At a glance
- The Cosy user manual (version 26-1) gives a recommended level of between 1 and 1.5 bar cold and says pressure “will need to be topped back up to 1.5 bar” after bleeding or long periods without heating.
- Octopus’s own top-up page says to switch the heat pump off, let it cool, and top up if the gauge is below 1 bar, closing the valve when it reads about 1 bar.
- The filling loop is “usually a small silver hose with one or two valves”; Octopus describes a flexible hose with two black plastic stopcock valves in the cylinder cupboard.
- The gauge is on the cylinder or shown on the heat pump screen, according to Octopus.
- A Hub flashing red means a heat pump fault; solid red means no primary Pod found; solid yellow means lost WiFi. None of these is a pressure light.
- Yes, an owner may top up: the manual lists it under User Maintenance alongside bleeding radiators.
Why is my Octopus Cosy heat pump showing low pressure?
An Octopus Cosy shows low pressure on the gauge, not on the Hub or in the app, because the Cosy user manual lists no low pressure fault code, pressure light or app alert. Your Cosy heating circuit is sealed and full of water. Low pressure means there is less water in it than there should be, so heat does not travel round the house as it should. The manual puts it this way: “If the pressure drops too low, Cosy may struggle to move heat efficiently, which can affect comfort and performance,” and its troubleshooting advice for a room that is not warming up is to “check your TRVs are open and your system pressure is correct”.
What the manual does describe is the Hub. A flashing red light on the Cosy Hub means a heat pump fault, and the manual says to call the aftercare helpline or email. Solid red means no primary Pod has been found, and solid yellow means the Hub has lost its WiFi connection. A Cosy Pod flashing red every 30 seconds is a low battery. We would not read a flashing red Hub as “low pressure” specifically, only as a fault that needs finding, and pressure is one of several possible causes. Our Octopus Cosy error codes and fault lights guide lists every light the manual describes, and the What to know about Heat Pump Not Working walks through the checks that apply to any make.
What pressure should an Octopus Cosy heat pump be?
An Octopus Cosy heating system should read between 1 and 1.5 bar when cold, according to the Cosy user manual. The components section describes the mains filling loop as the device “used to top up water pressure in your heating system if it drops”, notes that this “will happen if you bleed any radiators or you haven’t used your heating for a long time”, and says “the pressure will need to be topped back up to 1.5 bar”. The user maintenance section repeats the range: slowly open the valve or valves, watch the pressure gauge rise, and “when it reaches the recommended level (between 1 to 1.5 bar cold), close the valve(s) fully”.
Octopus’s separate web guide to topping up heat pump pressure uses slightly lower numbers: check the gauge “on the cylinder or heat pump screen”, and if it is below 1 bar it is time to top up, turning the valve off “when the gauge reads about 1 bar”. Both documents are Octopus’s own, so treat 1 bar as the floor and 1.5 bar as the comfortable cold target, and use whichever figure your installer wrote on the commissioning sheet if it differs. The gauge itself is on the hot water cylinder in most Cosy installations, next to the filling loop in the airing cupboard, with the expansion vessel (“about the size of a basketball”) nearby.
Why does an Octopus Cosy heat pump keep losing pressure?
- Bleeding radiators without topping up afterwards. The manual names this as the most likely reason, and tells you to check the pressure after bleeding.
- Long periods without heating. The manual says pressure is most likely to drop “usually after the warmer months”.
- A slow leak at a radiator valve, pipe joint, underfloor manifold or connection near the cylinder.
- A tired expansion vessel that has lost its air charge, making pressure rise and fall sharply.
- An automatic air vent that is weeping or stuck.
- Pressure relief valve discharge, where water leaves through the drain pipe.
- A faulty gauge, which can show a pressure that does not match reality.
- Radiator or TRV changes that alter how water flows.
Patterns matter. A slow, steady fall over weeks usually points to a tiny leak or a weeping air vent. A gauge that jumps up when the heating runs and drops back when it cools often points to the expansion vessel. A sudden drop after plumbing or radiator work is usually air or a disturbed joint. Whatever you find, write it down with dates, because it tells an engineer where to start looking. Winter adds one more load: during a defrost cycle the Cosy briefly takes heat from the house circuit to clear ice from the evaporator, and a circuit short of water or flow is what tips a marginal system into the fault covered in our guide to a frozen or iced-up Octopus Cosy.
How do I top up the pressure on an Octopus Cosy heat pump?
Octopus treats topping up as an owner task and publishes the steps, with the caution to “only adjust valves you are confident handling”. Combining the manual and the web guide, the procedure is:
- Switch the heat pump off and let the system cool for a few minutes, as Octopus’s guide requires. Read the pressure gauge on the cylinder and note the figure and date.
- Look for leaks: drips, damp patches, stained ceilings, wet floors, and water near the cylinder and relief valve pipe.
- Check radiators and TRVs. The manual points out that a primary Pod in a room with a TRV can affect heating, so make sure it is not being starved.
