At a glance
- Samsung EHS heat pump error codes are three-digit numbers shown with an E prefix on the wired remote controller, such as E911, E908 or E554; the same number also shows on the outdoor unit’s main board.
- E911 is a low flow rate error: Samsung raises it when flow stays low for 30 seconds at pump start or 15 seconds once running, with a threshold of 12 litres per minute on units above 9 kW and 7 litres per minute at 9 kW or below.
- E908 is freeze prevention where re-operation is possible; E909 is freeze prevention where re-operation is impossible; E913 is six flow switch errors in a row and the unit will not restart on its own.
- E554 is a gas leak error and E536 is a plate heat exchanger refrigerant leak error; both need a qualified engineer and must not be reset repeatedly.
- Samsung’s installation manual says to charge the system to 1.5 to 2.0 bar and keep the nominal water pressure at about 1.0 bar at all times.
- Samsung publishes no owner error-reset sequence for the EHS wired remote controller, so a code that does not clear itself needs the cause fixed first.
What do Samsung heat pump error codes mean?
A Samsung heat pump error code means the EHS system has detected a fault and has stopped or restricted itself to protect a component. Samsung EHS heat pumps show the code on the wired remote controller and on the outdoor unit’s main board, as a number such as 911 that most owners read as E911. The number tells you roughly where the problem sits: E1xx and E2xx are communication and sensor faults on the hydro unit or control kit, E4xx and E5xx are the outdoor unit, inverter and refrigerant circuit, E6xx are the wired remote controller and E9xx are the hydro unit’s water-side sensors, flow and freeze protection.
If a code keeps returning, or you are not sure what it means, book an engineer rather than guessing. Our guide to a Heat Pump Not Working questions answered covers the general checks for any make, and the Heat Pump Error Codes questions answered explains common codes across the main brands.
This guide is based on two Samsung documents: the installation manual for the EHS R-32 Mono outdoor units (AE***RXYDEG and AE***RXYDGG) and the user manual for the EHS wired remote control kit (MIM-E03CN), which lists the hydro unit and control kit codes. Meanings can differ slightly on older EHS Split and TDM models, so check your own manual if a description does not match. Never remove the casing of the outdoor unit or hydro unit, and leave anything electrical to a qualified engineer.
Is it safe to fix a Samsung heat pump fault yourself?
Only basic checks are safe for a homeowner on a Samsung EHS; the repair itself is engineer work. Reading the code on the wired remote controller, checking the pressure gauge on the hydro unit, opening valves you know about and clearing leaves or snow from around the outdoor unit are fine.
Never open the unit to reach the electrics. Many Samsung codes in the E4xx range point at the inverter board (IPM), the DC link and compressor wiring, which can hold a dangerous charge even after the power is off. Samsung’s own caution for R-32 units is not to remove fuses or disconnect the power plug with the power on, because of the risk of a spark.
Refrigerant work is legally restricted to qualified engineers, so codes such as E554, E536 and E403 are never DIY. If the remote controller sounds a refrigerant leak alarm, Samsung’s instruction is to turn off the alarm and consult a dealer or service centre. Unqualified work inside the unit can also cause problems with your manufacturer warranty, so check its terms before going beyond the checks in this guide.
Which Samsung error codes can you check yourself?
Only a handful of Samsung codes have a realistic homeowner check, mostly around water flow, airflow, power and the hot water schedule: E911, E907, E908, E919, E601, E500, E915, E458 and E475. Check once, and call us if the code comes back.
For E911, check the pressure gauge and that radiator and zone valves are open, and top up only if you have a filling loop and your manual allows it. Samsung’s installation manual says the system is charged to 1.5 to 2.0 bar and should stay at about 1.0 bar at all times to keep air out. Our guide to the Samsung E911 and E912 flow and pressure faults goes through the gauge and the filling loop on the hydro unit. If the pressure is fine and the code still shows, our Samsung E911 low flow guide covers closed valves, blocked filters and pump faults. For E907, look for drips under the hydro unit, at radiators and on visible pipework. For E908, make sure the unit has power and no breaker has tripped; if it changes to E909 the unit will not restart on its own. For E919, avoid large hot water draw-offs during the scheduled disinfection cycle.
