At a glance
- A Vaillant aroTHERM plus heat pump shows faults as an F code (for example F.022) on the VWZ AI appliance interface, with a short text line; status messages such as “Heating: Compressor blocked” use S codes instead.
- F.022 means the heating water pressure has stayed below 0.5 bar for more than a minute; Vaillant’s cold-system filling pressure is 1.0 to 1.5 bar, and message M32 appears below 0.7 bar.
- F.718 and F.785 mean fan unit 1 or fan unit 2 is blocked; the heat pump retries four times before locking out.
- F.9998 means the indoor and outdoor units have lost their eBUS connection or the outdoor unit has no power.
- Vaillant’s own reset route is the reset button on the VWZ AI after the cause is removed; if a code returns after several resets, Vaillant says to contact service.
- Codes in the F.5xx sensor range, F.73x refrigerant range and F.75x to F.82x inverter range are engineer-only, and refrigerant work needs a qualified engineer.
What do Vaillant heat pump error codes mean?
A Vaillant heat pump error code means the heat pump has stopped, or held itself back, to protect a component. On aroTHERM plus and aroTHERM split systems the code appears on the controller screen as an F followed by a number, such as F.022, with a short line of text. You may also see plain status messages like “Heating: Compressor blocked” with no F number at all.
Most Vaillant codes come down to a handful of causes: low water pressure, poor flow through the building circuit, a blocked fan, a defrost problem or a lost link between the indoor and outdoor units. Some of these you can check safely in a few minutes. Others involve mains electrics or the sealed refrigerant circuit, and those are for a qualified engineer only.
If your Vaillant heat pump is not showing a code, or you want to rule out the basics first, our guide to a guide to Heat Pump Not Working walks through the general checks that apply to every make. For codes on other brands, the Heat Pump Error Codes guide covers them brand by brand.
The Glow-worm GeniaAir is built by the same group and uses the same numbering scheme, but we have not verified its separate code list for this guide, so GeniaAir owners should check their own installation manual.
Is it safe to fix a Vaillant heat pump fault yourself?
Only the basic checks are safe for a homeowner on a Vaillant heat pump. That means reading the water pressure on the controller, clearing leaves or snow from around the outdoor unit, checking the breakers and isolator, and pressing reset once the cause has been dealt with.
Never open the outdoor unit or the indoor hydraulic station to look at wiring. The inverter electronics run at mains voltage and can hold a charge after you switch off. The aroTHERM plus is filled with R290 refrigerant, which Vaillant’s installation manual describes as flammable, and its warning stickers must not be removed.
Any work on the refrigerant circuit is legally restricted to qualified engineers. Manufacturer warranties also tend to rely on proper installation and servicing, so a DIY repair inside the unit can put your cover at risk. Check your paperwork before going further than the checks in this guide. If you smell burning or see water or refrigerant leaking, isolate the heat pump at the fused spur or isolator and call an engineer.
Which Vaillant error codes can you check yourself?
You can safely check a small group of Vaillant codes linked to water pressure, airflow, defrost, flow and power: F.022, F.718, F.785, F.733, F.741, F.819, F.788 and F.9998, plus the “Compressor blocked” status messages. Every other code in the full list further down needs an engineer.
For F.022, read the water pressure in the Live Monitor on the controller. Vaillant’s operating instructions say the filling pressure should sit between 1.0 and 1.5 bar when the system is cold, and that a taller house may need more, so follow the figure your installer set. If your system has a filling loop and your handover pack allows it, top up to that figure. If the pressure drops often, Vaillant says to find and fix the cause of the loss and tell a competent person. Our guide to the Vaillant F.22 and F.73 low water pressure faults goes through this in detail.
For F.718, F.785 and F.733, switch off at the isolator and clear leaves, snow or debris from the grille and the air route around the outdoor unit. For F.9998, check the breakers and isolator are on and restart once. For F.819, let the unit cool and make sure nothing is blocking the air around it. If a breaker has tripped, reset it once; if it trips again, leave it off and call us, as that points to an electrical fault.
