At a glance
- E135 on a CTC heat pump means “Risk of freezing”: the water leaving the heat pump (HP out) was too cold for defrosting, below 15 °C during a defrost or more than 15 °C below HP in for over 20 seconds.
- CTC asks for a heating return of at least 25 °C during a defrost period, and lists low circuit temperature, low flow and faulty HP in or HP out sensors as the causes.
- E135 is a critical alarm: it can be confirmed three times with installer code 4005, and after a fourth alarm the EcoAir is blocked and shows repeat code E218 until an installer attends.
- During a CTC EcoAir defrost the fan stops, the four-way valve reverses, you hear a hiss as water drains and a vapour cloud lasting a few seconds is normal.
- Related CTC alarms are E211 (flow under 10 or 15 litres a minute during defrost) and E163 (defrost max time duration).
- Ice on the front of an EcoAir must not be broken loose; CTC says to remove it with lukewarm water, and never to speed up defrosting beyond what the manual allows.
What does E135 mean on a CTC heat pump?
E135 means the CTC EcoAir outdoor unit has detected a risk of its water side freezing during a defrost. In CTC’s EcoZenith i255 manual the alarm text reads “Risk of freezing”, and the trigger is either an HP out temperature below 15 °C during a defrost period, or a difference of more than 15 °C between the HP in and HP out sensors for more than 20 seconds.
HP in is the sensor on the water entering the heat pump from your heating circuit, and HP out is the sensor on the water leaving it. A defrost borrows heat from that water to melt the evaporator, the finned coil on the front of the EcoAir, so if the water arrives cold or moves too slowly the outlet temperature collapses and the alarm fires.
CTC groups E135 with its critical alarms. The display on the EcoZenith, EcoLogic or other controlling product shows the alarm, and the red and yellow LED flashes. If the heat pump has stopped altogether rather than just alarming, our guide to a heat pump not working covers the wider checks, and every other CTC code is listed in our CTC heat pump error codes guide.
Is ice on a CTC heat pump normal?
Yes, frost on the evaporator of a CTC EcoAir is normal in cold, damp weather, and the unit is designed to clear it on a schedule. CTC’s EcoAir 600M manual says the vapour cloud you see after a defrost “is perfectly normal and stops after a few seconds”, and warns that a defrost can release large amounts of water, up to 70 litres of condensate a day in some conditions.
What CTC treats as abnormal is heavy ice that is still there after a defrost, or poor heating combined with ice. The EcoAir troubleshooting pages tie that picture to defective defrosting automation, a lack of refrigerant from a leak, or extreme weather. CTC also warns that a sheltered site such as a car port or outhouse can recirculate cold exhaust air and “cause abnormal ice formation in the evaporator”, which is worth remembering if your EcoAir sits in an alcove.
For a general picture of what heavy icing looks like across brands, see our guide to a guide to Heat Pump Frozen Outside Unit.
How does the CTC defrost cycle work?
A CTC EcoAir defrosts by reversing its refrigerant circuit, so the hot gas that normally heats your water is sent to the evaporator instead. CTC’s EcoAir 600M and 700M manuals describe the sequence: when defrosting starts the fan stops, the four-way valve changes direction and the discharge goes to the evaporator; a hissing sound is heard as water drains from the coil; the fan restarts when defrosting has finished.
The heat for that process comes from your heating water, which is why CTC sets minimum water volumes for reliable defrosting: 80 litres for the EcoAir 610M and 614M and 120 litres for the 622M, held above 25 °C. The EcoAir 700M manual states a flow requirement at defrost of 10 litres a minute, and below that an alarm is generated. A condensate tray in the base carries an electric heating coil to keep the tray free of ice, and a heating cable is available for the drain to a frost-free outlet.
Below an outdoor temperature of +2 °C the charge pump runs constantly to remove any risk of freezing. Our guide to the guide to Heat Pump Defrost Cycle explains the physics in more detail.
Why has my CTC heat pump frozen or shown E135?
CTC’s own cause list for E135 is short: the circuit temperature or flow rate is too low, or the HP in and HP out sensors are not reading correctly. Its recommended actions are to ensure the heating return is at least 25 °C during a defrost, to check the circulation pump, dirt filter, pipe system and pipe size, and to supplement with a volume tank where the system is too small. The table below puts the CTC alarms you may see in a cold snap side by side.
| What you see | CTC code | Likely cause | Who acts |
|---|---|---|---|
| “Risk of freezing” on the display, heat pump stopped | E135 | HP out below 15 °C in defrost; low return temperature, low flow or a sensor fault | Owner checks pressure and filter, then engineer |
| Alarm during defrost on a unit with the Flow Sensor accessory | E211 | Flow below 10 l/min (610M, 614M, 708M, 712M) or 15 l/min (622M, 720M) for more than 30 seconds | Engineer |
| Ice still on the evaporator after a long defrost | E163 | Defrost ran past its maximum time; poor airflow, low heat or defrost control fault | Owner clears snow, then engineer |
| Large temperature gap in heating mode | E216 | HP in to HP out difference above 12 °C for more than 15 minutes; low flow | Engineer |
| Heat pump blocked, repeat code shown | E218 | Fourth E135 critical alarm | Installer or engineer only |
| Heavy ice, poor heating, no alarm | None | Defective defrosting automation, refrigerant leak or extreme weather (CTC troubleshooting) | Engineer |
Behind the CTC wording sit the usual water-side problems: a dirt filter choked with sludge, a radiator circuit that has been closed down, low system pressure or a small system with no volume tank. If your EcoZenith shows low pressure as well, our guide to CTC Heat Pump Low Pressure guide explains what to check first.