For E601, switch off at the isolator for a few minutes and back on. For E500, clear anything blocking airflow around the outdoor unit and let the inverter cool. For E915, E458 and E475, look from outside for ice, leaves or debris blocking the fan without reaching inside. If a code reappears after its check, stop there and book an engineer.
What are the most common Samsung heat pump error codes?
The Samsung codes we see most involve water flow, freezing, sensors and communication. Causes start with what Samsung states in its manuals; anything marked general engineering knowledge comes from our experience, not the manual.
E911: low flow rate error
E911 means the pump is running but too little water is moving. Samsung triggers it when flow is low for 30 seconds while the pump signal is on at start-up, or for 15 seconds once running. The control kit manual gives the thresholds: below 12 litres per minute for outdoor units above 9 kW, and below 7 litres per minute for units of 9 kW or less and for the BXYD and CXYD ranges. Samsung also notes that on floor-only systems a 2-way valve can close when the outlet water temperature is too low and E911 can follow.
General engineering knowledge: air locks, a clogged strainer, sludge and closed zone valves are the usual underlying causes. Check the pressure gauge and valves. If E911 returns, an engineer will bleed the system, clean the strainer and test the pump. Six flow switch errors in a row trigger E913, after which Samsung says re-operation is not possible until the cause is fixed.
E908 and E909: freeze prevention
Both mean the hydro unit has acted to protect itself from freezing. With E908, Samsung says re-operation is possible; with E909 re-operation is impossible and an engineer must attend. Samsung gives no further cause in the user manual.
General engineering knowledge: low flow on a cold night, a weak glycol concentration where antifreeze is used, poor pipe insulation and loss of power are the usual reasons, since freeze protection needs electricity to run the pump. Our guide to the Samsung E908 and E909 freeze protection codes explains what to do while you wait. Samsung’s maintenance list also says to record the glycol concentration and pH at least once a year.
E403 and E436: plate heat exchanger freeze detection
E436 means the outdoor unit has detected freezing of the plate heat exchanger during heating. E403 is the same detection during cooling in the control kit manual, while the Mono outdoor manual describes it as detection of compressor freezing during cooling, so the wording depends on which document your installer uses. Both are outdoor unit faults.
Check the outdoor coil is not buried in snow, ice or leaves, and that the water side has flow. If the code persists with everything clear, an engineer needs to check the refrigerant cycle.
E907: pipe rupture protection
E907 means the hydro unit has raised its pipe rupture protection. Samsung names this code without giving causes in the user manual. General engineering knowledge: a leak, low system pressure and a failing expansion vessel are the usual reasons.
Check the gauge and look for drips. If pressure keeps falling, book a visit, because a leak that drops pressure will keep tripping both E907 and E911.
E901, E902, E903 and E904: water sensor faults
E901 is the water inlet temperature sensor at the plate heat exchanger, E902 the water outlet sensor at the plate heat exchanger, E903 the water outlet sensor after the backup heater and E904 the domestic hot water tank sensor, each reading open or short circuit. E910 means the water outlet temperature sensor has become detached from the pipe. E899 and E900 are the zone 1 and zone 2 water-out sensors.
There is no homeowner fix, so book an engineer, who will check the connector and test or replace the sensor.
E101, E201, E202, E203 and E601: communication faults
E101 is a wiring connection error between the hydro unit (or control kit) and the outdoor unit. E201 is a matching error between them and E202 is a communication error lasting 3 minutes. E203 is a communication error between the inverter and the main microcontroller inside the outdoor unit, timed at 4 minutes in the control kit manual and 6 minutes in the Mono manual. E601 is a communication error between the wired remote controller and the hydro unit, and E604 is a tracking error on the same link.
A restart may clear E601. Repeat communication codes need an engineer, who will check cable joints and any recent electrical work first.
