Panasonic Aquarea Heat Pump Error Codes: Meanings, Causes, Fixes & What to Do

Panasonic Aquarea error codes explained guide tile: a hand holding a smartphone showing the Panasonic Aquarea Smart Cloud app
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

Panasonic Aquarea heat pump error codes are a letter and two digits on the remote controller, such as H62, H21 or F12. This guide lists the codes from Panasonic's own installation and self-diagnosis documents, explains what each means, which checks are safe for an owner, how resets work and when to call an engineer.

At a glance

Get a cover plan here >

  • Panasonic Aquarea error codes are a letter and two digits on the remote controller, such as H62 or F12: H codes cover the indoor unit, water circuit, sensors and communication, and F codes cover the outdoor unit and refrigerant circuit.
  • H62 is a water flow fault that trips after 10 seconds of low flow; Panasonic’s UK installation guide says it is usually a low flow rate from a blocked Y strainer, an air lock, a closed valve or a pump that cannot overcome the system’s head loss.
  • H21 is an abnormal water pressure fault detected over 300 seconds, with a faulty pressure transducer or a water leak as the listed causes.
  • Panasonic’s UK installation guide says the system should be filled to around 2 bar, with a minimum of 1.5 bar.
  • H42 (low compression pressure), H98 (high pressure protection in heating) and H99 (indoor heat exchanger freeze protection) all involve the refrigerant circuit and need a qualified engineer.
  • H00 means no abnormality has been detected and needs no action.

What do Panasonic Aquarea heat pump error codes mean?

A Panasonic Aquarea error code means the heat pump has detected a condition outside its limits and has stopped or protected itself. The code is a letter and two digits on the remote controller display, such as H62 or F12, and the letter tells you which side of the system has the problem. H codes cover the indoor unit, the water circuit, sensors and communication. F codes cover the outdoor unit, the compressor drive and the refrigerant circuit.

Panasonic’s UK installation guide says that when an abnormality occurs the system stops, the OFF/ON LED on the control panel blinks and the error code is shown on the control panel. Most codes also carry a detection time or a repeat count: a sensor fault is usually confirmed after 5 seconds, while F12 needs four high pressure switch trips in 20 minutes before the code locks in. One rule matters more than the rest: never open the indoor or outdoor unit or touch wiring inside, as both carry mains voltage.

If your Aquarea is not showing a code, or you want to rule out the basics first, our guide to a Heat Pump Not Working explained walks through the general checks. If you own a different make, the What to know about Heat Pump Error Codes links to the other brands.

This guide uses two Panasonic documents: the UK Aquarea Installation Guide for the H and J generation monobloc units, and the Panasonic Pro Club Aquarea self-diagnosis guide covering generations H, J, K and L, which is published in Polish but carries the full code table. Older Aquarea generations may use fewer codes, so check your own manual if a code reads differently.

Is it safe to fix a Panasonic Aquarea heat pump fault yourself?

Only the basics are safe for a homeowner on an Aquarea: reading the code, checking the power supply, clearing the outdoor unit and checking the system pressure on the gauge. Panasonic itself treats almost every code as installer work, and its UK installation guide ends most troubleshooting flows with “refer to service manual or call tech support”.

Do not remove covers or touch electrics inside the unit. Most F codes relate to the outdoor unit, the inverter or the refrigerant circuit, and in the UK refrigerant work can only legally be done by a qualified engineer. The back-up heater behind H70 and the tank heater behind H91 are mains-powered, so their overload stats are an engineer’s job to reset.

Think about your warranty too. Manufacturer warranties generally expect qualified installation and maintenance, so opening the unit yourself could cause problems with a claim later. If you smell burning, hear hissing at the outdoor unit or see water running from the indoor unit, isolate the heat pump at the fused spur or isolator and call an engineer.

Which Panasonic Aquarea error codes can you check yourself?

A few Aquarea codes have a realistic, safe check you can make before calling anyone: H62, H21, H42, H98, H70, F15, F41, H76 and F32. The rest need an engineer.

