At a glance
- CTC’s EcoZenith i360 Installation and Maintenance Manual (162 505 77-9, April 2026) lists no alarm for low heating system pressure.
- Filled cold system: “approx. 1 bar or 0.2 to 0.3 bar above the pre-pressure on the expansion tank”; the supplied expansion tank is pre-pressurised to about 1 bar and the heating circuit safety valve is 2.5 bar.
- CTC’s end customer overview says to check the system pressure regularly, ask the installer what it should be, “this will normally be around 1 bar”, and refill if it is too low.
- Critical alarms E135, E211, E216 and E217 are flow and freeze-risk alarms; they can be acknowledged three times with code 4005, and after four alarms the heat pump is blocked until the installer is contacted.
- E043 “Low pressure sensor” is a refrigerant sensor alarm, not a heating water alarm.
- An alarm shows as a red or yellow flashing LED on the display with an info message at the bottom of the screen.
Why is my CTC heat pump showing low pressure?
A CTC heat pump shows low water pressure on the manometer, because CTC’s manuals list no alarm for low heating system pressure. We want to be plain about that. The CTC EcoZenith i360 Installation and Maintenance Manual, which covers the indoor module that controls EcoAir and EcoPart heat pumps, has no bar threshold tied to an alarm and no alarm text that reads “low system pressure”. The end customer overview for the same product says only that you should check the pressure regularly and that “if the pressure is too low, the system must be refilled”.
What CTC does list are flow alarms on air-to-water models, which can be triggered when low water or air in the system reduces circulation. These are the critical alarms in section 17.5 of the i360 manual, “Risk of freezing”:
- E135, Risk of freezing (all air/water heat pumps): the heat pump out temperature is lower than 15 °C during a defrost period, or the difference between heat pump in and out exceeds 15 °C for more than 20 seconds. Possible cause: “the circuit temperature and/or flow rate is too low”. Actions include supplementing with a volume tank and checking the circulation pump, dirt filter, pipe system and pipe size.
- E211, Risk of freezing low flow (EcoAir 600M, 700M and C100 with the flow sensor accessory): flow below 10 l/min on the 610M, 614M, 708M and 712M, or 15 l/min on the 622M and 720M, for more than 30 seconds during a defrost period.
- E216, HP flow temp diff (EcoAir 600M, 700M, C100): the difference between heat pump in and out exceeds 12 °C in heat operation for more than 15 minutes. Action: check the dirt filter, pipe system and circulation pump speed.
- E217, HP charge pump flow (EcoAir 400): charge pump speed above 70 percent in heat operation for more than 30 minutes, with the same flow checks.
Critical alarms need care. The manual says they can be acknowledged three times by entering code 4005, and after four alarms the heat pump is blocked and you must contact the installer. After one year without alarms the counter resets. That is a good reason not to keep resetting. The alarm message list also has E135 with the note that “the water volume in the system may be too low” and “the flow may be too low”, which is the clearest link CTC makes between lost water and an alarm. Our CTC heat pump error codes guide lists the rest, and the Heat Pump Not Working questions answered covers checks that are the same on any brand.
CTC also has alarms named “low pressure”, and again these are not about your heating water. E043 “Low pressure sensor” sits in the sensor alarm list alongside the high pressure sensor and the suction gas sensor, so it is a refrigerant circuit sensor fault. E040 “Low brine flow” is for ground source units, where air in the collector is the usual cause. If the display says low pressure, check which circuit it is talking about. Any refrigerant-side fault is for an engineer only.
What pressure should a CTC heat pump be?
A CTC system should read about 1 bar when cold, according to the EcoZenith i360 manual. The filling instruction is to “check the manometer for a filled cold system (approx. 1 bar or 0.2 to 0.3 bar above the pre-pressure on the expansion tank)”. The expansion tank supplied with the i360 is pre-pressurised to approximately 1 bar and must be adjusted to suit the building before the system is filled, and the manual states that “the system pressure must be set 0.3 bar higher than the pre-pressure in the expansion tank”. The tank’s safety valve for the heating circuit is 2.5 bar, so that is the ceiling.