E407 and E507: high pressure protection
E407 means the compressor has shut down on high pressure measured by the pressure sensor, and E507 means it has shut down on the high pressure switch. General engineering knowledge: poor water flow, a blocked plate heat exchanger or a blocked outdoor coil in cooling leave the heat nowhere to go, so flow is checked before the refrigerant circuit.
An engineer should check flow first, then the refrigerant circuit.
E554 and E536: refrigerant leak
E554 is a gas leak error from the outdoor unit and E536 is a plate heat exchanger refrigerant leak error. On R-32 units with leak sensors, E696 and E697 are first and second refrigerant leak detections, E698 is a leak sensor failure, and E699 and E700 are sensor replacement and unavailable alarms. All of these need a qualified engineer, and E554 should be treated as urgent.
Which error code might you see in common situations?
These are the Samsung codes most likely in everyday situations. Do the first check, then call us if the code stays.
| Scenario | Codes you may see on a Samsung | First check |
|---|---|---|
| Cold snap and iced outdoor unit | E908, E909, E436, E403 | Keep the unit powered and clear snow from around it. Do not chip ice off the coil. Our guide to More on do heat pumps work in cold weather shows what is normal |
| Losing pressure or low pressure | E907, E911, E973 | Read the gauge and look for drips at the hydro unit and radiators |
| Radiators lukewarm | E911, E407, E507, E440 | Check pressure and that radiator and zone valves are open; E440 means heating is blocked because it is above 35°C outside |
| No hot water | E904, E917, E919, E897 | Check the hot water schedule and avoid draw-offs during disinfection |
| After a power cut | E101, E202, E601, E466 | Give the system a few minutes to restart and check the breaker |
| Unit noisy or fan not spinning | E458, E475, E915 | Look for ice or debris around the fan from outside |
| After a service or filter clean | E911, E912, E910 | Check that isolation valves were reopened and pressure is back to the installer’s figure |
How do I reset a Samsung heat pump?
Samsung does not publish an owner error-reset sequence for the EHS wired remote controller, so most codes should follow a fix by an engineer rather than a reset. The user manual’s reset items are for Wi-Fi, the remote controller settings and service parameters, not for clearing a fault.
- Write down the full code and which unit the controller shows as the source.
- Deal with any owner-level cause: restore the water pressure, reopen a closed valve, clear the outdoor unit or reset a tripped breaker once.
- If the code was E601 or a communication code, switch the system off at the isolator, wait a few minutes and switch it back on.
- If the controller shows a refrigerant leak alert such as E696, Samsung allows the alarm sound to be stopped 4 minutes after it starts by holding the OK button for 3 seconds; the leak itself still needs an engineer.
- If the same code returns, leave it and book a visit.
Some codes behave differently. E913 will not clear until the flow fault is fixed, E909 does not allow the unit to run again, and E908 lets the unit resume on its own. Resetting over and over without fixing the cause strains the compressor and pump, and repeated flow errors are exactly what triggers the E913 lockout.
Samsung error code list
This list covers the codes in Samsung’s EHS R-32 Mono outdoor installation manual (DB68-08408A-07) and the EHS wired remote control kit user manual (DB68-08470A-18). Codes vary between EHS generations, so check your own manual if a description does not match.