For H62, check the isolation valves on the pipes under the unit are open and the pressure gauge reads normally; Panasonic’s UK guide lists an air lock, a closed valve and a blocked Y strainer among the causes. For H21, read the pressure gauge; Panasonic’s installation guide says the system should sit at around 2 bar with a minimum of 1.5 bar, so if you have a filling loop and your manual allows it, top up to the marked level and look for drips. Our guide to the Panasonic H62 and H21 flow and pressure faults covers where the gauge and filling loop are on the indoor unit. For H42, clear leaves, snow or debris from the outdoor coil and around the unit. For H98, check radiator valves are open, then reset once.

For H70, Panasonic’s guide says to make sure the heater is free from air, so bleed radiators if you are used to doing it, then leave the overload stat to an engineer. For F15, look for anything jamming the fan guard from outside and clear it. For F41, which Panasonic links to mains voltage spikes, reset once after a power cut. For H76, check the controller screen is lit, then try one reset. For F32, compare the room temperature shown with a separate thermometer, because the fault is the controller’s built-in thermostat. Stop and call an engineer if any code returns after one check and one reset.

What are the most common Panasonic Aquarea heat pump error codes?

The Aquarea codes we are called out for most are water flow, pump, pressure and freeze protection faults, followed by sensors and communication. Panasonic’s listed causes come first in each entry; anything marked general engineering knowledge is our own experience, not the manual.

H62: water flow fault

H62 means the flow sensor has detected a problem with the primary flow rate, which the UK installation guide says is usually because the flow rate is too low. The self-diagnosis table gives a 10 second detection time and names the water flow sensor as the component. Panasonic’s UK troubleshooting flow asks three questions: can the pump overcome the system head loss (if not, use hydraulic separation), is the Y strainer blocked (clean it), and is there an air lock or closed valve (vent the system and open all valves).

General engineering knowledge: sludge in the primary circuit, a weak pump and an undersized or throttled circuit are frequent underlying causes. Check the valves are open, reset once, and call us if H62 returns.

H20: water pump fault

H20 means the water pump is not operating correctly, detected over 5 seconds. Panasonic lists a fault on the indoor unit control board and a failed circulation pump as the causes. General engineering knowledge: sludge and magnetite are usually behind a seized or struggling pump, which is why an engineer checks the strainer and the water quality before fitting a new pump.

H21: water pressure fault

H21 means abnormal water pressure, detected over 300 seconds. Panasonic lists a faulty water pressure transducer or a water leak from the hydraulic system. General engineering knowledge: check the gauge first, because low pressure after a leak or a slow loss is the usual trigger, and an expansion vessel that has lost its charge will show the same symptom.

H42: low compression pressure in heating

H42 is the outdoor unit’s protection against low compression pressure. Panasonic lists the outdoor temperature sensor, a blocked expansion valve or filter, insufficient refrigerant, the outdoor control board and the compressor as causes. General engineering knowledge: a dirty or iced outdoor coil restricts airflow and produces the same low pressure, so H42 often shows in a cold snap. Our guide to the Panasonic H99 and H42 freeze protection codes explains what is normal frost and what is not. Refrigerant checks need an engineer.

H98 and F95: high pressure protection

H98 is the outdoor unit’s protection against excessive refrigerant pressure in heating mode, and F95 is the same protection in cooling. For H98 Panasonic lists the outdoor high pressure sensor, the circulation pump or a water leak, a blocked expansion valve or filter, too much refrigerant and the outdoor control board. General engineering knowledge: poor water flow from air locks, scale or sludge raises head pressure, so rule out H62-type causes first and reset only once.

H99: indoor freeze protection

H99 means the indoor heat exchanger freeze protection has operated. Panasonic lists the indoor heat exchanger itself and a refrigerant shortage. General engineering knowledge: very low water flow can let the plate heat exchanger get that cold, so air locks and sludge are worth checking. This is an engineer visit.

A related code, H65, is a defrost water circulation abnormality on two-fan units. Panasonic defines it as flow above 7 litres per minute for 20 seconds during defrost mode 2, and names the circulation pump, because water should not be flowing through the exchanger at that point.

H90 and H76: communication faults

H90 means the indoor and outdoor units have lost communication for more than a minute after start-up, and Panasonic points to the indoor to outdoor wiring and the two control boards. H76 means the indoor unit cannot communicate with the control panel, with a disconnected or damaged controller as the cause. Beyond checking power and the controller display, these need an engineer.