What are the most common Vaillant heat pump error codes?
The Vaillant codes we see most often cover low pressure, flow, fans, defrost and communication. The meanings and causes below come from the Vaillant VWZ AI appliance interface manual; where we add a cause from our own experience we say so.
F.022: low water pressure
F.022 means the water pressure in the building circuit is too low. Vaillant lists pressure loss through leaks or air pockets, or a faulty building circuit pressure sensor, as the causes. The code appears when the filling pressure stays below 0.5 bar for more than a minute and goes out once the pressure rises above 0.5 bar again. From general engineering knowledge, a tired expansion vessel or a weeping pressure relief valve can also let the pressure fall.
Top up only if you have a filling loop and your manual allows it. If the pressure falls again, book an engineer to find the leak and test the vessel and sensor. F.073 is the related sensor fault, where the pressure sensor is not connected or its input has short-circuited.
F.788, F.820 and F.094: pump and flow faults
F.788 means the electronics in the high-efficiency pump have detected a fault such as dry running, a blockage or an over- or under-voltage, and have locked the pump. F.820 means the pump is not reporting a signal back to the heat pump. F.094 is a fault with the vortex volume flow sensor. As general engineering knowledge, sludge, a blocked strainer, an air lock or a closed valve can all starve the system of flow.
Vaillant’s remedy for F.788 starts with switching the heat pump off for at least 30 seconds, then checking the pump, purging the building circuit and checking the dirt filter. Check any valves you know about are open and the pressure is normal, then leave the rest to an engineer.
F.718 and F.785: fan blocked
These codes mean the outdoor unit has no confirmation signal that fan unit 1 (F.718) or fan unit 2 (F.785) is rotating. Vaillant’s remedy is to check the air route and remove any blockages. Before the code locks in, the status S.252 shows: if the fan speed is 0 rpm the heat pump switches off for 15 minutes and restarts, and after four unsuccessful restarts it switches off and shows F.718.
Switch off at the isolator before clearing anything by hand. If the fan is clear and the code returns, the motor or its wiring needs an engineer.
F.741: return temperature too low during defrost
F.741 means the building circuit return temperature fell below 13°C while the heat pump was de-icing. Vaillant links this to too little water in the installation and says to ensure the minimum installation volume is maintained, fitting a series return cylinder if required. The message stays until the return temperature rises above 20°C, and the compressor is blocked while it is present. Vaillant’s own workaround is to activate the electric back-up heater to lift the return temperature.
Our guide to the Vaillant defrost fault codes explains what a normal defrost looks like and when ice is a problem. If ice keeps building, an engineer will check the system volume and the back-up heater.
F.731, F.733 and F.823: refrigerant protection
F.731 means the high-pressure switch has opened because refrigerant pressure is too high; the switch in the outdoor unit trips at 41.5 bar gauge. Vaillant’s causes include an unpurged building circuit, too low a flow because single room controls have closed on underfloor heating, a dirt filter that is no longer permeable and a low refrigerant flow rate. F.733 means the evaporation temperature is too low, usually from insufficient airflow through the outdoor heat exchanger or too little refrigerant. F.823 means the hot gas thermostat has shut the heat pump down because the refrigerant circuit went above 110°C; it retries after a 5-minute wait, then 30 minutes, and shows the fault after three failed starts in a row.
Clear any debris from the coil and make sure heating valves are open, then call an engineer, because the next checks involve the refrigerant circuit. F.731 also needs the high-pressure switch resetting and a manual reset on the product, which is an engineer task.
F.752, F.753 and F.817 to F.819: inverter faults
These codes point to the frequency converter, the inverter board that drives the compressor. F.752 is an internal electronics fault on the inverter PCB or a mains voltage outside 70 to 282 V. F.753 means the outdoor control board cannot see the frequency converter. F.817 is a compressor or inverter defect, or a loose compressor cable. F.818 means the mains voltage is wrong for the inverter, which Vaillant says must be between 195 and 253 V, and F.819 means the inverter is overheating; the outdoor unit’s maximum environmental temperature is 46°C.
