At a glance
- Worcester Bosch Compress 2000 AWF heat pumps show alarms as two-character codes such as E0, P0, H6 or PP on the multifunction keypad, viewed under MENU then SERVICE INFORMATION.
- E0 means three water flow failures and E8 is a single water flow failure that can reset after a few minutes; Worcester Bosch’s checks for E8 include fully open shut-off valves, a clean water filter, no air in the system and water pressure above 1 bar.
- Pb is antifreeze mode and is not a protection; the alarm light does not flash and the controller shows an antifreeze icon instead.
- Hb is raised after three consecutive PP faults with leaving water below 7°C, and H4 appears after three L signals in one hour and cannot be reset.
- Worcester Bosch says to identify and remove the cause before resetting an alarm, and warns that repeated resets can cause irreversible damage.
- The Compress 7400i AW uses a different fault code and sub-code system shown on its user interface, so owners of that range should check its own user guide.
What do Worcester Bosch heat pump error codes mean?
A Worcester Bosch heat pump error code is an alarm that tells you which part of the system has stopped or protected itself. On the Compress 2000 AWF the alarm is a two-character code, such as E0, P0 or H6, where the letter points to the area at fault. E codes mostly cover temperature sensors and water flow, P codes are protections such as refrigerant low or high pressure, H codes cover communication, more sensors and the fan, and L codes are inverter and compressor drive faults. C, F and b codes cover the heat sink, master and slave setup, the DC supply and the PED board.
These codes come from the Worcester Bosch Compress 2000 AWF installation and operating instructions (6721859133). The Compress 7400i AW and 7001i AW use a different system, where the user interface shows a fault code with a sub-code and Worcester Bosch asks you to confirm the fault, note both numbers and the controller’s ID number and call a contractor. The Compress 3400i AWS operation manual carries no code table at all, so owners of that range should look to their installer’s documentation. Check your own manual before relying on a meaning.
If your Worcester Bosch is not showing a code, or you want to rule out the basics first, our guide to a Heat Pump Not Working guide covers the general checks for any make. For other brands, the Heat Pump Error Codes explained explains the common codes. Safety first: never open the unit or touch the electrics inside.
Is it safe to fix a Worcester Bosch heat pump fault yourself?
Basic checks are safe, but almost every repair behind these codes is engineer work. Checking the pressure gauge, opening valves and clearing snow or leaves from around the outdoor unit are fine for most homeowners, and Worcester Bosch’s own E8 checklist starts with exactly those items.
Never open the casing or touch the wiring. Many codes involve the inverter module and compressor drive, which run at dangerous voltages. The Compress 7400i user guide warns of a risk of electric shock and grave personal injury and says to disconnect the power supply before any maintenance work, which applies just as much to the 2000 AWF.
Refrigerant work is legally restricted to qualified engineers, so codes such as P0, P1 and H8 that involve the refrigerant circuit are not DIY. Worcester Bosch’s remedy list for P0 includes charging the system with refrigerant, which only a qualified engineer may do. Unqualified work inside the unit can also affect your warranty, so check its terms first. A burning smell or hissing from the outdoor unit means isolating the unit at the fused spur or isolator and calling an engineer, not investigating.
Which Worcester Bosch error codes can you check yourself?
A few codes have a realistic first check, mostly those linked to water flow, airflow and power: E0, E8, PP, Pb, P0, Pd, H6, HH and H7. Do the check once, then call us if the code returns.
For E0, E8 and PP, Worcester Bosch’s troubleshooting table says to check that all shut-off valves in the water circuit are fully open, that the water filter is clean, that there is no air in the system, that the water pressure on the gauge is above 1 bar and that the expansion tank is intact. The installation instructions give a working range of 1 bar minimum to 3 bar maximum, so top up only if you have a filling loop and your manual allows it. Our guide to low pressure on a Worcester Bosch heat pump explains the gauge and filling loop in more detail.
For Pb, keep the unit powered; it is antifreeze mode, not a fault. For P0 and Pd, clear snow, leaves or debris from around the outdoor coil by hand, without tools, because a dirty or clogged external heat exchanger is a listed cause of P0. For H6 and HH, look from outside for ice, leaves or debris blocking the fan, and note whether the unit faces a strong wind, which Worcester Bosch lists as a cause of the fan running backwards. For H7, check for a power cut or tripped breaker; Worcester Bosch also says to keep the unit switched off for at least 3 minutes before switching it on again if it has been cycled on and off at close intervals.
