At a glance
- Viessmann Vitocal heat pump error codes are F numbers such as F.74, F.686 or F.1079 shown on the programming unit with the date, time, a short description and a subscriber number that identifies the module reporting the fault.
- F.74 means the hydraulic system pressure is too low and the heat pump switches off; Viessmann’s measure is to top up to the required pressure and vent, and if the message returns after about 10 seconds to drain, refill and vent.
- F.1078 and F.1079 mean the minimum flow rate in the secondary (heating) circuit was not reached, and the refrigerant circuit is locked until it is unlocked by a contractor through ViGuide.
- F.864 and F.1082 are defrost faults raised after 9 aborted defrost cycles, and F.807 is a fan fault whose first listed cause is wind exposure.
- The Vitocal 250-A stores its 10 most recent faults under Service menu, Message history, and its full fault descriptions are published online under Viessmann document number 6199893.
- Viessmann publishes no owner reset sequence: locked refrigerant circuit faults are unlocked by a contractor, and refrigerant work must only be carried out by a certified contractor.
What do Viessmann Vitocal heat pump error codes mean?
A Viessmann Vitocal error code is a fault message shown on the programming unit with the date and time it occurred, a short description and a subscriber number that identifies the part of the system reporting it. On current models such as the Vitocal 200-S, 222-S, 250-A, 150-A and 151-A the codes are F numbers, for example F.74 or F.686, and the same number scheme runs across the range. Viessmann says the possible faults vary with the system equipment, so not every message will appear on every system.
This guide is based on the fault message index and descriptions in Viessmann’s service instructions for contractors for the Vitocal 200-S, 222-S and 222-SI (Viessmann One Base, 6199961 GB, July 2024), read from a manualslib copy of the official document because Viessmann’s own ViBooks database needs a serial number to retrieve it. The 250-A installation and service instructions (6202074 GB) confirm the subscriber numbers and message history and point to Viessmann’s online document 6199893 for that model’s descriptions. Older Vitocal units with the Vitotronic 200 control use two-character codes that we have not verified, so owners of those should check their own manual.
If your Vitocal is not showing a code, or you want to rule out the basics first, our guide to a Heat Pump Not Working walks through the general checks. For other makes, the Guide to Heat Pump Error Codes covers the main brands. Never open the unit or touch internal wiring, as the electronics carry mains voltage.
Is it safe to fix a Viessmann heat pump fault yourself?
Only basic outside checks are safe on a Vitocal: reading the display, checking the breaker, clearing the outdoor unit and looking at the system pressure. Viessmann’s own manuals treat fault diagnosis and clearing as contractor work through the Service menu and the ViGuide tool.
Do not open panels or touch electrics inside the unit. Viessmann’s troubleshooting safety notes say that work on the refrigerant circuit must only be carried out by a certified contractor, that the inverter must not be repaired but replaced if defective, and that faulty components must be replaced only with genuine Viessmann spare parts.
Warranty matters here as well. Manufacturer warranties generally expect qualified installation and servicing, so a DIY repair inside the casing can complicate a later claim. Should you smell burning or hear hissing from the outdoor unit, switch the heat pump off at the fused spur or isolator and leave the rest to an engineer.
Which Viessmann error codes can you check yourself?
Only a few Vitocal codes leave room for a homeowner check, and even then the check is limited: F.74, F.87, F.807, F.864, F.1078, F.1079 and F.78. Write down the code and subscriber number before you do anything.
For F.74, hydraulic system pressure too low, read the pressure gauge and, if you have a filling loop and your manual allows it, top up to the pressure your installer set and vent the radiators. Viessmann’s own measure is to top up to the required pressure and vent, and if the message returns after about 10 seconds to drain, refill and vent the system, which is engineer work. Our guide to the Viessmann F.74 and F.75 low water pressure faults covers the gauge and filling loop on the indoor unit. F.87, system overpressure, is the opposite and needs the pressure reduced and the expansion vessel pre-charge checked, so call an engineer rather than draining anything yourself.
For F.807, fan fault, check from outside whether the outdoor unit is exposed to strong wind, which is Viessmann’s first listed cause, and whether anything is blocking the fan. For F.864 and F.1082, the defrost faults, clear snow and leaves from around the unit but do not de-ice it yourself; Viessmann reserves careful mechanical de-icing for the contractor. For F.1078 and F.1079, check isolation and radiator valves are open and the pressure is normal, because the fault is a minimum flow rate not reached. For F.78, no communication with the programming unit, check the power supply after a power cut and restart once. If any of these persists, book an engineer.
What are the most common Viessmann heat pump error codes?