The manometer, filling valve, safety valve and automatic bleed valve are supplied with the EcoZenith i360 and fitted by the installer on the connections at the top of the unit, with the safety valve doubling as a quick air release during filling. On an EcoAir monobloc paired with a different indoor module the gauge is wherever the installer put the filling arrangement, usually near the cylinder or buffer. Ask your installer for your own value, as CTC’s overview itself advises, and check the installation manual for your model if you have an EcoZenith i255, i555 or an older EcoLogic controller, because the figures above are from the i360 document.
Why does a CTC heat pump keep losing pressure?
- A leak at a joint, valve, pump connection or radiator.
- A failed expansion vessel that lets pressure swing. CTC’s filling instructions tie the correct system pressure directly to the tank’s pre-pressure, so a tank that has lost its charge upsets the whole reading.
- Air in the system, released by the automatic air vent. CTC says bleeding “is very important for the product to function” and lists problems that bleeding solves in its troubleshooting chapter.
- The safety valve discharging and not reseating. CTC’s overview says to fit or turn the safety valve about four times a year to keep it working.
- Recent bleeding or radiator work without a proper top-up. CTC advises bleeding the radiator system about a month after installation and at least once a year.
- A blocked dirt filter, which cuts flow and can trigger the flow alarms above. The manual says to clean the dirt filter regularly.
- A circulation or charge pump fault, with the same symptoms.
- A gauge or sensor fault, so the reading is wrong.
Low pressure and low flow are closely linked, which is why we have covered both here. A system that has lost water has less to circulate, and air that replaces it makes pumps struggle. CTC’s own wording on E135 reminds you that a water volume that is too low is a possible cause. In practice, an engineer will check the pressure first, then the dirt filter, then the pump, and only then move on to sensors. The defrost cycle is where it bites: E135 and E211 are both defined during a defrost period, when the EcoAir needs warm water from the house to clear its coil, and our guide to the CTC E135 risk of freezing alarm goes through that alarm on its own.
If you have an EcoZenith or EcoLogic controller, the info message at the bottom of the touchscreen gives more detail than the flashing light on its own. The manual’s signal table reads: green LED, OK; red or yellow flashing LED, alarm; info message at the bottom, information about the current status. Take a photo of the screen before you do anything, because the engineer will want the exact wording, plus the 12-digit serial number found behind the magnetic strip above the display.
How do I top up the pressure on a CTC heat pump?
CTC’s end customer overview tells the owner to check the pressure regularly and refill if it is too low, so topping up is an expected owner task on an EcoZenith, provided you know your target figure and can reach the filling valve. The order is:
- Read the manometer with the system cold and note the figure. CTC says around 1 bar is normal, but ask your installer for your own value.
- Look for visible drips, wet floors and damp patches around the unit, cylinder and pipework.
- Check radiator and zone valves are open.
- Write down any alarm text and code from the display or the info message at the bottom of the screen.
- Open the filling valve slowly, watch the manometer rise to your target, and close the valve. Do not exceed the 2.5 bar safety valve setting.
- Bleed radiators only if you are confident. CTC advises bleeding about a month after installation and at least once a year, and the gauge drops after bleeding, so recheck it afterwards.
See our guide to Heat Pump Losing Pressure guide first if you have not done this before.
What not to do:
- The refrigerant circuit, including the sensor behind E043, is for qualified engineers only.
- Do not remove the front panel; the electrical switchboard and the max thermostat reset sit behind it.
- Do not fill towards the 2.5 bar safety valve setting; stop at your installer’s figure.
- Topping up more than once is CTC’s own threshold for a fault, so do not keep going.
- Do not use code 4005 to acknowledge critical alarms repeatedly, as the heat pump will block after the fourth alarm.
Which CTC codes appear with low pressure?