What are the most common Worcester Bosch heat pump error codes?
The Compress 2000 AWF manual does not rank codes by frequency, so these are the ones with clear descriptions and causes an engineer can check. Causes listed by Worcester Bosch come first; anything marked general engineering knowledge is our own experience.
E0 and E8: water flow failure
E0 appears after three water flow failures and E8 is a single failure that is displayed three times and can reset after a few minutes. Worcester Bosch’s causes for E0 include a short or open flow switch circuit, insufficient water flow, a faulty flow switch and system pressure losses too high for the unit’s circulator. For E8 it adds the pump speed setting, the expansion tank, the backup heater supply and fuses if the fault occurs during defrost, and the pump and PCB fuses.
General engineering knowledge: a blocked strainer, sludge and scale in the plate heat exchanger are the usual reasons the flow switch opens. Check valves and pressure. If it returns, an engineer will bleed the system, clean the filter and check the pump.
PP and Hb: temperature difference and freeze risk
PP means the difference between the water entering and leaving the unit is abnormal. Hb is raised after three consecutive PP faults with leaving water below 7°C, and the alarm table says it is reset by a power failure. Worcester Bosch’s remedy for Hb is simply “see PP”, so the flow problem has to be found first. Our guide to the Worcester Bosch Pb and Hb freeze protection codes explains the difference between the two.
Treat repeated PP as a flow problem and fix it quickly, as low flow in cold weather risks freezing the plate heat exchanger. An engineer should find the cause before Hb is cleared.
Pb: antifreeze mode
Pb is not a protection fault. The alarm table says the alarm light does not flash, the remote control does not display Pb, and an antifreeze icon shows instead. Nothing needs doing beyond keeping the unit powered. Our guide to Do Heat Pumps Work in Cold Weather guide explains what else is normal in winter.
P0 and HP: low pressure protection
P0 means the refrigerant side is running at low pressure. Worcester Bosch lists no refrigerant in the system, a dirty or clogged external heat exchanger in heating or hot water mode, low water flow in cooling mode and a blocked electronic expansion valve or loose winding connector. HP is the cooling-mode version, raised when low pressure falls below 0.6 MPa three times in one hour, and it resets automatically.
Clear the area around the coil and check the fan is not blocked. Beyond that, call an engineer, because every other listed cause is on the refrigerant side.
P1, P3 and P4: high pressure, overcurrent and discharge temperature
P1 is the discharge temperature and high pressure control switch protection. In heating and hot water mode Worcester Bosch lists low water flow with high water temperature (expel air), water pressure below 0.1 MPa (fill to 0.15 to 0.18 MPa), too little refrigerant and a blocked expansion valve; in hot water mode it adds a cylinder coil with too little surface area; in cooling it adds a covered or dirty external heat exchanger. P3 (compressor overcurrent) and P4 (high discharge temperature) share the P1 checks, and P3 adds low supply voltage.
An engineer should restore flow and check the water pressure before suspecting the refrigerant circuit.
H6 and HH: DC fan failure
H6 is a DC fan error. Worcester Bosch lists a fan exposed to strong wind that makes it run in the opposite direction, with the remedy of turning the unit or fitting a guard, and a faulty fan motor. HH is raised after ten H6 failures within 120 minutes and resets after shutdown.
Look for ice, leaves, debris or an animal blocking the fan before anyone replaces it, and think about wind exposure if the unit sits in an open spot.
E3 to E7, E9, EA to EC, H2, H3, H5, H9 and HA: sensor failures
These cover the leaving water (T1), tank (T5), unit (T3), room (T4), inertial tank (Tbt1), suction (Th), discharge (Tp), solar, second tank (Tbt2), refrigerant (T2 and T2B), Ta, Tw2 and plate exchanger outlet sensors. For almost all of them Worcester Bosch gives the same three causes: a loose connector, a connector that is wet or contains water, and a failed sensor to be replaced.
An engineer tests the sensor resistance and dries or reseals the connector before replacing any board.
E2, H0, H1, HE and Hd: communication faults
E2 is between the user interface and the main hydraulic module board, H0 between the main PCB B and the hydraulic module board (no communication for 10 seconds), and H1 between the inverter module PCB A and the main PCB B. HE is listed in the alarm table as a hydraulic module to adapter board error, and Hd is between master and slave units in parallel systems. Worcester Bosch’s causes are disconnected or wrongly sequenced wires, strong magnetic fields or electrical interference from lifts or large transformers, and interference from power cables run alongside the control cable.
An engineer checks cabling and terminations first.
L codes and H4: inverter and compressor drive
L0, L1, L2, L4, L5, L7, L8 and L9 cover DC compressor module errors, DC bus low and high voltage, synchronisation, zero speed, phase sequence and speed variation above 15 Hz. H4 appears after three L signals in one hour and cannot be reset; the alarm table says to check the last three L signals to find the cause, while the troubleshooting table describes it as three P6 protection activations. Either way these need an engineer with refrigeration and electrical competence.
Which error code might you see in common situations?
These are the codes from the Compress 2000 AWF alarm table most likely in everyday situations. Do the first check, then call us if the code stays.
| Scenario | Codes you may see on a Worcester Bosch | First check |
|---|---|---|
| Cold snap and iced outdoor unit | Pb, P0, H6, HH, Hb | Keep the unit powered and clear snow from around it. Do not chip ice off the coil |
| Losing pressure or low pressure | E0, E8, PP, P1 | Read the gauge: Worcester Bosch wants more than 1 bar, and P1 can follow pressure below 0.1 MPa |
| Radiators lukewarm | E0, E8, PP, P1, P5 | Check valves are open and pressure is correct |
| No hot water | E4, EC | Check the hot water schedule on your controller |
| After a power cut | H7, F1, L1, E2, H0 | Give the system a few minutes to restart and check the breaker; wait at least 3 minutes before switching on again |
| Unit noisy or fan not spinning | H6, HH | From outside, look for ice or debris around the fan and note any strong wind |
| After a service or filter clean | E0, E8, PP | Check isolation valves were reopened and pressure is back above 1 bar |
How do I reset a Worcester Bosch heat pump?
You reset a Compress 2000 AWF alarm from the multifunction keypad after removing the cause. Worcester Bosch’s instructions are short: identify and remove the cause of the alarm, then reset the active alarm, and contact a service centre if in doubt. The same manual carries a notice that repeated resets can lead to irreversible damage such as malfunction of the system itself.
- Note the code; the “Active alarm” symbol on the keypad tells you one is present.
- Select MENU then SERVICE INFORMATION to view the alarms.
- Deal with any owner-level cause: reopen valves, restore pressure above 1 bar, clear the outdoor unit or reset a tripped breaker once.
- Reset the active alarm from the keypad.
- If the code returns, leave it and book an engineer rather than resetting again.
Some codes have their own reset behaviour. E8 can reset after a few minutes, HH resets after shutdown, HP resets automatically and Hb is cleared by a power failure. H4 cannot be reset at all, and the manual directs engineers to the last three L signals to find the real fault. On the Compress 7400i AW, you confirm a fault by pressing the selector, view active faults with the information key, and give the contractor the code, sub-code and user interface ID number.
Worcester Bosch error code list
This list covers every code in the Compress 2000 AWF alarm table (Table 53 of the installation and operating instructions). It applies to that range only, so check your manual if a description does not match. The manual also lists a Modbus register code beside each alarm, which is the number reported over a Modbus link to building controls.
