Grant Aerona Heat Pump C1, C3 & A7 Error: Frozen Outdoor Unit Meaning, Causes & Fixes

Grant Aerona freeze & defrost faults guide tile: a white Grant Aerona outdoor unit against a Cotswold stone wall on a paved area
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

A frozen Grant Aerona heat pump has no code of its own. Ice on the outdoor unit shows up as fan motor error C3 or C1, or as defrost temperature sensor error A7, in Grant's Aerona3 R32 manual. Here is what each code means, what Grant says about resets, and what an owner can safely check.

At a glance

Get a cover plan here >

  • Grant’s Aerona3 R32 manual has no “frozen unit” code. An iced outdoor unit shows as a fan motor error (C3 on the HPID6R32 and HPID10R32, C1 for the upper fan on the HPID17R32) or a defrost temperature sensor error (A7).
  • C3 needs a manual reset; C1 and A7 reset automatically once the fault clears. Grant’s homeowner support page says fault codes should be reset by your installer or service engineer, not by you.
  • The Aerona remote controller flashes a red LED on the ON/OFF switch and shows a warning icon and the code; it also has icons for “Frost protection is active” and “Defrost cycle is active”.
  • A base tray heater switches on at 2.5 °C and off at 5.5 °C to stop condensate freezing in the base; it cannot be adjusted or turned off.
  • Grant’s frost protection runs the water pump when outdoor air is below 4 °C, flow water is below 4 °C or room air is below 14 °C, even when the heat pump is idle, as long as mains power is on.
  • Grant’s clearances are 300 mm above, about 100 mm below, 600 mm in front, 300 mm behind, 100 mm left and 600 mm right of the outdoor unit.

What do C1, C3 and A7 mean on a Grant Aerona heat pump?

C3 means a fan motor error on the single-fan HPID6R32 and HPID10R32, or a lower fan motor error on the twin-fan HPID17R32. C1 means an upper fan motor error on the HPID17R32. A7 means a defrost temperature sensor error. All three come from the outdoor unit error code table in Grant’s Aerona3 R32 installation and servicing instructions, and none of them says “ice” in the manual. Grant lists blown fuses (CF6 or CF7), a faulty fan motor or a faulty main PCB for the fan codes, and a failed sensor for A7.

Ice still matters, because a fan blade locked by ice draws the current that trips a fan error, and a defrost sensor that is reading wrongly lets frost build until the coil is a block. So in winter the code is often the result of icing rather than the cause.

The Grant Aerona remote controller shows a fault by flashing the red LED on the ON/OFF switch and putting a warning icon and the code on the LCD screen; the same code appears on the terminal PCB display inside the unit. If the heat pump has stopped altogether with no code, start with our guide to a Heat Pump Not Working; for every other Aerona code see our Grant Aerona error codes guide.

Is ice on a Grant Aerona heat pump normal?

A film of frost on the evaporator of a Grant Aerona is normal in cold, damp weather and is cleared by the defrost cycle, which the remote controller flags with its “Defrost cycle is active” icon. The base tray heater keeps the condensate tray from freezing, switching on when the ambient temperature reaches 2.5 °C and off again at 5.5 °C, so a healthy Aerona should not grow a block of ice underneath itself.

Ice that encases the fan guard, fills the fin pack or persists after the defrost icon has gone is not normal. Grant’s “water not getting warm” fault, which has no code, lists the defrost heater, the 4-way valve, short cycling from insufficient air circulation and a clogged water circuit among its causes, and each of those can leave ice behind. Our guide to a Heat Pump Frozen Outside Unit shows the difference between frost and a fault across all brands.

How does the Grant Aerona defrost cycle work?

The Grant Aerona defrosts by sending hot refrigerant gas back through the evaporator, with the 4-way valve reversing the circuit, while the defrost temperature sensor tells the controller when the coil is warm enough to stop. That sensor is the part behind code A7, and an engineer can read its live value as monitor display d5, “Defrost temperature”, on the remote controller.

Grant’s installation manual does not state how long a defrost runs or describe what you will see, so the steam and dripping water that owners notice are general heat pump behaviour rather than Grant wording; our guide to the Heat Pump Defrost Cycle explains it. What Grant does specify is the plumbing that makes defrost reliable: a thermal fluid such as Grant HPC at 25 percent by volume, giving frost protection to minus 12 °C with a recommended minimum of minus 10 °C, and a condensate path that drains freely rather than onto a path where it will ice.

Frost protection is separate from defrost. Grant’s parameters 4311, 4321 and 4301 run the water pump when outdoor air drops below 4 °C, flow water below 4 °C or room air below 14 °C, even with the heat pump not operating, provided the mains supply stays on.

Why has my Grant Aerona frozen or shown a fan code?

A Grant Aerona ices up when airflow, defrost sensing or water flow is compromised, and the code you see depends on which part gives way first. Grant’s tables give the electrical causes; the table below adds the cold weather triggers our engineers find behind them.

Symptom Aerona code Cause Who acts
Fan stopped, ice on guard or blades C3 (HPID6R32, HPID10R32, lower fan HPID17R32) Grant: fuse CF6 or CF7, fan motor, main PCB. Ice jamming the blades is the winter trigger Engineer; manual reset only after the cause is cleared
Upper fan stopped on a twin-fan unit C1 (HPID17R32) Grant: fuse CF7, fan motor, main PCB Engineer; auto reset
Frost builds between defrosts, poor heat A7 Defrost temperature sensor or its cable; engineer tests resistance against Grant’s table Engineer; auto reset
Unit trips in high wind or with blocked grille A2, A4 Excess DC or AC current; Grant says check for blockage of the air inlet and outlet Owner clears blockage, engineer resets
Heat pump stops, high pressure FU Outside air recirculation or clogged water circuit; low flow Engineer
No circulation, cold radiators P1 Pump, main PCB or clogged pump and water circuit Engineer

Water-side problems feed all of these. A clogged water circuit, sludge in the magnetic filter or pressure that has drifted low leaves less heat available to clear the coil. If your gauge reads low, our guide to Grant Aerona low pressure covers the filling loop and expansion vessel checks.

How do I clear a Grant Aerona freeze fault safely?

These are the owner checks for an iced Aerona. They do not include a reset, because Grant’s support page says homeowners should not reset a fault code on the Aerona remote controller and that manual resets are for the installer or service engineer.

  1. