At a glance
- The Compress 3400iAWS E operation manual (6721852787, 2023/01) has no numeric fault code for low water pressure; faults are reported as a fault code, sub-code and user interface ID to the installer.
- Owner instruction: check the gauge one to two times a year, and “if the pressure is less than 0.5 bar, increase the pressure slowly to max. 2 bar by filling with water via the fill valve”.
- The pressure gauge is on the AWS E indoor unit, shown in the manual with the drip tray removed.
- Safety valves: check once or twice a year, never close them, and contact the installer if water comes out at pressures below 2 bar.
- On the AWE indoor unit used with the Compress 7001i AW and 7400i AW, a pressure switch trips below 0.5 bar and resets itself above 0.5 bar; it blocks the electric booster heater, not the heat pump.
- The 7400i/7001i installation manual tops up through the VW2 fill valve when the gauge reads less than 2 bar at commissioning.
Why is my Worcester Bosch heat pump showing low pressure?
A Worcester Bosch heat pump shows low pressure on the gauge on the indoor unit, because the user manuals do not assign a numeric fault code to low water pressure. Worcester Bosch sells several heat pump families, and their documents do not all say the same thing. The Compress 3400iAWS E operation manual tells you, if a fault persists, to confirm it by pressing the selector, display active faults with the info key, and “call an authorised contractor or customer service and give them the fault code and sub-code, as well as the ID no. of the user interface”. It does not list the codes. We have therefore written this as a general low pressure article and not tied it to a single code.
The AWE indoor unit, which pairs with the Compress 7001i AW and 7400i AW, adds a hardware clue. Its installation manual says the indoor unit “has a pressure switch which triggers once the pressure in the heating system falls below 0.5 bar”, that alarms or information at the control unit then indicate the operating pressure is too low, and that the switch resets itself once pressure exceeds 0.5 bar. Triggering it only blocks the electric booster heater; the heating pump and the heat pump can continue to run where there is a risk of frost. So a low pressure message on a 7001i or 7400i is the pressure switch talking, and the gauge will confirm it.
Those are two different products with two different behaviours, so identify your indoor unit from its data label before reading on. Our Worcester Bosch heat pump error codes guide lists the codes we could verify, and the Heat Pump Not Working explained covers the checks that apply to any make.
What pressure should a Worcester Bosch heat pump be?
A Compress 3400iAWS E should be topped up when the gauge drops below 0.5 bar and filled slowly to no more than 2 bar, according to its operation manual. The maintenance section reads: “Check the pressure at the pressure gauge. If the pressure is less than 0.5 bar, increase the pressure slowly to max. 2 bar by filling with water via the fill valve. If you have any questions about the procedure, consult the installer of the system.” The same manual tells you to check the operating pressure after a long absence, and to check it one to two times per year.
The gauge on the 3400i is on the indoor unit: the manual’s figure of the AWS E indoor unit with the drip tray removed labels item 1 as the pressure gauge. On the AWE indoor unit for the 7001i and 7400i the installation manual refers to the pressure gauge GC1 and the fill valve VW2 inside the unit, and its commissioning sequence says “if the pressure is less than 2 bar top up via the VW2 fill valve”. Those figures are different because the products are different, so use the one in the manual for your own heat pump and check the installation manual for your model if yours is a Compress 2000 or another family, for which we could not confirm a figure.
Why does a Worcester Bosch heat pump keep losing pressure?
- Leaks at radiator valves, joints, underfloor manifolds, the pump or the cylinder connections. The AWE manual’s own instruction when the pressure switch trips is to “eliminate any leaks in the system”.
- Expansion vessel faults. If the vessel’s air charge is lost the pressure behaves badly as the system heats and cools, and the AWE manual asks that the vessel and relief valve are configured for the operating pressure.
- Air in the system, which can come back after a drop in pressure.
- An automatic air vent that is weeping or has failed.
- Safety or relief valve discharge that has emptied some water out of the system. The 3400i manual notes that water is expelled from the safety valve during heat-up but should only happen if the maximum pressure is exceeded.
- Recent bleeding of radiators or other plumbing work without a top-up afterwards.
- A blocked particle filter, which causes poor flow messages that look like a pressure fault. The AWE manual says magnetic dirt on the magnetite bar that “frequently causes an alarm related to the poor flow (e.g., low or poor flow, high flow supply or HP alarm)” is a reason to fit an approved magnetite filter.
- A failed pressure switch or sensor, which reports a problem the system does not have.
Running the heating pump for a long time at low pressure can damage it, which is why the AWE manual carries a “material damage from running dry” notice. In winter the heat pump’s defrost cycle borrows heat from the house circuit, and poor flow at that moment is what produces the freeze protection codes covered in our guide to the Worcester Bosch Pb and Hb freeze protection errors.
How do I top up the pressure on a Worcester Bosch heat pump?
Worcester Bosch writes the top-up as an owner task in the 3400i operation manual, with the instruction to consult the installer if you have any questions about the procedure. If you are confident, work through these steps.
- Read the pressure gauge on the indoor unit with the system cold. Note the number and the date.
- Look for drips, water stains and damp patches around the indoor unit, cylinder, pipes and radiators. Check where the safety valve drainage hose discharges.
- Check that radiators, TRVs and zone valves are open. A shut circuit can trigger flow messages.
- Open the fill valve slowly and watch the gauge. On the 3400i stop no higher than 2 bar; on other models stay within your manual’s limit.