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| E0 | Water flow failure (three times) | Flow switch circuit, low flow, faulty switch, pressure loss too high for the circulator | Valves open, pressure above 1 bar | Homeowner check, then engineer |
| E1 | Line-to-line or zero phase error (three-phase models) | Loose or wrongly sequenced power cables | Nothing owner-side | Engineer |
| E2 | Communication error between user interface and hydraulic module | Disconnected or wrongly sequenced wires, interference | Nothing owner-side | Engineer |
| E3, E4, E5, E6, E7 | Leaving water T1, tank T5, unit T3, room T4 or inertial tank Tbt1 sensor failure | Loose or wet connector, failed sensor | Nothing owner-side | Engineer |
| E8 | Water flow failure (displayed three times, can reset after minutes) | Closed valves, dirty filter, air, pressure below 1 bar, pump speed, expansion tank, fuses | Valves, filter if accessible, pressure | Homeowner check, then engineer |
| E9, EA, Eb, EC | Suction Th, discharge Tp, solar or second tank Tbt2 sensor failure | Loose or wet connector, failed sensor | Nothing owner-side | Engineer |
| Ed, EE | Entering water sensor Tw_in failure; hydraulic module EEPROM failure | Sensor connector; EEPROM data or board | Nothing owner-side | Engineer |
| P0 | Low pressure protection | No refrigerant, clogged external heat exchanger, low flow in cooling, blocked EEV | Coil clear of debris and ice | Homeowner check, then engineer |
| P1 | Discharge temperature or high pressure control switch protection | Low flow or air, pressure below 0.1 MPa, low refrigerant, blocked EEV, small cylinder coil, covered coil in cooling | Valves open, pressure | Engineer |
| P3 | Compressor overcurrent protection | As P1, plus low supply voltage | Nothing owner-side | Engineer |
| P4 | Exhaust (discharge) temperature overheating protection | As P1 | Nothing owner-side | Engineer |
| P5 | Twin to Twout or Twout to Twin protection, or water supply temperature too high | Flow or temperature difference | Valves open | Engineer |
| P6 | Module protection (IPDU and IR341) | Inverter module | Nothing owner-side | Engineer |
| Pb | Antifreeze mode (not a protection; alarm light does not flash) | Cold weather | Keep the unit powered | No action |
| Pd | Unit T3 over-temperature protection | Blocked airflow | Clear around the unit | Homeowner check, then engineer |
| PP | Abnormal temperature difference between entering and leaving water | Low flow | Valves open, pressure above 1 bar | Homeowner check, then engineer |
| H0 | Communication error between indoor unit and unit (10 seconds) | Disconnected or wrongly sequenced cable, interference | Nothing owner-side | Engineer |
| H1 | Communication error between unit and inverter module (IR341) | Board supply, loose or broken wire, boards | Nothing owner-side | Engineer |
| H2, H3 | Gas side T2 or liquid side T2B refrigerant temperature sensor failure | Loose or wet connector, failed sensor | Nothing owner-side | Engineer |
| H4 | Three L signals (L0/L1) in one hour, cannot be reset | Repeated inverter or compressor drive faults | Nothing owner-side | Engineer |
| H5 | Temperature sensor Ta failure | Ta sensor setting or faulty sensor or interface | Nothing owner-side | Engineer |
| H6 | DC fan failure | Strong wind driving the fan backwards; faulty fan motor | Fan clear from outside; wind exposure | Homeowner check, then engineer |
| H7 | Abnormal power supply voltage | Supply outside range; switched on and off at close intervals; main PCB | Breaker; wait 3 minutes before restarting | Homeowner check, then engineer |
| H8 | High pressure sensor failure | Loose connector or faulty sensor | Nothing owner-side | Engineer |
| H9, HA | Sensor Tw2 failure; plate exchanger outlet temperature sensor failure | Loose or wet connector, failed sensor | Nothing owner-side | Engineer |
| Hb | Three consecutive PP faults with leaving water below 7°C (reset by power failure) | Unresolved low flow in cold conditions | Valves, pressure | Engineer |
| Hd | Communication error between slave and master (parallel units) | Wrong address, wiring, board fuse | Nothing owner-side | Engineer |
| HE | Communication error between hydraulic module and adapter board | Board or wiring | Nothing owner-side | Engineer |
| HF | Unit (inverter module) EEPROM failure | EEPROM data, chip or module | Nothing owner-side | Engineer |
| HH | H6 failure ten times in 120 minutes (reset after shutdown) | As H6 | Fan clear from outside | Homeowner check, then engineer |
| HL | PFC module fault | Power factor correction module | Nothing owner-side | Engineer |
| HP | Cooling mode low pressure protection (below 0.6 MPa three times in one hour, resets automatically) | As P0 | Nothing owner-side | Engineer |
| C0 | Multiple units configured as master | Configuration | Nothing owner-side | Engineer |
| C7 | Heat sink over-temperature protection | Inverter cooling | Nothing owner-side | Engineer |
| bH | PED board failure | Board; power off for 5 minutes then retest | Nothing owner-side | Engineer |
| F1, L1 | DC bus low voltage protection | Supply or inverter | Breaker after a power cut | Engineer |
| L0, L2, L4, L5, L7, L8, L9 | DC compressor module error, DC bus high voltage, synchronisation or closed circuit, zero speed, phase sequence, speed variation or speed difference above 15 Hz | Inverter or compressor drive | Nothing owner-side | Engineer |
Where do I find the Worcester Bosch fault code list?