Leave the electrics alone and book an engineer. The only owner check is for F.819: let the unit cool, check nothing is blocking its airflow and restart once.
Temperature and pressure sensor faults
Codes such as F.514, F.517, F.519, F.520, F.526, F.546, F.585, F.703, F.774 and F.825 all carry the same Vaillant cause: the sensor is not connected or the sensor input has short-circuited. The remedy is to check and if necessary replace the sensor, or replace the wiring harness.
There is no homeowner fix here. An engineer will test the sensor, its plug and the harness, and may need to replace a board if several sensor codes appear together.
F.9998: communication fault
F.9998 means a connection fault between the heat pump units. Vaillant’s causes are an eBUS cable that is not connected or is connected incorrectly, or an outdoor unit without supply voltage. The remedy is to check the connections between the power supply PCB and control PCB on the indoor and outdoor units.
Check the isolator and breakers, then restart once. If F.9998 returns, an engineer will check the eBUS cable and the outdoor unit’s supply.
“Compressor blocked” status messages
These messages are S status codes rather than faults. S.102 (heating), S.112 (cooling) and S.132 (domestic hot water) all mean the compressor is blocked because the heat pump is outside its application limits. That can be a very cold or very hot outdoor temperature, or water-side conditions such as a flow rate or temperature that the compressor is not allowed to start into. From our experience, a blocked strainer or a closed valve on the water side is a common reason a unit sits in this state.
Check any heating valves you closed are open again. An engineer will clean the strainers, check flow in the test menu and clear the fault list.
Which error code might you see in common situations?
The situation often tells you more than the code alone. Here is what a Vaillant heat pump tends to show in everyday problems, and what to look at first.
| Scenario | Codes you may see on a Vaillant | First check |
|---|---|---|
| Cold snap, outdoor unit iced up | F.741, F.733, F.718, F.785 | Wait a few minutes in case it is defrosting, then check the condensate drain and clear snow. Our guide to Guide to Do Heat Pumps Work in Cold Weather explains what is normal |
| Losing pressure or low pressure | F.022, F.073 | Read the water pressure and look for drips at valves and radiators |
| Radiators lukewarm | F.022, F.788, F.820, F.094, “Heating: Compressor blocked” | Pressure, then radiator and isolation valves |
| No hot water | “Domestic hot water: Compressor blocked” | Hot water schedule, then the strainer if your manual allows you to clean it |
| After a power cut | F.9998, F.818, F.1117 | Breakers and isolator on, then one restart |
| Noisy, or fan not spinning | F.718, F.785, F.819 | Debris or ice around the fan grille |
| After a service or filter clean | F.022, F.094, F.788, F.9998 | Pressure topped back up and all valves reopened |
How do I reset a Vaillant heat pump?
You reset a Vaillant aroTHERM plus heat pump by removing the cause of the fault and then pressing the reset button on the VWZ AI appliance interface. Vaillant’s installation instructions say to eliminate the fault, press reset to start the product again, and contact service if the fault recurs despite several reset attempts.
- Write down the F code and any message on the controller, or take a photo of the screen.
- Deal with the cause if it is an owner check: top up the water pressure, clear the fan grille, reopen a closed valve or reset a tripped breaker once.
- Press the reset button on the VWZ AI appliance interface (the button marked “reset” on the control panel).
- If the unit does not respond, switch it off at the isolator, wait around five minutes, then switch it back on and give it time to restart before judging whether it worked.
- If the same code returns, stop and book an engineer rather than resetting again.
Some faults are stored and stay in the fault memory until an engineer clears them from the installer level. So a code that seems to linger after a reset is not always a fresh fault. One reset is fine. Resetting repeatedly without fixing the cause can stress the compressor, and it hides the pattern an engineer needs to see.