- Close the fill valve fully and, if the loop is the removable type, disconnect it.
- Press the selector to confirm any fault on the display and write down the code and sub-code exactly, then check the gauge again in a day or two. If it has dropped, you have a leak or a fault.
Our guide to a Heat Pump Losing Pressure explained explains why repeated drops matter.
What not to do:
- Do not do any refrigerant work.
- Never remove panels from the outdoor or indoor unit beyond the drip tray the manual shows you.
- Do not over-pressurise. Going above the manual’s limit risks the safety valve lifting.
- Do not close or block the safety valve or its drain. The manual says never close the safety valve.
- Do not clean the particle filter or check the magnetite indicator if you wear a pacemaker; the manual warns of a strong magnet.
- Do not keep topping up without finding out where the water is going.
Which Worcester Bosch symptoms appear with low pressure?
Because the user manuals give no pressure-specific codes, this table lists symptoms and messages the manuals mention, not codes.
| Symptom or message | Meaning | First step |
|---|---|---|
| Gauge below 0.5 bar (3400iAWS E) | Manual says to fill slowly to a maximum of 2 bar via the fill valve | Check for leaks, top up only if competent, then monitor |
| Controller alarm or information about low operating pressure (AWE unit, 7001i/7400i) | Pressure switch has tripped below 0.5 bar; it resets above 0.5 bar and only blocks the booster heater | Check gauge, top up via the fill valve if competent, call an engineer if it recurs |
| Low or poor flow alarm, high flow supply or HP alarm | Dirt on the magnetite bar or a blocked particle filter | Engineer to clean the filter and advise on a magnetite filter |
| Water from the safety valve below 2 bar (3400iAWS E) | Valve or expansion vessel problem | Contact your installer |
| Fault code and sub-code on the display | Any fault; the manual does not list meanings | Confirm with the selector, note code, sub-code and user interface ID, call a contractor |
How can you stop it happening again?
- Follow Worcester Bosch’s own advice to check the gauge and safety valves once or twice a year, and look at it more often through winter. Our Heat Pump Annual Service Checklist explained shows what a service should include, and Why Heat Pump Servicing Is So Important explained explains the running-cost side.
- After a long absence, check the pressure. The 3400i manual says so specifically.
- Have the particle filter cleaned, and if it keeps clogging, ask about a magnetite filter. See our Heat Pump Powerflush questions answered guide for dirty systems.
- Act on drips straight away. Our Heat Pump Leaking Water explained guide explains the usual causes.
- If your heat pump struggles in cold weather, see our heat pump winter tips and our guide to Do Heat Pumps Work in Cold Weather explained.
When to call an engineer
- Pressure falls again after a top-up.
- Water is coming from the safety valve, especially when the gauge is below 2 bar on the 3400i.
- A fault code or controller message returns after being cleared.
- You can see leaks or damp on pipes, floors or around the cylinder.
- Heating or hot water stops working.
- You are not confident using the fill valve.
- Your heat pump is still under installer or Worcester Bosch warranty. Contact them first so you do not affect cover.
Book early. A leak left through winter gets worse and can damage floors and ceilings, and engineers are busiest when everyone’s system starts working harder. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Our engineers find the leak, check the expansion vessel and air vent, inspect the particle filter and reset the pressure to the manual’s figure. Book a a repair engineer visit, see our Worcester Bosch heat pump servicing and repairs page, compare service and cover plans, which keep an eye on pressure before it becomes a fault, or check the the towns and cities we cover. Read Is Heat Pump Cover Worth It explained and our Worcester Bosch Heat Pump Review guide for more background.
Frequently asked questions
Which Worcester Bosch heat pump do I have?
Look at the label on the indoor or outdoor unit, or your commissioning paperwork. The Compress 3400iAWS E has its own operation manual with the 0.5 to 2 bar figures, while the 7001i AW and 7400i AW use the AWE indoor unit with a pressure switch. Other families have different documents, so you need the right one.
Why does the pressure switch only block the booster heater?
The AWE installation manual says the pressure switch and the booster heater’s overheating protection are wired in series, so a low pressure trip stops the electric heater from running dry. The heating pump and heat pump are allowed to keep running where there is a frost risk, and the switch resets once pressure passes 0.5 bar.
Is water from the safety valve always a problem?
The valve should only release water when the pressure goes above its limit, and the 3400i manual notes a little is expelled during heat-up. If it releases water below 2 bar, Worcester Bosch says to contact the installer, and you should never close the valve off or block its drainage hose.
Can a heat pump run with low pressure?
Low pressure can cause flow problems, noise and shutdowns, and the AWE manual warns that running the heating pump for a long time at low pressure can damage it. Running with air in the system strains the pump, so do not leave a falling gauge unchecked.
Does Worcester Bosch use the same codes as its boilers?
No. Boiler fault codes should not be used for a heat pump. The heat pump manual asks you to take the fault code, sub-code and user interface ID from the display and give them to a contractor, so write all three down rather than looking the number up in a boiler list.
Sources and further reading: Worcester Bosch, Compress 3400iAWS E Operation Manual, 6721852787 (2023/01), sections 3.5 faults, 4.1.1 checking the operating pressure, 4.1.3 particle filter and 4.1.5 checking the safety valves (Worcester Bosch literature download); Bosch, AWE indoor unit for air to water heat pump Installation Manual, 6721835317 (2021/09), commissioning steps and section 6.4.1 pressure switch and overheating protection (Worcester Bosch literature download). Checked 30 October 2026.