Black Friday: up to 16% off standard plan prices, ends 23:59 on 30 November.Terms

Heat pump vs gas boiler: which has lower carbon emissions?

Research image showing 0.56 kg, the grid carbon intensity per kWh at which a heat pump at SPF 2.8 breaks even with a gas boiler.

The operating carbon comparison depends on the carbon intensity of electricity and on how much electricity the heat pump uses. With a gas boiler at 90% efficiency and gas emissions of 0.18 kg CO₂e per kWh of fuel (the government’s 2026 factor for natural gas, rounded), the boiler emits 0.20 kg CO₂e per kWh of useful heat. A heat pump at SPF 2.8 breaks even when grid electricity is 0.56 kg CO₂e per kWh on the same accounting basis. Sources: UK government conversion factors and Catapult field data.

Compare the same quantity of delivered heat

Operational emissions for 10,000 kWh of delivered heat
Example electricity factor Heat pump at SPF 2.8, per 10,000 kWh heat Gas boiler at 90%
0.15 kg CO₂e/kWh 536 kg CO₂e 2,000 kg CO₂e
0.25 kg CO₂e/kWh 893 kg CO₂e 2,000 kg CO₂e
0.56 kg CO₂e/kWh 2,000 kg CO₂e 2,000 kg CO₂e

The factors are rounded scenario inputs. For a formal calculation use the appropriate government workbook factors and specify whether upstream emissions and grid losses are in scope. An annual average electricity factor estimates emissions differently from a time-specific grid factor.

Our heat pump vs boiler guide covers running costs and lifespan as well as carbon.

What does a full environmental comparison include?

A whole-life assessment also covers manufacturing, refrigerant leakage, transport, repairs and disposal. The comparative equipment lives and the electricity mix over those lives affect the result. State the boundary clearly whenever quoting a saving, so a lifetime estimate is easy to distinguish from the operating model above.

Our guide to hydrogen boilers vs heat pumps looks at the other low-carbon option often raised.

Promotion terms

Loading the promotion terms…