Sensor codes

More than twenty Aquarea codes are sensor faults, including H15, H23, H28, H31, H36, H43, H44, H67, H68, H72, F30, F36, F37, F40, F42, F43, F45, F48 and F49. Panasonic lists a disconnected or damaged sensor for each, usually detected after 5 seconds, and for the optional sensors (H36, H43, H44, H67, H68, H72) the UK guide also asks whether the setting that expects the sensor should be switched off. An engineer checks the sensor’s resistance against its curve and replaces what has failed.

F12 to F29: refrigerant and drive faults

These include the high pressure switch operating four times in 20 minutes (F12), abnormal compressor speed (F14), excessive input current (F16), compressor overheat protection (F20), inverter module overheat (F22), excessive compressor output current (F23) and a refrigerant cycle abnormality (F24). Panasonic’s causes include refrigerant shortage or excess, a blocked expansion valve or filter, the outdoor control board and, for F23, too small a hot water coil or too little water in the heating system. They need an engineer. They do not automatically mean the compressor has failed.

Which error code might you see in common situations?

What was happening when the code appeared usually points to the right one. Here are the Aquarea codes most linked to everyday situations.

Scenario Aquarea codes you may see First check
Cold snap and iced outdoor unit H42, H99, H65, F43 Clear snow and ice from around the unit and let it defrost. Our guide to Do Heat Pumps Work in Cold Weather explained explains normal frost
Losing pressure or low pressure H21, H62 Read the pressure gauge and look for drips at valves and joints
Radiators lukewarm H62, H75, H20 Check isolation and radiator valves are open
No hot water H72, H91 Note the code and check the heating still works
After a power cut F41, H95, H90 Check the breaker, then do one reset
Unit noisy or fan not spinning F15, H42 Look for anything blocking the fan from outside
After a service or filter clean H62, H70, H76 Confirm valves were reopened, the system is back to around 2 bar and the controller is lit

How do I reset a Panasonic Aquarea heat pump?

You reset an Aquarea code from the remote controller once the cause has been dealt with. Panasonic’s operating instructions for each controller generation describe an error reset function on the controller, and the button sequence differs between the older button controllers and the current touch-style controllers, so follow the steps in the operating instructions for your own model rather than a generic sequence.

  1. Write down the code and the time it appeared; the OFF/ON LED blinking confirms the system has stopped on a fault.
  2. Deal with any owner-level cause: open a closed valve, bring the pressure back to the installer’s figure, clear the outdoor unit or check the breaker.
  3. Use the error reset function described in your controller’s operating instructions.
  4. If the controller does not respond, switch the heat pump off at the isolator, wait a few minutes and switch it back on.
  5. If the code comes straight back, the fault is still there and needs an engineer.

Panasonic’s self-diagnosis guide adds that a soft reset of the controller is expected after any change to installer settings, and that a soft reset keeps settings and energy data while a hard reset wipes them. Resist the urge to keep resetting. Each restart puts the compressor through another start under the same fault, and with flow or pressure codes that can turn a minor problem into a costly one.

Panasonic Aquarea error code list

This list is based on the Panasonic Pro Club self-diagnosis table for Aquarea generations H, J, K and L, cross-checked against the UK installation guide for the H and J generation. Detection times are as Panasonic states them. Older Aquarea models may use fewer or different codes, so check your own manual if a code is missing or reads differently.

Code Meaning Likely cause What to check Who should act
H00 No abnormality detected None Nothing No action
H12, H38 Indoor and outdoor units of mismatched capacity or model (90 seconds after power-on) Wrong combination, wiring or control boards Nothing owner-side Engineer
H15 Outdoor compressor temperature sensor fault (5 seconds) Sensor disconnected or damaged Nothing owner-side Engineer
H20 Water pump abnormality (5 seconds) Indoor control board or circulation pump Nothing owner-side Engineer
H21 Abnormal water pressure (300 seconds) Pressure transducer or water leak Gauge, visible drips Homeowner check, then engineer
H23 Indoor refrigerant liquid pipe temperature sensor (5 seconds) Sensor disconnected or damaged Nothing owner-side Engineer
H27 Service valve error (5 minutes) Service valves, high pressure transducer or liquid pipe sensor Nothing owner-side Engineer
H28, H31, H36 Solar, swimming pool or buffer tank sensor fault (5 seconds) Sensor disconnected or damaged, or setting expects a sensor not fitted Nothing owner-side Engineer
H42 Low compression pressure protection Outdoor sensor, blocked EEV or filter, low refrigerant, outdoor board, compressor Coil clear of leaves, snow and ice Homeowner check, then engineer
H43, H44 Zone 1 or zone 2 water temperature sensor (5 seconds) Sensor missing or not wired to the optional board Nothing owner-side Engineer
H62 Abnormal water flow (10 seconds) Low flow: strainer, air lock, closed valve, pump head Valves open, pressure normal Homeowner check, then engineer
H63 Low pressure sensor fault (4 times in 20 minutes) Sensor damaged or disconnected Nothing owner-side Engineer
H64 Abnormally high refrigerant pressure (5 seconds) Outdoor high pressure sensor damaged or disconnected Nothing owner-side Engineer
H65 Defrost water circulation abnormality (two-fan units) Circulation pump; flow above 7 l/min for 20 seconds during defrost Nothing owner-side Engineer
H67, H68 External room thermistor 1 or 2 (5 seconds) Thermistor missing or not wired; zone setting expects one Nothing owner-side Engineer
H70 Back-up heater overload protection (60 seconds) OLP stat open, power supply 2 missing, heater overheated, air in heater Bleed radiators if you are used to it Homeowner check, then engineer
H72 Hot water tank sensor fault (5 seconds) Tank sensor disconnected or damaged; tank setting on with no tank Nothing owner-side Engineer
H74 Communication error with the optional expansion board Indoor control board or CZ-NS4P board Nothing owner-side Engineer
H75 Low water temperature control Water flow through the plate exchanger too low; back-up heaters not working Valves open Engineer
H76 Indoor unit to control panel communication Controller disconnected or damaged Controller screen lit; one reset Homeowner check, then engineer
H90 Indoor to outdoor communication (over 1 minute) Interconnecting wiring or control boards Breaker on Engineer
H91 Tank heater overload protection (60 seconds) Tank heater OLP disconnected or tripped Nothing owner-side Engineer
H95 Abnormal voltage between indoor and outdoor units Supply voltage or control cable Breaker on after a power cut Engineer
H98 High pressure protection, heating mode High pressure sensor, pump or leak, blocked EEV or filter, excess refrigerant, outdoor board Radiator valves open; one reset Homeowner check, then engineer
H99 Indoor heat exchanger freeze protection Indoor heat exchanger or refrigerant shortage Nothing owner-side Engineer
F12 High pressure switch operated (4 times in 20 minutes) High pressure switch Nothing owner-side Engineer
F14 Abnormal compressor speed (4 times in 20 minutes) Compressor Nothing owner-side Engineer
F15 Outdoor DC fan motor locked (2 times in 30 minutes) Outdoor control board or fan Fan guard clear from outside Homeowner check, then engineer
F16 Excessive input current (3 times in 20 minutes) Excess refrigerant or outdoor board Nothing owner-side Engineer
F20 Compressor overheat protection (4 times in 30 minutes) Compressor sensor, blocked EEV or filter, refrigerant leak, outdoor board, compressor Nothing owner-side Engineer
F22 Inverter module (IPM) overheat (3 times in 30 minutes) Poor heat dissipation from the inverter heat sink Nothing owner-side Engineer
F23 Excessive compressor output current (7 times in a row) Outdoor board, compressor, undersized hot water coil, too little water in the heating system Nothing owner-side Engineer
F24 Refrigerant cycle abnormality (2 times in 20 minutes) Refrigerant leak, outdoor board, weak compression Nothing owner-side Engineer
F25 4-way valve fault (4 times in 30 minutes) 4-way valve or its coil plug Nothing owner-side Engineer
F27 High pressure switch fault (60 seconds) High pressure switch Nothing owner-side Engineer
F29 Low discharge temperature Discharge sensor, high pressure sensor or switch, outdoor board Nothing owner-side Engineer
F30, F37, F45 Water outlet 2, water inlet or water outlet temperature sensor (5 seconds) Sensor disconnected or damaged Nothing owner-side Engineer
F32 Built-in controller thermostat abnormal (5 seconds) Controller thermostat; room temperature reading wrong Compare with a separate thermometer Homeowner check, then engineer
F36, F40, F42, F43 Outdoor air, discharge, outdoor heat exchanger or defrost sensor (5 seconds) Sensor disconnected or damaged Nothing owner-side Engineer
F41 Power factor correction (PFC) fault (4 times in 10 minutes) Mains voltage spikes One reset after a power cut Homeowner check, then engineer
F46 Outdoor current transformer open circuit Insufficient refrigerant, outdoor board, weak compression Nothing owner-side Engineer
F48, F49 Evaporator outlet or bypass outlet temperature sensor (5 seconds) Sensor disconnected or damaged Nothing owner-side Engineer
F95 High pressure protection, cooling mode As H98, in cooling Nothing owner-side Engineer

Where do I find the Panasonic Aquarea fault code list?

Panasonic’s UK Documents and Support page holds the operating instructions for owners, and its Pro Club site hosts the installer guides and the self-diagnosis document this guide draws on. The self-diagnosis document is in Polish, but its code table, detection times and component lists are easy to follow, and it covers generations H, J, K and L.

If your controller shows a code that is not in this guide, check the installation manual for your exact model before acting on it.

When to call an engineer

Call an engineer for an Aquarea when H62 or H21 returns after you have checked the valves and pressure, when H42, H98, H99 or any F code appears, when H70 or H91 trips more than once, or when the controller shows H90 or H76 with the power confirmed on. Isolate the heat pump at the fused spur or isolator first if you smell burning, hear hissing at the outdoor unit or see water running from the indoor unit, and do not touch the refrigerant pipework.

UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We work on Panasonic heat pumps across the monobloc, bi-bloc and all-in-one ranges, and a Our repair service begins with reading the code, testing sensors and flow, and a quote before any part is fitted.

Many Aquarea codes, H62, H20 and H42 among them, trace back to sludge, a blocked Y strainer or a dirty coil, which is exactly what an annual service deals with; read Why Heat Pump Servicing Is So Important explained for the detail. Our service and cover plans bundle the annual service with callouts, and our the towns and cities we cover confirms the areas we reach. If you are deciding whether a plan suits you, our guide to Is Heat Pump Cover Worth It explained sets out the costs and benefits.

Frequently asked questions

Does an Aquarea error code void the warranty?

No, a code is the heat pump protecting itself and does not affect your cover by itself. Warranty trouble usually comes from ignoring a fault for weeks or from unqualified work inside the unit, because manufacturers expect qualified installation and maintenance. Our Panasonic Aquarea Heat Pump Review covers what to keep in mind when you own one.

What does H00 mean on an Aquarea?

H00 means no abnormality has been detected, and Panasonic’s self-diagnosis table lists no detection time or component against it. You might see it when checking the error display, and it needs no action. If the heating still is not working with H00 showing, the cause lies outside the unit’s self-diagnosis, for example a controller setting or an external thermostat, so book a check.

Why would I see F25 or F95 if I only use heating?

Both relate to cooling: F25 is a 4-way valve fault, the valve that switches the outdoor unit between heating and cooling, and F95 is high pressure protection in cooling mode. Seeing one on a heating-only system is unusual, so note it down and ask an engineer to look at the settings and the valve rather than resetting it repeatedly.

Can I see Aquarea error codes on my phone?

If your system is linked to Panasonic’s online control service, codes may show remotely as well as on the controller. Not every installation is connected, so check with your installer. The remote view does not replace a visit when the same code keeps returning, and the controller display is still what Panasonic’s troubleshooting refers to.

Why does H70 only appear in cold weather?

Panasonic’s UK guide explains that H70 only occurs at the time the back-up heater is activated, so a tripped overload stat or a missing heater supply stays hidden until the heater is called on. Cold weather is when the heater runs to support the heat pump, which is why the code seems to arrive with the first frost. An engineer checks the supply voltage, resets the stat and makes sure the heater is free of air.

Sources and further reading: Panasonic Pro Club UK, Aquarea Installation Guide, Monobloc H and J Generation (2023), commissioning error codes and filling pressure; Panasonic Pro Club, Aquarea self-diagnosis guide for generations H, J, K and L (2023, Polish), code table with detection times and components; Panasonic Heating and Cooling UK documents and support. Checked October 2026.

Myles Robinson

Written by , an expert in heating and renewables with over 15 years in the industry. The guides published here are written and maintained by Myles with input from the company's engineering team, and are reviewed whenever grant schemes, prices or manufacturer advice change.