The Vitocal codes owners ask about most are flow and pressure faults, defrost faults, fan and communication faults, and the refrigerant circuit shutdowns. Viessmann’s listed causes and measures come first; anything marked general engineering knowledge is our own experience, not the manual.
F.74 and F.87: hydraulic pressure too low or too high
F.74 means the hydraulic system pressure is too low and the heat pump switches off. Viessmann’s measures are to top up to the required pressure and vent, to drain, refill and vent if the message returns after about 10 seconds, and to check all hydraulic connections for leaks. F.87 means system overpressure, with the heat pump in a fault state; the measures are to reduce the pressure, check the water pressure sensor and its connection on the EHCU module, and check the expansion vessel’s pre-charge pressure. F.1010 is a water pressure sensor fault, which is the sensor rather than the pressure.
General engineering knowledge: a small leak, a passing relief valve or an expansion vessel that has lost its charge sits behind most repeat F.74 messages.
F.1078, F.1079 and F.1081: minimum flow not reached
F.1078 means the flow rate was repeatedly too low at compressor start-up, and F.1079 means the minimum flow rate in the secondary circuit was not reached; both lock the refrigerant circuit. Viessmann’s measures include fully venting the secondary circuit until it is bubble-free, ensuring the minimum flow rate, checking the refrigerant circuit for damage and unlocking the refrigerant circuit via ViGuide. F.1081 means the flow temperature of the secondary circuit or heating circuit 1 is too low, with the same flow and refrigerant checks if it occurs more than twice an hour.
General engineering knowledge: a clogged filter, closed valves, a worn circulating pump or sludge are the usual reasons the flow falls short. Our guide to the Viessmann frozen unit and low evaporation faults explains how low flow turns into a freeze or evaporation fault.
F.864 and F.1082: defrost faults
F.864 means the defrost was not terminated successfully: the defrost process was aborted 9 times, there is no defrost and the compressor cannot be switched on. Viessmann’s measures are to check the evaporator for dirt and clean it, de-ice carefully if necessary, check the refrigerant circuit for damage, check the minimum flow rate of the secondary circuit and the circulation pump parameters, and unlock the refrigerant circuit via ViGuide. F.1082 is a condensing temperature fault during defrosting, again after 9 failed cycles, with the added check of the 4-way diverter valve.
F.1080 and F.1083: evaporator temperature
F.1080 means the evaporator temperature is too low, and the refrigerant circuit is off; Viessmann’s measures if it occurs more than twice an hour are to isolate the outdoor unit for at least 2 minutes, check for unobstructed flow in the refrigerant circuit, ensure the minimum flow rate in the secondary circuit, check the refrigerant circuit for damage and top up refrigerant if necessary. F.1083 is the evaporator temperature too high in cooling mode. General engineering knowledge: an iced coil or blocked airflow gives the same low evaporator temperature in a cold snap, so clear the unit before calling.
F.807, F.808 and F.812: fan faults
F.807 is a fan fault, and the refrigerant circuit will not start. Viessmann’s first measure is to check whether the outdoor unit is exposed to wind and, if so, to protect it with an air diverter in front of the fans; then to check the fan and motor bearings for damage and blockages by turning them slowly by hand, check the cable and plug on the refrigerant circuit controller, replace the fan if there is voltage at the plug, and check the fuse. F.808 is a wrong signal for the number of connected fans and F.812 is a fault on the upper fan.
F.685, F.686, F.687 and F.78: communication faults
F.686 is a communication error with the refrigerant circuit controller, and the refrigerant circuit will not start; Viessmann’s measures are to check the connecting cables and plug-in connections on the communication and inverter boards, the line filter and the inverter, and the mains voltage and fuse on the line filter. F.685 is the same type of error with the HPMU electronics module and F.687 with the EHCU module. F.78 means no communication with the programming unit, where the first check is the power supply.
F.881: safety shutdown of the refrigerant circuit
F.881 means the refrigerant circuit’s safety shutdown has operated and the circuit will not start. Viessmann’s measures are to check the outdoor unit’s power supply, check whether the shutdown was triggered via the contactor, and test the continuity of the safety high pressure switch, replacing it if necessary. This is engineer work.
Inverter faults: F.836, F.837, F.843, F.862 and F.914
These cover inverter load current too high, a faulty inverter phase connection to the compressor, an overcurrent shutdown on the power factor correction filter, an internal inverter fault and inverter temperature too high. Viessmann’s safety note is that the inverter is not repaired but replaced if defective, so these are engineer jobs and do not automatically mean the compressor has failed.
