At a glance
- Grant’s Aerona3 R32 installation and servicing manual (DOC 0136 Rev 2.4, February 2024) lists no fault code for low water pressure.
- System water pressure is specified as 0.1 to 0.3 MPa (1 to 3 bar), with a safety valve set at 3 bar and a 0 to 4 bar gauge fitted next to the filling loop.
- Filling instruction: fill until the gauge reads between 0.5 and 1.0 bar cold, which should be 0.2 to 0.3 bar above the expansion vessel charge; typical fill pressures are about 0.5 bar for a bungalow and 1.0 bar for a two-storey house.
- Grant’s warning: “Only ever fill or add water to the system when it is cold and the heat pump is off. Do not overfill.”
- A fault shows as a flashing red LED on the remote controller’s on/off button plus a warning icon and code on the LCD; P1 is a pump error and FU means the high pressure switch has operated.
- Minimum water flow is 5 l/min (HPID6R32), 10 l/min (HPID10R32) and 15 l/min (HPID13R32 and HPID17R32).
Why is my Grant Aerona heat pump showing low pressure?
A Grant Aerona3 shows low pressure on the system gauge, not as an error code, because Grant’s installation and servicing manual lists no code described as low water pressure. The fault table in Section 11 covers sensor faults, pump and pressure switch faults and communication faults, and we could not find a code in it that is tied to the heating water pressure, so we are not going to invent one. If the heat pump has stopped with a code showing, it will be one of the water-circuit codes covered further down rather than a pressure code.
What the manual does give is useful pressure information. The specification table lists the system water pressure as 0.1 to 0.3 MPa (1 to 3 bar). The sealed system section asks for a 0 to 4 bar pressure gauge “located in an accessible place next to the filling loop”, a safety valve set to operate at 3 bar fitted in the flow pipework near the heat pump, and an automatic air vent at the highest point. The filling procedure says to fill a cold system until the gauge reads between 0.5 and 1.0 bar.
Some websites quote a different target, such as 1.5 bar. Where sources disagree we take the cautious reading and follow Grant’s manual, plus whatever fill pressure your installer recorded at commissioning. Our full Grant Aerona heat pump error codes guide covers every other code, and the general Heat Pump Not Working questions answered covers the checks that are the same whatever the brand.
What pressure should a Grant Aerona heat pump be?
A Grant Aerona3 system should read between 0.5 and 1.0 bar when cold, according to the filling procedure in Grant’s manual, within an overall working range of 1 to 3 bar. The two figures sit together because the cold fill depends on the building: Grant says the system fill pressure (cold) should be 0.2 to 0.3 bar greater than the expansion vessel charge pressure, “giving typical system fill pressures of approx 0.5 bar for a bungalow and 1.0 bar for a two storey house”. The vessel charge itself should be about 0.2 bar lower than the maximum static head at the level of the vessel, with 1 bar equal to 10.2 metres of water.
The Aerona3 is a monobloc, so the gauge, filling loop and safety valve are not inside the outdoor unit. They sit indoors on the system pipework, usually near the cylinder or the plant area, and Grant requires the gauge to be next to the filling loop. Pressure rises as the water warms, and the 3 bar safety valve is the ceiling, so a hot reading creeping towards 3 bar means the vessel or the fill pressure needs looking at. Grant also depends on a minimum water flow, listed as 5 l/min for the HPID6R32, 10 l/min for the HPID10R32 and 15 l/min for the HPID13R32 and HPID17R32. When pressure is low, air gets drawn in and the pump struggles, so flow-related faults can follow.
Why does a Grant Aerona heat pump keep losing pressure?
A sealed Aerona3 system should hold its pressure for months. If it does not, look at these likely causes:
- A leak at radiators, valves, joints, underfloor manifolds or the connections near the heat pump.
- An expansion vessel with the wrong or lost air charge. Grant specifies the charge relative to the static head at the vessel, so a vessel that has been recharged incorrectly can cause pressure problems.
- Air in the system after filling or maintenance, which can mimic a drop and affect flow.
- The safety valve discharging at 3 bar after the pressure has risen too high, which then drops the gauge once it reseats.
- Recent bleeding or radiator work that removed water from the circuit.
- A leaking automatic air vent.
Nothing in the heat pump electronics warns you about a slow loss, so a regular look at the gauge is the most useful habit. Grant’s own check of the safety valve is a related cause people forget: the manual describes turning the valve head anticlockwise until it clicks to confirm it lifts, then topping up the system pressure “as necessary”, so a safety valve test will itself drop the gauge a little. In freezing weather a defrost cycle draws heat from the water circuit to clear the outdoor coil, and a circuit short of water or flow is what triggers the fan and freeze codes described in our guide to Grant Aerona C1, C3 and A7 errors on a frozen outdoor unit.
How do I top up the pressure on a Grant Aerona heat pump?
Grant writes the filling procedure for the installer and adds a warning that applies to anyone: only ever fill or add water when the system is cold and the heat pump is off, and do not overfill. If your installer left the filling loop connected and showed you how, and you are competent, follow this order, and stop and call an engineer at any step you are unsure of.
- Switch the heat pump off and let the system cool. Grant’s warning is specific on this point.
- Read the gauge. Compare it with the cold fill range in the Grant manual, 0.5 to 1.0 bar, and with any figure your installer recorded.
- Check for a fault code on the remote controller and see whether the red on/off LED is flashing. Write down the code before you do anything else.