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| E101, E201, E202 | Hydro unit to outdoor unit wiring connection error, matching error, or communication error (3 minutes) | Cable, terminals or a unit without power | Breakers for both units | Engineer |
| E203 | Communication error between inverter and main microcontroller in the outdoor unit | Outdoor boards or wiring | Nothing owner-side | Engineer |
| E116, E122, E123 | Indoor R-32 sensor, EVA inlet or EVA outlet temperature sensor short or open | Sensor or connector | Nothing owner-side | Engineer |
| E120, E121 | Zone 2 or zone 1 room temperature sensor short or open (room thermostat installations) | Thermostat sensor or wiring | Nothing owner-side | Engineer |
| E162, E198 | EEPROM error; terminal block thermal fuse open | Control board; overheated terminal block | Nothing owner-side | Engineer |
| E221, E231, E251, E320 | Outdoor air, condenser, discharge or OLP temperature sensor error | Sensor or connector | Nothing owner-side | Engineer |
| E403, E436 | Plate heat exchanger freeze detection during cooling or heating | Low flow, low refrigerant, blocked coil | Coil clear, valves open | Homeowner check, then engineer |
| E404 | Outdoor unit overload protection | Operating conditions, airflow or refrigerant | Airflow clear | Engineer |
| E407, E507 | Compressor down on high pressure sensor, or on high pressure switch | Poor water flow, blocked exchanger, refrigerant fault | Valves open, pressure normal | Engineer |
| E416 | Compressor discharge overheated | Refrigerant charge or expansion valve | Nothing owner-side | Engineer |
| E419 | Outdoor unit EEV operation error | Expansion valve or coil | Nothing owner-side | Engineer |
| E425 | Power source line missing (three-phase models) | Lost phase | Breakers on | Engineer |
| E440, E441 | Heating blocked above 35°C outside; cooling blocked below 9°C outside | Outdoor temperature outside mode limits | Nothing: not a fault | No action, wait |
| E458, E475 | Outdoor unit fan 1 or fan 2 error | Obstruction, ice or motor | Fan clear from outside | Homeowner check, then engineer |
| E461 to E469 | Inverter compressor start-up, total or PFC current, OLP overheat, IPM over-current, compressor overload, DC link voltage, rotation, current sensor or DC link sensor error | Compressor, inverter or supply | Nothing owner-side | Engineer |
| E470, E471, E590 | Outdoor unit EEPROM read/write error; inverter EEPROM checksum error | Outdoor boards | Nothing owner-side | Engineer |
| E474, E484, E485 | IPM or PFCM temperature sensor error; PFC overload; input current sensor error | Inverter electronics | Nothing owner-side | Engineer |
| E500 | IPM (inverter module) overheated | Blocked airflow, hot conditions | Airflow clear, let it cool | Homeowner check, then engineer |
| E536, E554 | Plate heat exchanger refrigerant leak error; gas leak error | Refrigerant leak | Nothing owner-side | Engineer, urgent |
| E601, E604, E607 | Wired remote controller to hydro unit communication or tracking error; main to sub controller error | Cable or controller | One restart | Homeowner check, then engineer |
| E602, E633 | Wired remote controller main/sub setting error; incompatible device connection | Controller setup | Nothing owner-side | Engineer |
| E653, E654 | Wired remote controller temperature sensor short or open; controller EEPROM error | Controller | Nothing owner-side | Engineer |
| E686 to E700, E797 | R-32 leak detection sensor faults, first and second leak detections, sensor replacement or lifetime alarms | Refrigerant leak or sensor | Nothing owner-side | Engineer |
| E897, E899, E900 | Water tank inlet sensor; zone 1 or zone 2 water-out temperature sensor | Sensor or connector | Nothing owner-side | Engineer |
| E901 to E904, E906 | Water inlet, water outlet (PHE), backup heater outlet, DHW tank or refrigerant gas inlet temperature sensor error | Sensor or connector | Nothing owner-side | Engineer |
| E907 | Pipe rupture protection | Leak, low pressure, expansion vessel | Gauge and visible drips | Homeowner check, then engineer |
| E908 | Freeze prevention, re-operation possible | Cold weather with low flow or no power | Power on, breaker not tripped | Homeowner check |
| E909 | Freeze prevention, re-operation impossible | As E908, more severe | Nothing owner-side | Engineer |
| E910 | Water outlet temperature sensor detached from pipe | Sensor clip | Nothing owner-side | Engineer |
| E911 | Low flow rate error (flow switch off while pump running) | Valves, strainer, air, pump | Gauge and valves | Homeowner check, then engineer |
| E912 | Normal flow rate detected for 10 minutes with the pump off | Flow switch or external pump | Nothing owner-side | Engineer |
| E913 | Six flow switch errors, re-operation not possible | Unresolved E911 cause | Nothing owner-side | Engineer |
| E914, E917 | Incorrect thermostat connection; water tank sensor configuration error | Wiring or settings | Nothing owner-side | Engineer |
| E915 | DC fan on the hydro unit not operating | Fan or obstruction | Visible obstruction only | Homeowner check, then engineer |
| E916 | Mixing valve sensor error | Sensor or connector | Nothing owner-side | Engineer |
| E919 | Disinfection set temperature not reached or not held for the requested time | Hot water drawn during the cycle; heater fault | Disinfection schedule | Homeowner check, then engineer |
| E920 | FSV SD card data error | Service settings card | Nothing owner-side | Engineer |
| E973 | Water pressure error (sensor open or short) | Pressure sensor or wiring | Gauge reading | Engineer |
Where do I find the Samsung fault code list?