Sensor faults
Viessmann lists a lead break and a short circuit code for each sensor: flow (F.1, F.2), return (F.3, F.4), cylinder (F.7, F.8), outside (F.13, F.14), top cylinder (F.23, F.24), primary inlet (F.33, F.34), refrigerant inlet to the evaporator (F.111, F.112), liquid gas (F.123, F.124), hot gas (F.151, F.152), the flow and return sensors downstream of the condenser (F.770, F.771) and the evaporator temperature sensor (F.877, F.878), among others. An engineer measures the sensor’s resistance and checks the plug before replacing the sensor or the module.
Which error code might you see in common situations?
The situation often tells you more than the code on a Vitocal, because so many of the codes share a cause on the water side. Use this table as a starting point, not a final diagnosis.
| Scenario | Vitocal codes you may see | First check |
|---|---|---|
| Cold snap and iced outdoor unit | F.864, F.1082, F.1080, F.807 | Clear snow from around the unit and let a defrost finish; do not de-ice it yourself. Our guide to Do Heat Pumps Work in Cold Weather shows what is normal |
| Losing pressure or low pressure | F.74, F.1010 | Read the pressure gauge and look for drips at joints and valves |
| Radiators lukewarm | F.1078, F.1079, F.1081, F.1069 | Check radiator and isolation valves are open |
| No hot water | F.7, F.8, F.23, F.24, F.791 to F.793 | Note the code and subscriber number; check the heating still works |
| After a power cut | F.78, F.685, F.686, F.1065, F.1066 | Check the breaker, then note whether the code clears |
| Unit noisy or fan not spinning | F.807, F.812 | Look for anything blocking the fan from outside and note wind exposure |
| After a service or settings change | F.74, F.1013 to F.1015, F.1092 | Check valves were reopened and pressure restored; DIP switch codes need the engineer back |
How do I reset a Viessmann heat pump?
You do not reset a Vitocal fault yourself in the way you might a boiler. Viessmann’s service instructions clear faults through the Service menu and, for locked refrigerant circuit faults such as F.864, F.1078 and F.1079, through the ViGuide tool, once the cause has been fixed. Neither the 250-A nor the 200-S instructions describe a homeowner button sequence.
- Write down the F code, the date and time shown, and the subscriber number.
- Deal with any owner-level cause: restore the pressure for F.74, reopen valves for the flow codes, clear snow and debris from the outdoor unit.
- For a communication fault after a power cut, Viessmann’s measure for F.875 is to isolate the system from the power supply, wait at least 2 minutes and switch it on again; the same single restart is reasonable for F.78 and F.686.
- Check the programming unit; a fault that clears will still be listed in the message history.
- If the code returns, leave it and book an engineer.
Repeatedly switching the power off and on to clear a code is a bad idea. Viessmann attaches “if message occurs more than twice an hour” to several flow and evaporator faults precisely because repetition is the signal that something is wrong, and running on after a flow fault risks the compressor.
Viessmann error code list
These are the fault messages in the index of Viessmann’s service instructions for the Vitocal 200-S, 222-S and 222-SI, grouped where they share a cause. The 250-A, 150-A and 151-A use the same F number scheme, with their descriptions published in Viessmann document 6199893. Check your own manual or ask an engineer before relying on a meaning for a different model.
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| F.1 to F.4, F.7, F.8, F.13, F.14, F.23, F.24, F.33, F.34 | Lead break or short circuit on the flow, return, cylinder, outside, top cylinder or primary inlet temperature sensor | Sensor, cable or plug | Nothing owner-side | Engineer |
| F.74 | Hydraulic system pressure too low (heat pump switched off) | Leak, air, expansion vessel | Gauge; top up and vent if permitted | Homeowner check, then engineer |
| F.78 | No communication with programming unit | Power supply, cable at X5, programming unit | Power on; one restart | Homeowner check, then engineer |
| F.87 | System overpressure | Over-filled, expansion vessel pre-charge, pressure sensor | Gauge reading | Engineer |
| F.91, F.92, F.100, F.101, F.160 | Communication error DIO or ADIO; PlusBus voltage error or short circuit; CAN bus communication fault | Extension modules or bus wiring | Nothing owner-side | Engineer |
| F.111, F.112, F.123, F.124, F.151, F.152 | Lead break or short circuit on the evaporator refrigerant inlet, liquid gas or hot gas temperature sensor | Sensor, cable or plug | Nothing owner-side | Engineer |
| F.425, F.430, F.431, F.472, F.519, F.520 | Time synchronisation failed; communication error gateway, KNX, energy meter, BACnet; internal gateway fault | Connectivity or gateway | Router and gateway power | Engineer if it persists |
| F.544 to F.549, F.578 | Lead break or short circuit on heating circuit 2 to 4 flow sensors; lead break on the wireless remote control room sensor | Sensor or wiring | Nothing owner-side | Engineer |