- Look for drips and damp patches under radiators, around the pipework and near the safety valve discharge pipe, and make sure radiator and zone valves are open.
- Open the double check valve on the filling loop gradually until you hear water flow, watch the gauge, and close the valve when it reads between 0.5 and 1.0 bar, or at your installer’s figure.
- Close the fill point and both valves, then disconnect the loop. Grant says the loop must be isolated and disconnected after filling. Check the gauge again after a day.
Grant’s procedure is the one to follow, but for the general background on repressurising and what a normal rate of loss looks like, our Heat Pump Losing Pressure guide has it.
What not to do:
- The refrigerant circuit is out of bounds. It needs a qualified engineer, and nothing on the water side is fixed by touching it.
- Leave the outdoor unit casing alone. The internal automatic air vent in Grant’s procedure is for the installer, and the fan, compressor and live terminals share that space.
- Do not creep the gauge towards 3 bar for safety’s sake. That is the safety valve setting, and lifting it just empties water you have paid to heat.
- Needing the filling loop more than once or twice a year means water is leaving the system, and it needs finding.
Which Grant Aerona codes appear with low pressure?
Grant lists no low pressure code, so this table shows the water-circuit codes from the fault finding section of the Aerona3 manual. In the event of a fault, Grant says, the red LED on the on/off switch of the remote controller flashes and a warning icon and error code appear on the LCD screen and on the terminal PCB display. Pressing the minus and plus buttons together for three seconds resets the display.
| Code | Meaning | First step |
|---|---|---|
| P1 | Pump error. Grant’s checks are the pump voltage, the pump itself and the main PCB, and a clogged pump or water circuit is listed. | Check there is water in the system and the gauge is in range, then book an engineer to test the pump. |
| FU | High pressure switch is operating (refrigerant side). Listed causes are outside air recirculation and a clogged water circuit; a large flow and return temperature difference means the flow rate is too low. Manual reset. | Make sure nothing blocks the outdoor unit’s air inlet and outlet, then book an engineer to check flow, strainer and the water circuit. |
FU refers to the refrigerant-side switch, so low water pressure is only an indirect link, but Grant’s advice to check the outgoing and return water temperature difference on the monitor display is a useful pointer to poor flow.
How can you stop it happening again?
- Book an annual service. The Heat Pump Annual Service Checklist includes gauge reading, expansion vessel check, strainer clean and a leak inspection, and More on why heat pump servicing is so important explains what the visit protects.
- Do not ignore slow drips. Read our guide on a Heat Pump Leaking Water to see what to look for.
- If the circuit is dirty or flow is poor, a Heat Pump Powerflush explained can help clear the system.
- If the unit stops running properly, our guide on a Heat Pump Running But Not Heating guide covers wider troubleshooting.
- Record the cold gauge reading once a month, and before winter read our guide to More on do heat pumps work in cold weather.
When to call an engineer
- The gauge keeps falling after you top it up.
- A fault code such as P1 or FU shows on the controller and returns after being reset.
- The safety valve has discharged or is dripping.
- Heating output is poor, the flow and return temperatures are far apart, or the unit is noisy.
- You can see water leaking from the system.
Do not leave it for spring. Each top-up admits fresh oxygen, which over months corrodes radiators and clogs the strainer, and finding a small leak in autumn costs far less than a January no-heating call-out. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We repair Grant Aerona systems and can trace the leak, test the expansion vessel charge against the manual and set the fill pressure correctly. Book a fault diagnosis and repair, see our Grant heat pump servicing and repairs page, look at breakdown cover and annual servicing if you would rather spread the cost of looking after the system, or check the where we work. Read Is Heat Pump Cover Worth It questions answered before you decide, and our Grant Aerona Heat Pump Review for how the unit stacks up.
Frequently asked questions
What does the red flashing light on my Grant Aerona mean?
According to Grant’s manual, when a fault is detected the red LED on the on/off switch of the remote controller flashes and a warning icon and error code are shown on the LCD screen. Note the code before resetting anything and contact your installer or an engineer if it returns.
Can I repressurise my Aerona3 myself?
If you are competent and the filling loop is accessible, you can top up through it to the correct figure with the system cold and the heat pump off, as Grant’s warning requires. If the pressure keeps dropping, that is a sign of a leak and not something to keep fixing yourself.
Why does the gauge on my Grant system read higher when the heating runs?
Warm water takes up more space, so the pressure rises a little, and the expansion vessel absorbs the difference. The safety valve is set at 3 bar, and anything approaching that when hot needs checking, usually the vessel charge or an over-filled system.
What is the minimum flow rate for an Aerona3?
Grant lists 5 l/min for the HPID6R32, 10 l/min for the HPID10R32 and 15 l/min for the HPID13R32 and HPID17R32. Poor pressure, air or a blocked strainer can pull the flow below that, which is when pump and temperature-difference faults appear.
Where is the error code table for my Aerona?
It is in the Fault Finding section of the Grant installation and servicing manual for your model, which also explains the error history display on the terminal PCB and how each code resets. Keep the manual with the system paperwork.
Sources and further reading: Grant Engineering (UK) Limited, Grant Aerona3 Air to Water High Efficiency Heat Pump Range, Installation and Servicing Instructions, UK DOC 0136 Rev 2.4, February 2024: technical specification, Section 4.1 sealed system requirements, 4.2 filling the sealed system, 4.3 pressure relief valve operation, 8 remote controller and 11 fault finding (Grant UK PDF). Checked 30 October 2026.