At a glance
- Ideal Logic Air heat pump error codes are numbers shown on the control box on the cylinder, with a bell icon at the top of the screen; fault 370 means an outdoor unit fault and carries an F sub-code from F0 to F27, read on the Info screen as, for example, 370 F27.
- 370 F27 is a no water flow fault; Ideal’s user guide says to check the system pressure is at 1 to 1.5 bar and refill with the filling loop if it is under 1 bar.
- 127 is an anti-Legionella temperature fault; Ideal’s check is that the fused spur near the cylinder feeding the immersion heater relay has not been switched off.
- 60 and 65 are room thermostat 1 and 2 faults; Ideal’s check is the Halo Air batteries, after which the thermostat re-pairs automatically.
- Ideal’s user guide says most fault codes can be cleared with a power cycle: turn off the rotary isolator near the outdoor unit, wait 1 minute, turn it back on and let the heat pump boot for a few minutes.
- Work inside the outdoor unit needs someone familiar with R32, and work on the refrigeration circuit must be done by a qualified engineer.
What do Ideal Logic Air heat pump error codes mean?
An Ideal heat pump error code is a fault number the Logic Air system shows on its control box, with a bell icon at the top of the screen to tell you a fault is present. Some codes stand alone, such as 127 or 385. Others come in two parts: fault 370 means the outdoor unit has reported a problem, and an F sub-code from F0 to F27 tells you what it is. Ideal’s user guide also notes that 370 can be caused by poor flow through the pipework rather than the outdoor unit itself.
To see the full code, go to the control box on the cylinder and turn the wheel so the bar graph symbol is highlighted, which opens the Info screen and shows the complete code, for example 370 F27. This guide is about Ideal’s Logic Air heat pumps, not its Logic boilers, which use a different code system, and it uses the fault code list in the Logic Air installation and maintenance manual (252130 A02, for units from serial AHU onwards) together with the Logic Air user guide and maintenance manual.
If your Logic Air is not showing a code, or you want to rule out the basics first, our guide to a Guide to Heat Pump Not Working covers the general checks for any make. The Heat Pump Error Codes guide covers the other makes we see. Before you check anything outside, switch the outdoor unit off at its isolator and never open the casing.
Is it safe to fix an Ideal heat pump fault yourself?
Only the simple checks are safe for a homeowner on a Logic Air; anything inside the outdoor unit, cylinder or control box is for an engineer. Ideal’s user guide covers the owner checks itself: the power cycle, the pressure check for 370 F27, the immersion spur for 127 and the Halo Air batteries for 60 and 65.
Never remove panels or touch the wiring, boards or sensors, even when a code names a single thermistor. Ideal’s installation manual says all maintenance and servicing must be carried out by a competent and sufficiently qualified engineer, that removing the heat pump’s exterior casing is only for people familiar with the risks of R32 refrigerant, and that work on the electrical system is for competent persons only.
Refrigerant work is restricted by law: Ideal’s manual states that work on the refrigeration circuit must only be carried out by a qualified engineer, so pressure, compressor and discharge temperature faults are not DIY jobs. Work inside the unit by anyone unqualified can also affect your Ideal warranty. If you smell burning or hear hissing at the outdoor unit, isolate it at the fused spur or isolator and call an engineer.
Which Ideal error codes can you check yourself?
Ideal’s user guide gives homeowner checks for four faults: 370 F27, 127, 60 and 65. A few others, the fan, airflow and outdoor connection faults, also have a safe first step: 370 F17, 370 F0, F1 and F22, 490, 499, 516, 385 and 370 F21 and F26.
For 370 F27, check the pressure gauge reads 1 to 1.5 bar; if it is below 1 bar, top up through the filling loop as the user guide describes. If the code is still showing after topping up, Ideal says to contact your installer because the system filter could be blocked or there may be air in the primary pipework. Our guide to the Ideal 370 F27 and AE low water pressure faults shows where the gauge and filling loop are on the cylinder. For 127, check the fused spur near the cylinder that supplies the immersion heater relay in the control box is switched on; Ideal says it should be left on at all times. For 60 and 65, replace the Halo Air batteries and leave it to pair back to the heat pump automatically.
For 370 F17, the fan fault, clear leaves and snow from the outdoor unit by hand without reaching inside; our guide to an Ideal heat pump with a frozen outdoor unit covers the winter version. For 370 F0, F1 and F22 and for 490, 499 and 516, all no outdoor connection faults, check the isolator by the outdoor unit is on and no breaker has tripped. For 385, low mains voltage, and 370 F21 and F26, outdoor power supply faults, do the power cycle once after a power cut. Stop and call an engineer if any of these returns, or if a breaker trips again.