| F.685, F.686, F.687 | Communication error with the HPMU electronics module, the refrigerant circuit controller or the EHCU module | Cables, plug-in connections, line filter, inverter, mains voltage, fuse | Breaker on; one restart | Engineer |
| F.744 to F.749, F.764, F.765 | Programming unit incompatible, incompatible configuration, internal or touch panel error, incompatible firmware; another CAN bus subscriber reports a fault or a communication error | Software or bus | Nothing owner-side | Engineer |
| F.770, F.771 | Lead break or short circuit on the secondary circuit flow sensor downstream of the condenser | Sensor or wiring | Nothing owner-side | Engineer |
| F.788, F.790, F.801 | Lead break or mechanical fault on the 4/3-way valve; malfunction of the refrigerant circuit reversal valve | Valve or coil | Nothing owner-side | Engineer |
| F.791 to F.793 | Failure of the instantaneous heating water heater, phase 1, 2 or 3 | Heater or supply | Nothing owner-side | Engineer |
| F.797 to F.800 | Mechanical or electrical fault on the circulation pump for heating circuit 1 or 2 | Pump | Nothing owner-side | Engineer |
| F.807, F.808, F.812 | Fan fault; wrong signal for number of connected fans; fault on the upper fan | Wind exposure, blockage, bearings, cable, fuse | Fan clear and sheltered from wind | Homeowner check, then engineer |
| F.830, F.831, F.836, F.837, F.843, F.844, F.862 | Inverter current sensor faults; load current too high; faulty phase connection to compressor; PFC overcurrent shutdown; internal reference voltage fault; internal inverter fault | Inverter (replace, not repair) | Nothing owner-side | Engineer |
| F.864 | Defrost not terminated successfully (aborted 9 times; compressor cannot switch on) | Dirty or iced evaporator, refrigerant circuit, low flow, pump parameters | Unit clear of snow and leaves | Homeowner check, then engineer |
| F.875 | Communication error with the connected main appliance (cascade) | CAN bus wiring | Nothing owner-side | Engineer |
| F.876, F.877, F.878 | Lead break on the combined flow rate and temperature sensor; short circuit or lead break on the evaporator temperature sensor | Sensor or wiring | Nothing owner-side | Engineer |
| F.881 | Safety shutdown, refrigerant circuit | Outdoor supply, contactor, safety high pressure switch | Nothing owner-side | Engineer |
| F.906, F.909, F.910 | Discrepancy between outdoor and indoor unit; no information on energy management; multiple main appliances recognised | Configuration | Nothing owner-side | Engineer |
| F.914 to F.916 | Inverter temperature too high; inverter cooling temperature sensor short circuit or lead break | Inverter cooling or sensor | Airflow around the unit | Engineer |
| F.923 to F.970 | Data from an energy meter, inverter, consumer, generator or battery module not available (energy management) | Connected devices | Nothing owner-side | Engineer if it persists |
| F.990 to F.997 | Short circuit or lead break on low loss header or buffer cylinder temperature sensors | Sensor or wiring | Nothing owner-side | Engineer |
| F.998 | Communication error, refrigerant circuit controller to EHCU or flow rate signal | Wiring | Nothing owner-side | Engineer |
| F.1008, F.1013 to F.1019, F.1034, F.1035, F.1092 | Supported device count exceeded; incorrect DIP switch settings; sensors not recognised; CAN bus faults; incorrect refrigerant circuit controller configuration | Commissioning or configuration | Nothing owner-side | Engineer |
| F.1010 | Water pressure sensor fault | Sensor or wiring | Gauge reading | Engineer |
| F.1045, F.1050, F.1051, F.1054 | External heat or cooling generator 1 fault, sensor faults or maximum temperature exceeded | External boiler or sensor | Nothing owner-side | Engineer |
| F.1057 | Fault, high pressure sensor, refrigerant circuit | Sensor or wiring | Nothing owner-side | Engineer |
| F.1062, F.1063, F.1065 to F.1067 | Inverter voltage too low or too high; utility power supply too low, too high or frequency too high | Mains supply | Breakers after a power cut | Engineer |
| F.1069 | Condenser overheating | Low flow or high set temperature | Valves open | Engineer |
| F.1078, F.1079 | Flow rate repeatedly too low at compressor start-up; minimum flow rate in secondary circuit not reached (refrigerant circuit locked) | Air, closed valves, filter, pump | Valves open, pressure normal | Homeowner check, then engineer |
| F.1080, F.1083 | Evaporator temperature too low; evaporator temperature too high in cooling | Refrigerant circuit, airflow, low flow | Unit clear | Engineer |
| F.1081 | Flow temperature of secondary circuit or heating circuit 1 too low | Low flow, refrigerant circuit | Valves open | Engineer |
| F.1082 | Condensing temperature during defrosting too low (aborted after 9 failed cycles) | Ice, refrigerant circuit, 4-way valve | Unit clear of snow | Homeowner check, then engineer |
Where do I find the Viessmann Vitocal fault code list?
