country not selected | Commissioning setting | Nothing owner-side | Engineer |
| 998 | Display has restarted after a temporary dip in the power supply | Power dip | None needed | No action |
Where do I find the Nibe fault code list?
Nibe publishes its service manuals and alarm lists as PDFs on its own document store, and these are the documents this guide is based on. The alarm list for your indoor module or controller is the one to use, because the outdoor unit’s alarms are displayed there.
- NIBE SMO 40 alarm list (TIF EN 2042-1)
- NIBE F2040 service manual (SEM GB 1503-1)
- NIBE F750 service manual (SEM EN 1726-2)
If your display shows a number that is not in this guide, check the installation manual for your own model before acting on it.
When to call an engineer
Call an engineer for a Nibe heat pump when an alarm returns after one acknowledgement, when 221, 230, 232, 261 or 266 appears at all, when any inverter alarm in the 262 to 268 or 421 to 461 ranges shows other than 268 after a power cut, or when message 165 keeps coming back after a top-up. Isolate the heat pump at the fused spur or isolator first if there is a burning smell, hissing at the outdoor unit or water leaking from the indoor module, and do not touch the refrigerant pipework.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We work on Nibe heat pumps from F2040 and F2120 air source units to F750 exhaust air units and the S series, and a Heat pump repairs starts with reading the alarm log and testing sensors, flow and the refrigerant circuit before a quote.
Many of the alarms above, especially flow, defrost and high pressure faults, are far less likely on a unit that is looked after; guide to Why Heat Pump Servicing Is So Important explains what the yearly visit prevents. A heat pump cover plans from us bundles that annual service with callouts, and our find your nearest engineer lists the areas we reach. If you are weighing up a plan, read guide to Is Heat Pump Cover Worth It.
Frequently asked questions
Does a Nibe alarm void my warranty?
No, an alarm on its own does not affect your warranty, because it is the unit protecting itself. Problems tend to arise when a fault is ignored for a long time or someone without the right qualifications opens the unit. Check your warranty terms, keep a record of each service and quote the alarm number when you call.
Are Nibe alarms stored after they clear?
Yes. Nibe’s SMO 40 alarm list says information messages are not registered in the alarm log, which is the clue that proper alarms are, so an engineer can see what happened even after you acknowledge one. Green-lamp information messages simply disappear once the condition has passed. Write down any alarm number and the time it appeared, as that speeds up diagnosis.
Can I see Nibe alarms on my phone?
If your heat pump is connected to the internet through Nibe’s online service, alarms can show in the app as well as on the display. Not every installation is connected, so ask your installer if you are unsure. The app tells you a fault exists but does not replace a visit when the alarm keeps coming back. Our Nibe Heat Pump Review explained covers the controls in more detail.
Does a Nibe alarm mean the compressor has failed?
Usually not. Most Nibe alarms carry the action “compressor is blocked”, which is a protective state, not a failure. Alarm 218 is the only one in these lists that names a blocked compressor rotor as the cause; inverter alarms such as 449 failed compressor starts list fuses, cable connections and the inverter before the compressor itself. An engineer tests those first.
Why does my Nibe show alarm 220 after a power cut?
Nibe’s F2040 manual says that if the voltage supply to the outdoor unit is switched off and on too quickly, alarm 220 may be displayed and this is normal. A power cut that flickers can do the same. Acknowledge it once with the power restored; if it returns with no further interruption, the usual high pressure causes, from poor flow to a blocked coil, need checking.
Sources and further reading: NIBE, Technical information: alarm list SMO 40 (TIF EN 2042-1), alarm and information messages; NIBE, F2040 service manual (SEM GB 1503-1), chapter 5 troubleshooting; NIBE, F750 service manual (SEM EN 1726-2), chapter 6 alarm list. Checked October 2026.