How do I clear a CTC freeze fault safely?
Work through these owner checks in order, keeping the power on throughout. CTC’s charge pump and condensate tray heater both need mains power to protect the unit.
- Read the alarm text. On an EcoZenith i255 touchscreen or EcoLogic display, note the exact code and time. The alarm log under Advanced, Service holds up to 500 entries, and myUplink shows operating alarms remotely.
- Look at the evaporator from outside. If ice remains on the front of the EcoAir, CTC’s instruction is not to break it loose but to melt it with lukewarm water. Do not use hot water, a heat gun or any tool on the fins.
- Clear the airflow. Brush snow and leaves away from the front and the 250 mm or 400 mm wall gap behind the unit. CTC asks for two metres of clearance to bushes.
- Check the condensate path. Make sure melt water can reach the ground or the drain. A frozen drain hose refreezes the base of the unit.
- Check pressure and valves. Confirm the heating system pressure is in the range your installer set and that radiator valves and any zone valves are open, so the return can reach 25 °C during a defrost.
- Press Reset alarm once. CTC says to press reset and check whether the alarm recurs. E135 is critical, so a repeat needs installer code 4005 to confirm it, and a fourth alarm blocks the heat pump.
Never remove the EcoAir casing, and never touch the refrigerant circuit. CTC’s safety section says not to speed up the defrosting process beyond what the manufacturer recommends. Refrigerant work is restricted to qualified engineers, so if you see heavy ice with poor heating, isolate the unit only if an engineer tells you to, and book a visit.
When to call an engineer
Call an engineer when E135 returns after one reset, because each repeat moves the EcoAir closer to the E218 block. Call straight away if E211 or E163 appears alongside it, if ice stays on the evaporator after a full defrost, if the system pressure keeps falling, or if the house is losing heat in freezing weather.
An engineer will measure the flow and return temperatures at HP in and HP out, test the sensors against CTC’s values, check the circulation pump speed, clean the dirt filter and assess whether the system needs a volume tank. Where ice and poor heating point to a refrigerant leak, only a qualified engineer may open the circuit.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. You can book a book a repair, compare our annual cover with servicing included, or check the engineers across England, Scotland and Wales.
How can I stop E135 coming back?
E135 is prevented by keeping warm water moving through the EcoAir during every defrost. That means a clean dirt filter, correct system pressure, open circuits and enough water volume, which is why CTC’s own actions for the alarm read like a service checklist. An annual service covers the filter, pressure, sensors and a defrost test, and our article on Why Heat Pump Servicing Is So Important explains what a good visit includes.
Siting matters too. CTC asks for a level stand on concrete blocks with a foundation that lets condensate and melted snow drain into the ground, and advises against sheltered spots that recirculate air. If roof snow can fall on the unit, protect it. For running advice through a cold spell, read our guide to Do Heat Pumps Work in Cold Weather, and if you would rather not meet repair bills in January, see whether Is Heat Pump Cover Worth It for your system.
Frequently asked questions
Is E135 the same as a frozen CTC outdoor unit?
No. E135 is about the water inside the EcoAir getting too cold during a defrost, measured at the HP out sensor. A frozen outdoor unit is ice on the air side of the evaporator. The two are linked, because a weak defrost leaves ice behind, but E135 can appear with very little visible ice if the heating return is cold or the flow is low.
Can I confirm E135 myself with code 4005?
The EcoZenith manual gives code 4005 under Advanced, Service, Coded settings as the installer’s method of confirming a critical alarm, and allows three confirmations before the heat pump is blocked. We recommend one Reset alarm press, then an engineer, because confirming the alarm without fixing the cause simply uses up the three chances and risks freezing the heat exchanger.
What is the difference between E135 and E211?
E135 is triggered by temperature at HP out, while E211 is triggered by measured flow during a defrost and only applies to EcoAir 600M, 700M and C100 units fitted with CTC’s Flow Sensor accessory. The thresholds are 10 litres a minute on the smaller models and 15 litres a minute on the 622M and 720M, held for more than 30 seconds.
Why does a CTC EcoAir need a volume tank?
CTC’s manuals give minimum water volumes above 25 °C of 80 litres for the 610M and 614M and 120 litres for the 622M. A small radiator system with thermostatic valves closing down may hold less than that, so the defrost runs out of warm water. A volume tank, which CTC lists as a remedy for E135, adds the missing capacity.
Does E135 mean the refrigerant is low?
Usually not. CTC’s listed causes are circuit temperature, flow and the HP in and HP out sensors. Low refrigerant is in CTC’s troubleshooting list for heavy ice after defrost combined with poor heating, which is a different symptom. Only a qualified engineer can test the refrigerant charge and repair a leak.
Sources and further reading: CTC EcoZenith i255 Installation and Maintenance Manual, alarm list (ctc-heating.com); CTC EcoAir 600M Installation and Maintenance Manual (ctc-heating.com); CTC EcoAir 700M Installation and Maintenance Manual (ctc-heating.com); CTC EcoLogic XL/L/M II Installation and Maintenance Manual (ctc-heating.com).