What are the most common Ideal heat pump error codes?
The Ideal codes we see most often are 370 F27 for no water flow, the fan and outdoor connection faults, and the room thermostat codes 60 and 65. Ideal’s fault list names each code and refers engineers to the maintenance manual for the diagnosis; causes marked general come from engineering experience, not the manual.
370 F27: no water flow (also F23 and F24)
Ideal’s user guide says to check the system pressure is 1 to 1.5 bar and top up if it is below 1 bar, and that if the code stays it points to a blocked system filter or air in the primary pipework. The maintenance manual’s troubleshooting for low water flow adds checks on the water pressure level, closed valves in the water loop, anti-freeze valves and thermostatic radiator valves, the filter trap, the condenser pump speed and whether a pump fault is displayed. General causes also include sludge in the magnetic filter or strainer and a failing pump.
F23 is a hydraulic heat exchanger temperature fault and F24 a primary circulation pump fault. If pressure keeps dropping, book an engineer to find the leak, clean the filter and bleed the system.
370 F17 and F15: fan fault and current trip
F17 is a heat pump fan fault. Ideal’s user guide advises clearing leaves and snow from the unit, and generally ice building up on the coil or fan when defrost is struggling is the cause in winter, though a fan motor can also fail. F15 is a current trip in the outdoor unit, which the manual sends to the same troubleshooting section as the outdoor electrical error F13, so it is an engineer job rather than an airflow check. Do not chip at ice on the unit.
370 F20 and F14: low pressure and pressure sensor
F20 is outdoor low pressure and F14 an outdoor pressure sensor fault. General causes are refrigerant loss, an iced coil or a failed sensor. Both need an engineer.
370 F16, F18 and F19: compressor and discharge temperature
These are a heat pump compressor fault, an outdoor discharge temperature fault and a compressor temperature fault. In general, refrigerant loss, a blocked coil, poor airflow or a worn compressor sit behind them. Clear the unit if it is blocked, then call an engineer.
370 F2 to F12 and F25: outdoor thermistor faults
These codes name a specific outdoor sensor: the outdoor heat exchanger (F2), discharge (F5), compressor (F6), intermediate heat exchanger (F7), outlet heat exchanger (F8), defrost (F9), heatsink (F10), PFC (F11), expansion valve (F12) and evaporator outlet (F25) thermistors. General causes are a failed sensor, a loose plug or a damaged cable. A faulty defrost sensor can also cause poor or mistimed defrosting.
370 F3, F4 and F13: inverter and electrical faults
F3 is a heat pump inverter fault, F4 an outdoor electrical filtering fault and F13 an outdoor electrical error. These are engineer jobs, and the maintenance manual’s power supply troubleshooting checks the breaker, loose cables, voltage drops, momentary power failures and electrical noise before any part is replaced.
370 F0, F1, F22 and 490, 499, 516: no outdoor connection
All of these mean the system has lost contact with the outdoor unit. Generally that is an isolator switched off, a tripped supply or a loose or damaged communication cable. Check the isolator and breakers, then call an engineer if it stays.
127: anti-Legionella fault
Ideal’s user guide says 127 means the anti-Legionella cycle has not been achieved. Check the fused spur near the cylinder that feeds the immersion heater relay is on, and contact your installer if the fault persists with the spur on. In general, a failed immersion element or cylinder sensor is the next suspect.
60 and 65: room thermostat faults
These relate to room thermostat 1 and 2. Ideal’s guide says to check the Halo Air batteries and replace them if necessary, after which it pairs back automatically. Generally, a lost wireless link from distance or interference is the other cause.
10, 26, 33, 44, 50 and 366: sensor faults
These are the outside sensor, header thermistor, indoor flow thermistor, return thermistor, DHW thermistor and room temperature sensor. Ideal’s fault finding for each checks the wiring is securely connected at both ends, then the sensor’s resistance against the stated values, before replacing the sensor or the board. An engineer will test it before replacing anything.
Which error code might you see in common situations?