Samsung publishes the installation manual for its EHS R-32 Mono outdoor units and the user manual for the EHS wired remote control kit on its UK support site, and both carry an error code table. Search your own model number there, because documents vary between models and generations.
- Samsung UK support page for the AE160RXYDEG/EU EHS Mono unit, with the installation manual download
- Samsung UK support page for the MIM-E03CN wired remote control kit, with the user manual download
If your controller shows a code that is not in this guide, check the manual for your exact hydro unit and outdoor unit before acting on it.
When to call an engineer
Call an engineer for a Samsung heat pump when E911 or E907 returns after you have checked the pressure and valves, when E909 or E913 appears, when any E4xx or E5xx outdoor code shows, or when the controller reports a refrigerant leak. For E554, E536 or a leak alarm, isolate the heat pump at the fused spur or isolator, keep ignition sources away from the outdoor unit and call an engineer; do not try to find the leak yourself.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We work on Samsung heat pumps from older EHS Split systems to current Mono and ClimateHub units, and a Heat pump repairs starts with reading the code history and a clear quote.
Samsung’s own maintenance list is a good guide to what an annual service should cover: checking the water pressure, cleaning the water filter, testing the pressure relief valve and checking the glycol concentration and pH, all by qualified personnel at least once a year. Our breakdown cover and annual servicing bundle that service with callouts, and the where we work page confirms we reach your postcode. For the case for a plan, read Is Heat Pump Cover Worth It questions answered.
Frequently asked questions
Will a Samsung error code void my warranty?
A code on its own does not void anything; it is the heat pump protecting itself. Warranty problems usually come from unqualified repairs inside the unit or missed annual servicing, and Samsung’s manual expects maintenance by qualified personnel at least once a year. Keep your service records and check the warranty terms before anyone works on the system.
Does an E4xx code mean the compressor has failed?
Not necessarily. The E46x codes describe inverter start-up, current, voltage and rotation errors, and many turn out to be a supply problem, a sensor or the inverter board rather than the compressor itself. An engineer measures the supply, the DC link and the compressor windings before condemning anything, and the outdoor unit’s own fault history helps with that.
Can I keep using my Samsung heat pump while it shows a code?
Some codes stop the unit and others let it carry on. E440 and E441 are not faults at all, just heating or cooling blocked by the outdoor temperature, and E908 lets the unit resume on its own. If the unit has stopped on E909, E913 or any refrigerant code, do not keep restarting it; book a check instead.
Why does E911 keep coming back on my Samsung?
Repeated E911 means the flow problem has not been fixed, not that the sensor is wrong. Samsung’s thresholds are strict, 12 litres per minute on larger units, so a part-blocked strainer, a closed zone valve or pressure that has slipped below 1 bar is enough. An engineer will measure the flow rate on the controller, clean the strainer and test the pump; our Samsung EHS review covers how the hydro unit is laid out.
What should I note down before calling an engineer?
Note the exact code, which unit the controller names as the source, when it appeared, the pressure gauge reading and the weather. A photo of the data plate on the outdoor unit and the hydro unit helps us bring the right parts. Why that matters is covered in More on why heat pump servicing is so important.
Sources and further reading: Samsung, EHS R-32 Mono outdoor unit installation manual DB68-08408A-07 (January 2024), error codes and maintenance pages; Samsung, EHS wired remote control kit MIM-E03CN user manual DB68-08470A-18 (June 2026), troubleshooting tips and error codes appendix. Checked October 2026.