Vaillant error code list
This list covers the aroTHERM plus F codes published in the Vaillant VWZ AI appliance interface installation instructions (0020291573_01). It is not every code the controller can show, so check your own installation manual for anything not listed here.
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| F.022 | Building circuit water pressure too low | Leak or air pocket; faulty pressure sensor | Water pressure on the controller; visible leaks | Homeowner check, then engineer |
| F.042 | Coding resistor fault | Coding resistor damaged or not set | Nothing owner-side | Engineer |
| F.073 | Building circuit water pressure sensor fault | Sensor not connected or input shorted | Nothing owner-side | Engineer |
| F.094 | Vortex (volume flow sensor) fault | Sensor not connected or input shorted | Nothing owner-side | Engineer |
| F.103 | Spare part identification fault | Wrong control PCB fitted in the outdoor unit | Nothing owner-side | Engineer |
| F.514, F.517 | Compressor inlet or outlet temperature sensor fault | Sensor not connected or input shorted | Nothing owner-side | Engineer |
| F.519, F.520 | Building circuit return or flow temperature sensor fault | Sensor not connected or input shorted | Nothing owner-side | Engineer |
| F.526, F.585, F.774, F.825 | EEV outlet, condenser outlet, air inlet or condenser inlet temperature sensor fault | Sensor not connected or input shorted | Nothing owner-side | Engineer |
| F.546, F.703 | High pressure or low pressure sensor fault | Sensor not connected or input shorted | Nothing owner-side | Engineer |
| F.582 | Electronic expansion valve (EEV) fault | EEV not connected correctly or cable break to the coil | Nothing owner-side | Engineer |
| F.718, F.785 | Fan unit 1 or fan unit 2 blocked | No signal that the fan is rotating | Isolate, then clear the air route | Homeowner check, then engineer |
| F.729, F.732 | Compressor outlet temperature too low or too high (above 110°C) | EEV, 4-port valve, refrigerant charge or sensor | Nothing owner-side | Engineer |
| F.731 | High-pressure switch open (trips at 41.5 bar gauge) | Poor flow or heat rejection on the water side; low refrigerant flow | Heating valves open; dirt filter if your manual allows | Engineer |
| F.733 | Evaporation temperature too low | Too little air through the outdoor coil; low refrigerant | Coil clear of leaves, snow and ice | Homeowner check, then engineer |
| F.734, F.735, F.737 | Condensation or evaporation temperature out of range | System temperatures outside limits; charge, EEV or flow | Nothing owner-side | Engineer |
| F.741 | Building circuit return temperature below 13°C during de-icing | Too little water volume in the installation | Whether the back-up heater is enabled; ice on the unit | Homeowner check, then engineer |
| F.752, F.753 | Frequency converter fault, or not recognised | Inverter PCB fault, mains voltage out of range, wiring | Nothing owner-side | Engineer |
| F.755 | 4-port valve position not correct | Valve in wrong position; sensor reading wrong | Nothing owner-side | Engineer |
| F.788, F.820 | Building circuit pump fault, or pump not signalling back | Dry running, blockage, voltage, cable or pump defect | Pressure and valves; one 30-second power-off | Homeowner check, then engineer |
| F.817 | Frequency converter fault: compressor | Compressor or inverter defect; loose compressor cable | Nothing owner-side | Engineer |
| F.818 | Frequency converter fault: mains voltage | Supply outside 195 to 253 V; supplier shutdown | Breakers and isolator on | Engineer |
| F.819 | Frequency converter overheating | Internal overheating; blocked air route; ambient above 46°C | Let it cool; clear airflow; restart once | Homeowner check, then engineer |
| F.823 | Hot gas temperature switch open | Refrigerant circuit above 110°C; EEV or refrigerant filter | Nothing owner-side | Engineer |
| F.1117 | Compressor phase failure | Blown fuse, wiring, low voltage, supplier lockout over three hours | Breakers and isolator on | Engineer |
| F.9998 | Connection fault: heat pump | eBUS cable not connected or wrong; outdoor unit without power | Breakers and isolator on; one restart | Homeowner check, then engineer |
Where do I find the Vaillant fault code list?