Worcester Bosch publishes its heat pump installation and user manuals in its online literature library, organised by manufacture date. The Compress 2000 AWF installation and operating instructions carry the alarm table and troubleshooting table used here (section 11.4 and chapter 12). The Compress 7400i AW user guide explains its own fault display, and the Compress 3400i AWS operation manual has no code list, so ask your installer for the installation instructions for that range.
- Worcester Bosch heat pump manuals, including the Compress 2000 AWF installation and operating instructions
- Worcester Bosch heat pump user manuals, including the 3400i AWS and 7400i AW guides
If your controller shows a code that is not in this guide, check the installation manual for your exact model and manufacture date before acting on it.
When to call an engineer
Call an engineer for a Worcester Bosch heat pump when E0, E8 or PP returns after you have checked the valves and pressure, when Hb, H4 or HH appears, when any P or L code shows apart from Pb, or when the Compress 7400i displays a fault with a sub-code. If the fault involves refrigerant, which covers P0, P1, P4, H8 and HP, isolate the unit at the fused spur or isolator if you hear hissing or smell anything unusual, and wait for an engineer.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We work on Worcester Bosch heat pumps across the Compress range, and a Our repair service starts with reading the service information screen and a clear quote. Our Worcester Bosch Heat Pump Review explained sets out the ranges and how they differ.
Flow, fan and sensor alarms are often caught early at an annual service, where the water filter is cleaned, the pressure is restored and the wet connectors Worcester Bosch mentions so often are dried and resealed. Our cover plans combine that service with callouts, and the areas we cover page confirms we reach you. For the case for a plan, read Is Heat Pump Cover Worth It guide, and for what the annual visit prevents, Why Heat Pump Servicing Is So Important guide.
Frequently asked questions
Why do the codes in my manual not match this list?
Worcester Bosch has sold several heat pump ranges, and alarm lists differ between them. The two-character codes here are from the Compress 2000 AWF; the Compress 7400i AW shows a fault code and sub-code on its user interface instead, and older Greensource units have their own displays. Always go by the manual for your exact model and manufacture date; the model name is on the unit’s data plate.
What is the Modbus number next to some codes?
The Compress 2000 AWF alarm table lists a Modbus register code beside each alarm, for example 1 for E0 and 50 for P0. That is the number reported over a Modbus link to building controls or a monitoring system. Most homes will never see it, but an engineer may use it on larger or connected systems, and it is useful if your installer monitors the unit remotely.
Will an alarm code void my warranty?
An alarm on its own does not affect your warranty; it is the heat pump protecting itself. Warranty problems usually come from unqualified repairs inside the unit, repeated resets that Worcester Bosch warns can cause irreversible damage, or missed servicing, so check your terms and keep a record of each annual visit.
Does an L code mean the compressor has failed?
Not necessarily. L codes also cover DC bus low and high voltage, phase sequence, synchronisation and speed variation faults, which are often supply or board issues rather than a failed compressor. An engineer checks the supply voltage, the inverter module and the last three L signals that H4 records before condemning the compressor.
What can I check before paying for a call-out?
Confirm the unit has power, airflow around it is clear and the controller settings have not changed. Check the pressure gauge reads above 1 bar and that valves are open, then note the code from the service information screen and the model name before you call. Worcester Bosch’s E8 checklist is a good template for what an engineer will ask you about.
Sources and further reading: Worcester Bosch, Compress 2000 AWF installation and operating instructions 6721859133 (November 2023), section 11.4 alarms (Table 53), chapter 12 troubleshooting and the water pressure requirements; Worcester Bosch, Compress 7001i/7400i AW AWE user guide 6721835320 (September 2021), section 3.5 faults; Worcester Bosch, Compress 3400iAWS E operation manual 6721852787 (January 2023). Checked October 2026.