At a glance
- 7H-01 is “Water flow problem”: the unit temporarily stops and the error resets automatically, per the Daikin Altherma 3 R F installer reference guide 4P596821-1A.
- 7H-04 (during domestic hot water), 7H-05 (during heating or sampling) and 7H-06 (during cooling or defrost) all need a manual reset.
- Daikin’s yearly maintenance checklist says “Keep water pressure above 1 bar. If it is lower, add water”; the maximum water pressure is 4 bar.
- Minimum required flow rate for the Altherma 3 R F ERLA03 is 12 l/min; below that the indoor unit stops and displays 7H.
- The indoor unit’s expansion vessel is 10 litres with a factory pre-pressure of 1 bar, and only a licensed installer may adjust it.
- HJ-10 is a separate water pressure sensor abnormality, which is an engineer job.
What does 7H-01 and 7H-05 mean on a Daikin Altherma heat pump?
A 7H code on a Daikin Altherma is a water flow fault, and the number after the dash tells you when it happened. Daikin’s installer reference guide for the Altherma 3 R F lists the indoor unit error codes as follows: 7H-01 “Water flow problem”; 7H-04 “Water flow problem during domestic hot water production”, manual reset, check the domestic hot water circuit; 7H-05 “Water flow problem during heating/sampling”, manual reset, check the space heating/cooling circuit; 7H-06 “Water flow problem during cooling/defrost”, manual reset, check the plate heat exchanger; and 7H-07 “Water flow problem, pump deblocking active”.
The same guide explains the mechanism. When the minimum water flow is lower than the figure in the table, the unit will temporarily stop operation and the user interface will display error 7H-01; after some time the error resets automatically and the unit resumes. For the ERLA03 and EHFZ03 combination the minimum required flow rate is 12 l/min, and the guide warns that when remotely controlled valves close heating loops, the minimum flow must still be maintained or a flow error 7H will be generated with no heating.
So a 7H code does not prove your pressure is low, but low pressure is a sensible first thing to rule out, because a circuit short of water cannot deliver flow. Daikin’s troubleshooting section lists “the water pressure at the pump inlet is too low” as a cause of pump trouble, with the corrective actions: check that the water pressure is above 1 bar, that the water pressure sensor is not broken, that the expansion vessel is not broken, that the valve towards the expansion vessel is open, and that the vessel pre-pressure is correct. The rest of the Altherma code list is in our Daikin Altherma error codes guide, and the brand-neutral checks are in our Guide to Heat Pump Not Working.
What pressure should a Daikin Altherma heat pump be?
A Daikin Altherma water circuit should stay above 1 bar and never exceed 4 bar, according to the Altherma 3 R F installer reference guide. The yearly maintenance checklist for the indoor unit puts it in one line: “Keep water pressure above 1 bar. If it is lower, add water.” The piping section gives the ceiling: “The maximum water pressure is 4 bar. Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.” Daikin does not publish one universal figure for every Altherma, so your own unit’s documents are what count, and you should check the installation manual for your model if it is not an Altherma 3 R F.
The Altherma 3 indoor unit has its own water pressure sensor, B1PW on the wiring diagram, which is why the Altherma family can raise HJ-10, “Water pressure sensor abnormality”, as a separate code. Many installations also have a mechanical gauge on the filling kit fitted by the installer, because Daikin says “To fill the water circuit, use a field supply filling kit”, so the gauge and the filling point sit wherever the installer placed that kit, typically on the return pipework near the indoor unit. The user interface shows the error code and, the guide says, “will display how to reset an error code”. On some Altherma 3 models the home screen also shows a water pressure reading; check the installation manual for your model to see whether yours does.
Why does a Daikin Altherma keep losing pressure?
Sealed heating systems lose a little pressure over time, but a steady or sudden drop always has a reason. The usual ones:
- A slow leak at a radiator valve, pipe joint, underfloor manifold, pump seal or the heat pump’s own connections.