Viessmann’s UK site links to ViBooks, its online manual database, where you can download the manual for your Vitocal by entering the article or serial number from the type plate or control unit. The fault descriptions for the Vitocal 250-A sit in a separate online document, number 6199893, that the installation and service instructions point to. Viessmann’s UK fault codes support page covers boilers only, not heat pumps.
- Viessmann ViBooks manual database (UK)
- Viessmann UK instruction manuals page
- Viessmann Vitocal 200-S, 222-S and 222-SI service instructions for contractors, 6199961 GB (manualslib copy of the Viessmann document)
If your programming unit shows a code that is not in this guide, note it with the subscriber number and check the manual for your exact model before acting on it.
When to call an engineer
Call an engineer for a Vitocal when F.74 returns after a top-up, when any locked refrigerant circuit fault such as F.864, F.1078, F.1079 or F.1082 appears, when F.881 or an inverter fault shows, or when F.686 or F.78 stays after one restart. For hissing at the outdoor unit or a smell of refrigerant, isolate the heat pump at the fused spur or isolator and wait for a qualified engineer, because Viessmann’s instructions reserve all refrigerant circuit work for a certified contractor.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We work on Viessmann heat pumps across the 200-S, 222-S, 250-A, 150-A and 100-A ranges, and a A repair engineer visit starts with reading the message history and subscriber numbers through the Service menu before a quote.
Flow and pressure faults such as F.74, F.1078 and F.1079 are much less common on a well-maintained system, which is the case set out in Why Heat Pump Servicing Is So Important. Each of our annual cover with servicing included wraps the annual service and callouts together, and our engineers across England, Scotland and Wales shows where we work. If you are weighing up a plan, read Is Heat Pump Cover Worth It, and for the range itself, our Guide to Viessmann Vitocal Heat Pump Review.
Frequently asked questions
What is the subscriber number shown next to a Vitocal fault?
It identifies the component that raised the fault. On the Vitocal 250-A, CAN bus subscriber 1 is the HPMU electronics module, 45 is the inverter, 54 is the VCMU refrigerant circuit controller, 58 is the communication module and 59 is the HMI programming unit, while PlusBus subscribers 0 to 47 are extension and cylinder modules. Give this number to your engineer along with the code.
Does a Vitocal keep a record of old faults?
Yes. The 250-A installation and service instructions say the 10 most recent faults, including ones that have already been remedied, and the service messages are stored, and that a contractor views them under Service menu, Message history, then Fault list or Service messages. That history helps an engineer spot a pattern, such as a flow fault that only appears in cold weather.
Why can’t I find my Vitocal code online?
Viessmann keeps its detailed fault descriptions in contractor documents and in ViBooks, which needs the serial number from your unit, rather than on a public list, and its UK fault codes page covers boilers only. Older units with two-character codes use a different scheme again. If your code is not on this page, note it with the subscriber number and we will look it up during diagnosis.
Does a Vitocal error code affect my warranty?
A code on its own does not, since it is the heat pump protecting itself. Problems come from leaving a fault unrepaired or from unqualified work inside the unit; Viessmann’s instructions say the inverter must not be repaired and that only genuine spare parts may be used, so a DIY repair can complicate a claim. Keep a record of each service and fault.
Can I see Vitocal faults remotely?
If your system has a Viessmann communication module fitted (subscriber 58 on the 250-A), faults may be visible through Viessmann’s online services as well as on the programming unit, and the gateway and connectivity codes F.430 and F.472 relate to that link. Not every installation has one, so ask your installer. Remote alerts are handy, but a repeat fault still needs a visit.
Sources and further reading: Viessmann, Service instructions for contractors, Vitocal 200-S, 222-S, 222-SI, 6199961 GB (July 2024), fault message index and fault message descriptions (manualslib copy of the Viessmann document); Viessmann, Vitocal 250-A installation and service instructions for contractors, 6202074 GB (February 2023), troubleshooting chapter (manualslib copy); Viessmann UK fault codes page (boilers only) and ViBooks. Checked October 2026.