At a glance
- 89-01, 89-02 and 89-03 all read “Heat exchanger frozen” in Daikin’s Altherma low temperature split installer reference guide: the plate heat exchanger inside the indoor unit has iced.
- Daikin’s minimum water flow during defrost or backup heater operation is 12 litres a minute; below that the unit stops temporarily and the user interface shows 7H-01, which resets itself.
- Daikin states that an error should be understood and dealt with by a licensed installer or dealer before it is reset.
- Daikin’s siting rules for snow: at least 300 mm of free space below the outdoor unit, the unit at least 100 mm above the expected snow level, and a drain pan heater (EKDPH008CA) in colder regions.
- Water pressure in the Altherma circuit should be above 1 bar; low pressure and a dirty filter both cut the flow that keeps the heat exchanger above freezing.
- Daikin’s R32 warning: do not use any means to accelerate defrosting other than those the manufacturer recommends.
What does 89-01, 89-02 or 89-03 mean on a Daikin Altherma heat pump?
Each of the three 89 codes means the heat exchanger in the Daikin Altherma indoor unit has frozen. The plate heat exchanger is the sealed stack of metal plates where refrigerant from the outdoor unit gives up its heat to your heating water. If the water inside it stops moving fast enough on a cold day, it can freeze, and ice expanding inside a plate heat exchanger can crack it.
Daikin’s installer reference guide for the Altherma low temperature split (ERGA outdoor units with EHBH and EHBX indoor units) lists 89-01, 89-02 and 89-03 with the single description “Heat exchanger frozen” and refers engineers to the service manual for the detailed troubleshooting. The guide does not define the sub-number after the dash, so treat it as detail for the engineer and write the whole code down.
On the Daikin user interface a fault appears on the home screen as “Error” or “Malfunction” depending on severity, and the Malfunctioning menu gives the short and long description. The malfunction history is kept in menu 8.2, so an engineer can see whether a 7H flow code came before the 89 code. If the whole system has stopped, our guide to a Heat Pump Not Working guide covers the first checks, and our Daikin Altherma error codes guide explains every other code.
Is ice on a Daikin Altherma heat pump normal?
Frost on the ERGA outdoor unit’s coil is normal in cold, damp weather and the Altherma clears it with a defrost. An 89 code is different: it is ice inside the indoor unit’s heat exchanger, which should never happen while water is circulating properly. So the question to ask is not “is there frost outside” but “why did the water in the indoor unit get cold enough to freeze”.
Daikin’s own answer points at flow. The installer reference guide sets a minimum of 12 litres a minute during defrost or backup heater operation. When flow drops below that figure the unit stops for a while, shows 7H-01 and then resets itself; 7H-06 is the same flow problem during cooling or defrost. A system that keeps throwing 7H codes in December is one short step from an 89 code.
Heavy ice on the outdoor coil is a separate fault, covered in our guide to a Heat Pump Frozen Outside Unit explained, though it can starve the indoor unit of heat and make an 89 code more likely.
How does the Daikin Altherma defrost cycle work?
The Daikin Altherma defrosts by reversing the refrigerant circuit so the outdoor coil warms up and sheds its frost, using heat drawn from the heating water in the indoor unit. That is why Daikin’s installer guide states that during defrost operation the shut-off valve is always opened and sets the 12 litre a minute flow floor: the defrost takes heat out of the water, and if the water is slow or scarce it chills quickly.
Daikin gives installers a manual defrost start in the installer settings (menu 9.H), and the guide warns that in some conditions it is normal for the unit to choose a low water flow. The installer reference guide does not describe what you will see and hear during a defrost, so the general picture of steam, a change in fan noise and water dripping from the base comes from our engineers’ experience rather than from Daikin. Our guide to the Heat Pump Defrost Cycle explained covers that in detail.
Two Daikin settings protect the water side when the unit is not heating: water pipe freeze prevention (field setting 4-04, intermittent or continuous) protects the outdoor water pipes, and room frost protection keeps running even if emergency operation has not been confirmed. Daikin recommends setting Emergency to Automatic if the house will be unattended for a long period.
Why has my Daikin Altherma frozen inside?
An 89 code appears when the plate heat exchanger loses heat faster than the water brings it in, which comes down to flow, water volume and temperature. Daikin’s troubleshooting page for a unit that is not heating as expected lists the checks for low flow: all shut-off valves open, the water filter clean, no air in the circuit, water pressure above 1 bar and the expansion vessel intact. The table below sets out what you may see in a cold snap.
| Symptom | Daikin code | Likely cause | Who acts |
|---|---|---|---|
| “Heat exchanger frozen” on the user interface | 89-01, 89-02, 89-03 | Water flow or volume too low while the unit was cold; ice in the plate heat exchanger | Licensed installer or engineer before any reset |
| Unit stops, then restarts by itself | 7H-01 | Flow below 12 l/min: closed valve, dirty filter, air, low pressure | Owner checks valves and pressure, then engineer |
| Flow fault while defrosting | 7H-06 | Not enough water movement during a defrost | Engineer |
| Outdoor unit stops in heating | A5-00 | High pressure peak cut or freeze protection problem | Engineer |
| Outdoor fan not turning | E7-00 | Outdoor unit fan motor malfunction; ice or debris can jam the fan | Owner clears debris from outside, then engineer |
| Pressure reading wrong or very low | HJ-10 | Water pressure sensor abnormality | Engineer |
If the gauge on your Altherma keeps dropping below 1 bar, read our guide to Daikin Altherma 7H-01 and 7H-05 low water pressure before anything else, because low pressure is the commonest route to low flow.