- A weak expansion vessel. The indoor unit’s vessel is 10 litres with a factory pre-pressure of 1 bar. If the air side has lost its charge, pressure swings between cold and hot and the pressure relief valve may lift; Daikin lists a broken expansion vessel as the first cause of the relief valve opening.
- Air in the system. Air makes the gauge read oddly, causes gurgling and can starve the pump of water, which then shows up as a flow fault. Daikin’s remedy for pump cavitation noise is a manual or automatic air purge on both zones.
- A stuck or failing automatic air vent that weeps water or lets air in.
- Pressure relief valve (PRV) discharge. If it has opened, water goes down the drain pipe and pressure falls. Daikin’s own symptom list includes “the water pressure relief valve leaks”, with dirt on the seat as the usual cause.
- Recent bleeding or radiator work. Bleeding radiators removes air and lowers pressure, so it needs topping back up.
- A blocked strainer or magnetic filter. This does not lower pressure, but it gives the same 7H flow fault. Cleaning the water filters and the magnetic filter is on Daikin’s yearly checklist.
- A faulty sensor or flow sensor. The pressure reads fine on the gauge but the unit disagrees.
It is worth knowing that a closed stop valve or a shut zone can produce the same 7H code with normal pressure, which is why a proper diagnosis beats guessing. A defrost cycle is the other moment the fault surfaces: 7H-06 is raised specifically during cooling or defrost, when the unit pulls heat from the water circuit to clear the outdoor coil, and a frozen plate heat exchanger is a separate family of codes covered in our guide to the Daikin 89-01, 89-02 and 89-03 frozen heat exchanger errors.
How do I top up the pressure on a Daikin Altherma heat pump?
Daikin’s “add water” instruction is written for the installer, and filling uses a field-supplied kit, so whether you can do it yourself depends on whether your installer fitted an accessible filling loop and showed you how. If so, and you are confident, follow these steps.
- Read the pressure gauge on the indoor unit or hydraulic pipework when the system is cold. Note the figure and the date, so you can see if it is falling.
- Look for visible drips, damp patches, stained carpets or wet floors near the unit, the cylinder, radiators and the pressure relief discharge pipe.
- Check that radiators and any zone valves are open, and that nobody has shut a stop valve near the heat pump.
- Open the filling loop valve slowly, watch the gauge, stop at the figure your installer recorded (above 1 bar and well short of 4 bar), and close it fully afterwards.
- Write down the exact code, the time and what the system was doing. An engineer will want all three.
- Reset once from the user interface, following the instructions it shows. 7H-01 clears itself; 7H-04, 7H-05 and 7H-06 need the manual reset. If the code returns, leave it.
Our guide to a Heat Pump Losing Pressure explained explains what repeated drops usually mean.
What not to do:
- Do not touch refrigerant circuits or pipework.
- Never remove panels or covers from the outdoor or indoor unit.
- Do not keep adding water until the gauge looks high. Over-pressurising can lift the relief valve and damage components.
- Do not ignore repeated top-ups. A system that needs filling every week or two has a leak or a fault.
- Do not keep resetting a 7H code. The unit stopped for a reason.
- Do not try to adjust the expansion vessel pre-pressure. Daikin says only a licensed installer may do it, using dry nitrogen.
Which Daikin Altherma codes appear with low pressure?
| Code | Meaning | First step |
|---|---|---|
| 7H-01 | Water flow problem (automatic reset) | Check gauge, stop valves and radiators open, then call an engineer if it returns |
| 7H-04 | Water flow problem during domestic hot water production (manual reset) | Check the cylinder circuit valves and gauge, reset once |
| 7H-05 | Water flow problem during heating or sampling (manual reset) | Check radiators and zone valves open, check pressure |
| 7H-06 | Water flow problem during cooling or defrost (manual reset) | Check pressure and valves, then book an engineer to inspect the plate heat exchanger |
| 7H-07 | Water flow problem, pump deblocking active | Leave the unit to run its deblocking; engineer if it repeats |
| HJ-10 | Water pressure sensor abnormality | Engineer only: sensor and wiring check |
How can you stop it happening again?