Vaillant publishes its installation and operating instructions as free PDFs on its UK professional site. On aroTHERM plus systems the fault code table sits in appendix F of the VWZ AI heat pump appliance interface instructions, while aroTHERM split codes are in the hydraulic station manual. The S status codes are in the same VWZ AI document, and the operating instructions explain the M32 pressure message and the F.22 pressure threshold.
- VWZ AI heat pump appliance interface operating and installation instructions (PDF)
- aroTHERM plus VWL 35 to 75/6 A S2 installation and operating manual (PDF)
- Vaillant literature and manuals finder
If your controller shows a code that is not in this guide, check the manual for your exact model and software version before acting on it. The VWZ AI installation instructions also note that a maintenance message appears when heating water pressure drops below 1 bar, and that the minimum operating pressure is 0.7 bar.
When to call an engineer
Call an engineer for a Vaillant heat pump when a code returns after one reset, when the water pressure keeps falling after a top-up, when any sensor, inverter or refrigerant code appears, or when you see or smell anything unusual at either unit. Isolate the heat pump at the fused spur or isolator first if there is a burning smell, a water leak or the sound of hissing from the outdoor unit, and do not touch the refrigerant pipework.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We service and repair Vaillant heat pumps from the aroTHERM plus to older split systems; a Our repair service starts with fault diagnosis and a clear quote before any work goes ahead.
Many of the codes above, especially the pressure, flow and fan faults, are avoidable. An annual service catches clogged strainers, low pressure and dirty coils before they trip the unit, which is why guide to Why Heat Pump Servicing Is So Important on a Vaillant. Our heat pump cover plans include the annual service and cover callouts, and you can check the find your nearest engineer for your postcode. If you are weighing up a plan, our guide to guide to Is Heat Pump Cover Worth It sets out the trade-offs.
Frequently asked questions
Does a Vaillant error code void my warranty?
No, a code on its own does not affect your warranty. Problems tend to come from unqualified work inside the unit or missed servicing, as most manufacturer warranties depend on both. Keep your service records, note each code as it appears and use a certified engineer for any repair that goes beyond the owner checks in this guide.
Can I see Vaillant error codes in an app?
Depending on your controller and whether an internet gateway is fitted, faults may also show as alerts on your phone. The controller screen is still the most reliable place to read the full F code and the matching S status code, which Vaillant asks you to quote when you contact service. Our Guide to vaillant aroTHERM Plus Heat Pump Review looks at the controls and app in more detail.
Does a compressor code mean the compressor has failed?
Usually not. Vaillant lists a loose compressor cable or a defective frequency converter among the causes of F.817, and F.1117 is a phase failure that can come from a blown fuse, poor connections, low mains voltage or a supplier lockout lasting more than three hours. An engineer measures the compressor windings and the inverter output before condemning the compressor.
Are old error codes stored on the controller?
Yes. The VWZ AI keeps a fault memory that an engineer can read from the installer level, and fault lists can only be deleted once faults have occurred. That history helps an engineer spot a repeat problem quickly, so a photo of the screen each time a code appears is useful too.
Why does my Vaillant show F.022 every few weeks?
Repeated F.022 means the system is losing water, not that the code is faulty. Vaillant’s operating instructions say that if the pressure drops frequently you should identify and eliminate the cause of the loss. Typical causes are a small leak at a radiator valve or joint, a pressure relief valve that is passing or an expansion vessel that has lost its charge, all of which an engineer can test on one visit.
Sources and further reading: Vaillant, Heat pump appliance interface VWZ AI operating and installation instructions, 0020291573_01 (December 2022), appendix F fault codes, appendix E status codes and section 3.5 on water pressure; Vaillant, aroTHERM plus VWL 35 to 75/6 A S2 installation and operating manual, 0020330791_03, for the R290 refrigerant warnings and pressure sensor thresholds; Vaillant UK literature finder for other models. Checked October 2026.