What is going on around the house is often the quickest route to the right code. These are codes from Ideal’s Logic Air list.
| Situation | Codes you may see on an Ideal | First check |
|---|---|---|
| Cold snap and iced outdoor unit | 370 F17, F20, F9 | Frost during a defrost is normal; if ice stays, clear snow and leaves around the unit. Our guide to Guide to Do Heat Pumps Work in Cold Weather shows what is normal |
| Losing pressure or low pressure | 370 F27 | Check the gauge reads 1 to 1.5 bar and top up if below 1 bar |
| Radiators lukewarm | 370 F27, F23, F24 | Check pressure first. Cooler radiators in mild weather are normal on a heat pump |
| No hot water | 127, 50, 126 | Check the spur near the cylinder is on and the hot water settings |
| After a power cut | 385, 370 F21, F26, 490, 499, 516 | Do the isolator power cycle once the supply is stable |
| Unit noisy or fan not spinning | 370 F17, F16 | Look for ice or debris around the fan without reaching inside |
| After a service or filter clean | 370 F27, F24 | Check pressure is back to 1 to 1.5 bar and valves were reopened |
How do I reset an Ideal heat pump?
Ideal’s user guide gives one general reset: most fault codes can be cleared with a power cycle. Turn off the rotary isolator near the outdoor unit, leave the power off for 1 minute, turn it back on and leave the heat pump to boot up for a few minutes. If the fault code persists, Ideal says to contact your installer or the Ideal Heating support team.
- Write down the full code from the Info screen, including any F sub-code after 370.
- Deal with any owner-level cause: top up the pressure to 1 to 1.5 bar, switch the immersion spur back on or replace the Halo Air batteries.
- Turn off the rotary isolator near the outdoor unit and wait 1 minute.
- Turn it back on and leave the heat pump to boot for a few minutes before judging whether the fault has cleared.
- If the code comes back, leave it and book an engineer.
Repeated resets without fixing the cause are a bad idea. Ideal’s list includes code 134, a re-occurring heat pump fault, and the “number of heat pump starts exceeded” fault, both of which generally appear when an earlier fault has never been put right.
Ideal error code list
This list covers the Logic Air fault codes in section 9.1.1 of Ideal’s installation and maintenance manual, including the 370 F sub-codes, with the titles as Ideal prints them. Units with earlier serial numbers (up to AHL) have their own edition of the manual, so check the current guide for your model.
| Code | Meaning | Likely cause | What to check | Who should act |
|---|---|---|---|---|
| 10, 26, 33, 44, 50, 366 | Outside sensor, header thermistor, indoor flow thermistor, return thermistor, DHW thermistor or room temperature sensor fault | Wiring, connector or failed sensor | Nothing owner-side | Engineer |
| 60, 65 | Room thermostat 1 or 2 fault | Flat Halo Air batteries or lost pairing | Replace batteries, let it re-pair | Homeowner check |
| 81, 82, 83, 84 | LPB (cascade) short circuit or communication fault; LPB address collision; BSB short circuit; BSB address collision | Bus wiring or addressing | Nothing owner-side | Engineer |
| 100, 102 | Two clock time masters; clock without back-up | Configuration | Nothing owner-side | Engineer |
| 106 | Source temperature too low | Operating conditions | Nothing owner-side | Engineer |
| 126 | 7093 DHW setpoint fault | Hot water setting outside limits | Hot water settings | Engineer |
| 127 | Anti-Legionella temperature fault | Immersion spur off; immersion or cylinder sensor | Fused spur near the cylinder is on | Homeowner check, then engineer |
| 134 | Re-occurring heat pump fault | An earlier fault not resolved | Note the previous codes | Engineer |
| 146 | Configuration error | Commissioning settings | Nothing owner-side | Engineer |
| 171, 369 | Alarm contact 1 active; external fault | External device or wiring | Nothing owner-side | Engineer |
| 385 | Low mains voltage fault | Supply | Power cycle after a power cut | Homeowner check, then engineer |
| 489 | No cascade master fault | Cascade configuration | Nothing owner-side | Engineer |
| 490, 499, 516 | No outdoor connection fault | Isolator off, tripped supply, communication cable | Outdoor isolator and breakers on | Homeowner check, then engineer |
| 506 | Back-up boiler no temperature rise fault | Hybrid boiler | Nothing owner-side | Engineer |
| 7 | Number of heat pump starts exceeded | Repeated starts after an unresolved fault | Nothing owner-side | Engineer |
| 370 F0, F1, F22 | No outdoor connection fault | Isolator, supply or cable | Outdoor isolator and breakers on | Homeowner check, then engineer |
| 370 F2, F5 to F12, F25 | Outdoor heat exchanger, discharge, compressor, intermediate HX, outlet HX, defrost, heatsink, PFC, expansion valve or evaporator outlet thermistor fault | Failed sensor, plug or cable | Nothing owner-side | Engineer |
| 370 F3, F4, F13 | Heat pump inverter fault; outdoor electrical filtering fault; outdoor electrical error | Inverter or supply | Nothing owner-side | Engineer |
| 370 F14 | Outdoor pressure sensor fault | Sensor or wiring | Nothing owner-side | Engineer |
| 370 F15 | Current trip | Electrical fault | Nothing owner-side | Engineer |
| 370 F16 | Heat pump compressor fault | Supply, overheating or compressor | Nothing owner-side | Engineer |
| 370 F17 | Heat pump fan fault | Ice, debris or fan motor | Unit clear of leaves and snow | Homeowner check, then engineer |
| 370 F18, F19 | Outdoor discharge temperature fault; compressor temperature fault | Refrigerant loss, blocked coil, airflow | Airflow clear | Engineer |
| 370 F20 | Outdoor low pressure | Refrigerant loss or iced coil | Nothing owner-side | Engineer |
| 370 F21, F26 | Outdoor power supply fault | Supply | Power cycle after a power cut | Homeowner check, then engineer |
| 370 F23, F24 | Hydraulic heat exchanger temperature fault; primary circulation pump fault | Low flow, pump | Pressure and valves | Engineer |
| 370 F27 | No water flow fault | Low pressure, blocked filter, air, closed valves | Gauge at 1 to 1.5 bar; top up if under 1 bar | Homeowner check, then engineer |
Where do I find the Ideal fault code list?