- Have the system looked at every year. Daikin’s own yearly checklist covers water pressure, water filters, the magnetic filter, the relief valve and its hose. Our Heat Pump Annual Service Checklist explained shows the same items, and Guide to Why Heat Pump Servicing Is So Important explains the cost of skipping it.
- Check the gauge monthly in winter and write the figure down. A slow trend is far easier to act on than a sudden stop.
- Deal with drips early. Our guide to a Heat Pump Leaking Water explained explains where leaks usually start.
- Keep the system clean. Debris blocks strainers and filters, and a dirty circuit may need a guide to Heat Pump Powerflush.
- After bleeding a radiator, check the gauge straight away.
- Do not leave zone valves or stop valves partly closed after maintenance; the guide to Heat Pump Commissioning is a useful record of how they were set.
When to call an engineer
- The 7H code comes back after one reset.
- You are topping up more than occasionally, or the pressure drops again within days.
- Water is coming from the pressure relief valve discharge pipe.
- You can see or hear a leak, or the floor, ceiling or cylinder cupboard is damp.
- The heating or hot water has stopped and the house is getting cold.
- The gauge reads zero, or the pressure swings sharply between cold and hot.
- HJ-10 or any sensor code appears alongside the flow fault.
Book early. A small leak found in October is a cheap fix. The same leak found in January, when the heating is running flat out and guide to Do Heat Pumps Work in Cold Weather is testing the system, tends to arrive with a cold house and a queue for appointments. If the system is still under warranty with Daikin or the installer, contact them first so you do not put cover at risk. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Our engineers find the leak, check the expansion vessel and air vent, test the flow and clear the code. Book a our repair service, see our Daikin heat pump servicing and repairs page, compare heat pump cover plans or check the find your nearest engineer. For background, read guide to Is Heat Pump Cover Worth It and our Daikin Altherma Heat Pump Review explained.
Frequently asked questions
Can I clear a 7H code by switching the Daikin off and on?
You can try one reset from the user interface, which shows you how, but a 7H code that returns means the fault is still there. Repeated restarts hide the pattern an engineer needs to see, so note the time and code each time and let it be after the second appearance.
Is the 7H-01 reset automatic?
Daikin’s installer reference guide says that when flow falls below the minimum the unit stops, displays 7H-01, and after some time the error resets automatically. 7H-04, 7H-05 and 7H-06 are listed as manual reset. Your model or software version may behave differently, so check the installation manual for your unit.
Will a blocked filter cause the same code?
Yes. A clogged water filter or magnetic filter restricts flow without changing the gauge reading, so pressure alone will not tell you. Daikin puts cleaning the water filters and the magnetic filter or dirt separator on the yearly maintenance list for exactly this reason.
Does the heat pump need a bypass?
Daikin’s guide says that where remotely controlled valves close heating loops, the minimum flow rate must be maintained even if all valves are closed, or a 7H flow error will be generated. Whether your system needs a bypass or buffer to achieve that depends on the design, which is a job for the installer or a service engineer to confirm.
Could a 7H code appear in a heatwave or in summer?
It can. Cooling and defrost have their own code, 7H-06, and any time of year a closed valve or air in the circuit can starve the pump. Season does not cause the fault, but how hard the system is working can expose it.
Sources and further reading: Daikin, Installer reference guide, Daikin Altherma 3 R F, ERLA03DAV3 + EHFZ03S18DJ3V, 4P596821-1A (2020.05): sections 7.2 expansion vessel, 7.6.5 filling the water circuit, 12.4 yearly maintenance checklist, 13.3 troubleshooting symptoms and 13.4 error codes (Daikin document library PDF). Checked 30 October 2026.