These are the verified flow-related alarms from the CTC EcoZenith i360 manual. None is a direct low water pressure code.
| Code | Meaning | First step |
|---|---|---|
| E135 | Risk of freezing (critical); heat pump out below 15 °C during defrost, or in/out difference over 15 °C for 20 seconds; water volume or flow may be too low | Check pressure and valves, do not keep resetting, then book an engineer |
| E211 | Risk of freezing low flow (critical, EcoAir 600M/700M/C100 with flow sensor); flow under 10 or 15 l/min for 30 seconds during defrost | Book an engineer to check pump, dirt filter, pipe size and flow sensor |
| E216 | HP flow temp diff (critical); in/out difference over 12 °C for 15 minutes in heating | Book an engineer to check dirt filter, piping and pump speed |
| E217 | HP charge pump flow (critical, EcoAir 400); charge pump over 70 percent for 30 minutes | Book an engineer to check filter, piping and pump settings |
| E043 | Low pressure sensor; refrigerant-side sensor fault | Call an engineer. Not a water pressure fault |
After four occurrences of a critical alarm the display shows a follow-on code, E218 for E135, E219 for E211, E220 for E216 and E221 for E217, which means the heat pump is blocked until the installer clears it.
How can you stop it happening again?
- Book an annual service. Our guide to Heat Pump Annual Service Checklist covers pressure, filters, the expansion vessel and pumps, and More on why heat pump servicing is so important explains the running-cost side.
- Clean the dirt filter regularly, as CTC’s maintenance section requires, and consider a Heat Pump Powerflush guide if the system is sludgy.
- Treat small drips quickly. See Guide to Heat Pump Leaking Water.
- Bleed the radiators about a month after installation and at least once a year, as CTC’s overview advises, and top up afterwards.
- Check the gauge monthly and note the reading, and read our guide to More on do heat pumps work in cold weather before the defrost season.
When to call an engineer
- You have had to top up more than once.
- Any critical flow alarm (E135, E211, E216 or E217) appears.
- The safety valve is dripping or you can see a leak.
- The display shows a low pressure sensor alarm such as E043.
- Radiators stay cold after bleeding.
- You have lost heating or hot water.
Book early. Four critical alarms and the heat pump blocks itself, so a delay can turn a small fault into a no-heating call-out. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Our engineers find the leak, check the expansion tank pre-pressure against CTC’s figure, clean the dirt filter and clear the alarm. Book a heat pump repairs, see breakdown cover and annual servicing, or check the where we work. If you are weighing a plan up, read Is Heat Pump Cover Worth It questions answered.
Frequently asked questions
What pressure should a CTC heating system be at?
CTC’s EcoZenith i360 manual says a filled cold system reads approximately 1 bar, or 0.2 to 0.3 bar above the expansion tank pre-pressure, and the end customer overview says to ask your installer for the right value. We cannot give a figure that applies to every CTC model, so check your own manual.
How often should I bleed the radiators?
CTC’s overview says to bleed the radiator system and products about a month after installation, and at least once per year, and to close the bleed screw on the automatic bleeder about three months after installation. Bleeding lowers pressure, so check the manometer afterwards and top up to your figure.
What does “critical alarm” mean on a CTC?
It is an alarm the heat pump treats as serious: E135, E211, E216 and E217. Each can be acknowledged three times by entering code 4005 in the service menu. After four alarms the heat pump is blocked and the installer must be contacted, and the count only resets after a year with no alarms.
Should I operate the safety valve myself?
CTC’s end customer overview says to fit or turn the safety valve about four times a year to check it works. Expect a little water to come out and the gauge to drop slightly. If no water runs, or it keeps dripping afterwards, get an engineer to look at it.
Why does my CTC say low pressure when the gauge looks fine?
The alarm is almost certainly E043, the low pressure sensor, which belongs to the refrigerant circuit, not the heating water. Leave it to an engineer. A true loss of heating water shows on the manometer, not as an alarm.
Sources and further reading: CTC, Installation and Maintenance Manual, CTC EcoZenith i360, 162 505 77-9, 2026-04-17: sections 5.5 to 5.10 (expansion tank, safety valve, filling and bleeding), 14.3 alarm management, 17.4 alarm messages and 17.5 critical alarms (CTC PDF); CTC, End customer overview, CTC EcoZenith i360, 16250576-5 (CTC PDF). Checked 30 October 2026.