Ideal publishes the Logic Air installation and maintenance manual, user guide and maintenance manual as PDFs on its own website, with fault codes covered in section 9 of the installation manual and the troubleshooting flows in the maintenance manual. Homeowner guides for Ideal products are in its user guides library.
- Ideal Logic Air heat pump guides page, with the installation guide, maintenance manual and user guide
- Ideal Heating user guides library
If your control box shows a code that is not in this guide, check the installation manual for your serial number range before acting on it.
When to call an engineer
Call an engineer for a Logic Air when 370 F27 stays after the pressure is back to 1 to 1.5 bar, when 127 persists with the immersion spur on, when any thermistor, inverter, pressure or compressor sub-code appears, or when 134 or the heat pump starts exceeded fault shows. For 370 F20, F18 or F19, which can mean refrigerant loss, isolate the unit at the fused spur or isolator if you hear hissing and wait for an engineer rather than looking for the leak yourself.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. A repair engineer visit starts with reading the full code from the Info screen, testing the part behind it and a quote before any work goes ahead.
Many of these faults, especially 370 F27 and the fan code, are less likely on a system that is looked after, because the annual visit covers the filter, the pressure and the outdoor coil; Guide to Why Heat Pump Servicing Is So Important explains what the visit prevents. Our heat pump cover plans include that service and cover callouts, and the find your nearest engineer page confirms we reach you. If you are deciding whether a plan suits you, read guide to Is Heat Pump Cover Worth It.
Frequently asked questions
Are Ideal heat pump codes the same as Ideal boiler codes?
No. Ideal’s Logic and Logic Plus boilers use a separate fault code system, and Ideal’s own fault codes support page covers boilers rather than the Logic Air. Make sure any list you follow is for the Logic Air heat pump, and read the full code from the Info screen on the control box, including the F sub-code after 370.
Does an Ideal error code void my warranty?
No, a code on its own does not affect your warranty. What can affect it is unqualified work inside the unit, which Ideal’s manual restricts to competent engineers familiar with R32, or missed servicing if your terms require it. Check your warranty paperwork before anyone opens a panel, and keep a record of each service.
Is water under the outdoor unit a fault?
Usually not. A heat pump sheds condensate from the outdoor unit as it runs and defrosts, and water on the ground beneath it in cold weather is normal. A steady drip from the pipework, the cylinder or the control box is a different matter, and if the pressure gauge is also falling the two are probably linked, so book a check.
Does 370 F16 mean the compressor has failed?
Not necessarily. Ideal titles F16 a heat pump compressor fault, but the maintenance manual’s troubleshooting for the outdoor unit starts with the power supply, loose connections, voltage drops and electrical noise before any part is condemned. An engineer will test the supply and the inverter before replacing a compressor.
How long does an Ideal heat pump repair take?
Flow, sensor and wiring faults are often fixed in one visit. If a part such as a pump, fan motor or board needs ordering, expect a second visit. Refrigerant leaks take longer, because the leak must be found and tested before the system is recharged, and that work needs a qualified engineer.
Sources and further reading: Ideal Heating, Logic Air installation and maintenance manual 252130 A02 (serial AHU onwards), section 9 fault finding; Ideal Heating, Logic Air user guide (2023, Rev C), fault codes and customer fault finding; Ideal Heating, Logic Air 8-10 maintenance manual (May 2023), troubleshooting 24 and 25. Checked October 2026.