How do I clear a Daikin Altherma freeze fault safely?
Daikin’s instruction is clear: understand the problem and take measures before resetting the error code, and have that done by a licensed installer or your local dealer. The checks below are the ones an owner can make without opening either unit.
- Record the full code. Open the main menu, then Malfunctioning, and note the long description and the time. Photograph the screen for the engineer.
- Keep the power on. Daikin’s freeze prevention and room frost protection only run with mains power, so do not isolate the unit to “clear” the fault.
- Check the water pressure. Daikin asks for more than 1 bar. If the gauge is below that, a filling loop top-up is reasonable; if it needs topping up repeatedly, there is a leak.
- Open every valve. Any shut-off valve on the indoor unit, zone valve or radiator valve closed for the summer will cut flow. Daikin lists closed valves first in its low-flow checks.
- Look at the outdoor unit from outside. Make sure the ERGA unit is not snowed up, that the 300 mm gap beneath it is clear and that melt water can drain from the base. Do not scrape or pour water on the coil.
- Do not reset repeatedly. Daikin says how a code can be reset is shown on the user interface. One reset after the checks above is sensible; if 89 returns, stop and book an engineer.
Never remove the panels on the EHBH or EHBX indoor unit, and never touch the R32 refrigerant circuit. Daikin’s safety wording for R32 is that you must not use any means to accelerate the defrosting process or clean the equipment other than those the manufacturer recommends.
When to call an engineer
Call an engineer whenever an 89 code appears, because Daikin wants the cause found before the code is reset, and ice inside a plate heat exchanger can crack it. Call straight away if the code returns after one reset, if 7H codes keep appearing in cold weather, if water is leaking from the indoor unit, if the pressure keeps falling below 1 bar, or if you hear gurgling, which Daikin links to air in the system and pump cavitation.
An engineer will check the water filter, purge air with the automatic air purge function, verify the flow rate against Daikin’s 12 litre a minute minimum, check the expansion vessel and freeze prevention settings, and pressure test the heat exchanger if freezing has occurred.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Our engineers work on the Altherma range through our Daikin heat pump servicing and repairs page, you can book a fault diagnosis and repair directly, or compare cover plans. We list the areas we cover by region.
How can I stop the 89 code coming back?
An 89 code is prevented by keeping the Altherma’s water moving: a clean filter, pressure above 1 bar, open valves, no air and the freeze prevention settings active. Those are exactly the items checked at an annual service, and our article on Why Heat Pump Servicing Is So Important guide explains how each one protects the heat exchanger.
Outside, follow Daikin’s siting rules: 300 mm of free space under the outdoor unit, at least 100 mm above the maximum expected snow level, a snow cover or pedestal where needed, and the EKDPH008CA drain pan heater in colder regions so melt water does not freeze in the base. Daikin rates the Altherma for heating down to minus 25 °C outdoors, so the unit itself is not the weak point; the water circuit is. Our guide to Do Heat Pumps Work in Cold Weather guide explains how output changes as temperatures fall, and if you want repairs covered before winter, read whether Is Heat Pump Cover Worth It guide. For a wider view of the brand, see our Guide to Daikin Altherma Heat Pump Review.
Frequently asked questions
Will my Daikin Altherma still heat the house with an 89 code showing?
Usually not in the normal way. The unit protects the heat exchanger by stopping heat pump operation, and depending on your emergency and backup heater settings the electric backup heater may keep some heating or hot water going. Daikin recommends Emergency set to Automatic for unattended homes. Treat backup heat as a stopgap and get the cause of the freeze found.
Why did I get 7H-01 before the 89 code?
7H-01 is Daikin’s low flow warning: the unit saw less than 12 litres a minute, paused and restarted. If that keeps happening in freezing weather the water in the plate heat exchanger is barely moving, so an 89 freeze code often follows. Closed valves, a dirty filter, air or pressure under 1 bar are the usual reasons.
Can a frozen heat exchanger damage my Daikin?
Yes, which is why the code exists. Ice expands, and a plate heat exchanger that has frozen hard can split and leak water into the indoor unit. The 89 code stops the unit early, but repeated freezes stress the plates, so an engineer should pressure test the exchanger after any freeze and fix the flow problem behind it.
Why is my house cold in very low temperatures when there is no code?
Daikin’s troubleshooting lists four reasons for poor heating at low outdoor temperatures: the backup heater not activated, the equilibrium temperature set wrongly, air in the system, and too much capacity going to hot water. All four are settings or water-side issues an engineer can put right in one visit.
Does Daikin let me reset the code myself?
Daikin’s guide says the reset method is shown on the user interface, but also that the problem should be understood and dealt with by a licensed installer or dealer before resetting. One reset after checking pressure and valves is reasonable; repeated resets while the heat exchanger keeps freezing are not.
Sources and further reading: Daikin Altherma Low temperature split Installer Reference Guide, 4P496758-1 (ERGA04 to 08DAV3, EHBH and EHBX 04 to 08DA), error code list and troubleshooting sections (daikin.co.uk).