- Find the mains filling loop in the cylinder cupboard, a small silver hose with one or two black valves. If the hose is not already attached, fit it as Octopus describes.
- Open the valve or valves slowly and watch the gauge rise. Stop between 1 and 1.5 bar cold, the manual’s recommended level, and close the valve or valves fully.
- Switch the heat pump back on and check the pressure over the next few hours and days to make sure it stays steady. Keep a cloth handy for drips.
Our guide to a Heat Pump Losing Pressure explains why repeated drops matter.
What not to do:
- Do not do any refrigerant work. The Cosy uses R290 propane, and that circuit is for engineers only.
- Never remove panels from the heat pump or the cylinder.
- Do not keep over-pressurising. The manual’s target is 1.5 bar, not as high as the gauge will go.
- Do not ignore repeated top-ups.
- Do not leave filling loop valves open once you have finished.
Remember that the manual treats a top-up as an occasional task, such as after the warmer months or after bleeding. If you find yourself reaching for the filling loop every few weeks, that is the moment to stop and have the system checked, not to keep going.
Which Octopus Cosy symptoms appear with low pressure?
The manual uses lights, not codes. This table covers the lights it lists plus pressure symptoms.
| What you see | Meaning per the manual | First step |
|---|---|---|
| Hub flashing red | Heat pump fault | Call Octopus aftercare or book an engineer; check the gauge |
| Hub solid red | No primary Pod found | Check Pod battery and move it within 5 m of the Hub (not a pressure fault) |
| Hub solid yellow | Lost WiFi connection | Check the router; the Hub reconnects itself (not a pressure fault) |
| Pod flashing red every 30 seconds | Low battery | Replace with two AAA alkaline batteries (not a pressure fault) |
| Gauge below 1 bar cold | Octopus says it is time to top up | Top up carefully if competent, then monitor |
| Rooms not heating evenly | Manual links this to TRVs, Pod placement and system pressure | Check TRVs are open and pressure is correct |
How can you stop it happening again?
- Arrange a yearly check. Our Heat Pump Annual Service Checklist covers pressure, the expansion vessel, the air vent and a leak check, and Why heat pump servicing is so important in detail explains the cost of leaving it.
- Check the gauge monthly and every time you bleed a radiator. The manual says pressure often drops after the warmer months, so check it before the heating season starts.
- Fix drips quickly. See our Heat Pump Leaking Water guide.
- If heating is poor despite normal pressure, our What to know about Heat Pump Running But Not Heating guide covers other causes.
- Keep TRVs open as the manual advises, particularly in the primary Pod’s room, and read our guide to Do heat pumps work in cold weather in detail before winter.
When to call an engineer
- The gauge falls again within days of topping up.
- The Hub is flashing red.
- Water is dripping from the relief valve pipe.
- You can see or smell dampness near pipes or the cylinder.
- Heating or hot water has stopped.
- You are not confident about the filling loop.
- The system is under warranty. Contact Octopus first so cover is not affected.
Book early. A small leak found early is much cheaper to repair than a damaged floor or ceiling, and winter appointments go quickly. If your Cosy was installed in the last year, mention the pressure history to your installer too, because they will have the commissioning figures that show whether your current reading is normal for your house. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Our engineers find the leak, check the expansion vessel and air vent and put the system back to the manual’s pressure. Book a book a repair, look at a heat pump service plan so pressure problems are found early, or check the local heat pump engineers. Read what to know about Is Heat Pump Cover Worth It if you are weighing it up.
Frequently asked questions
Does the Octopus app warn me about low pressure?
The Cosy manual says you can check for fault indications on the Hub and monitor Pod batteries in the app. It does not describe a pressure alert, and the LED table has no pressure entry. Octopus’s web guide says pressure can drop naturally over time and recommends checking a few times a year, so watch the gauge yourself.
Why is my Cosy pressure lower after summer?
The manual says pressure is most likely to drop if you have not used your heating for a while, usually after the warmer months. Even so, a big or repeated drop is a sign of a leak, so do not simply top up every autumn without looking for the cause.
Is a flashing red Hub light always a pressure fault?
No. The manual lists it as a heat pump fault, without naming a cause, and tells you to call the aftercare line or email. Check the gauge so you can report it, then call for help rather than resetting the Hub.
Can I top up straight after bleeding a radiator?
Yes, and the manual says to check the pressure after bleeding and top up if needed. Turn the heating off and let it cool first, as the bleeding tip itself advises, then read the gauge with the system cold so the figure is accurate.
Should I top up to 1 bar or 1.5 bar?
The Cosy user manual says 1.5 bar, within a recommended cold range of 1 to 1.5 bar, while Octopus’s web guide says to stop at about 1 bar. Either is inside Octopus’s own range. Use the figure your installer recorded if you have it, and never go above 1.5 bar cold.
Sources and further reading: Octopus Energy, Cosy Series User Manual version 26-1, sections on components (expansion vessel, mains filling loop), User Maintenance (bleeding radiators, topping-up system pressure) and the LED table (PDF); Octopus Energy, Top up your heat pump pressure. Checked 30 October 2026.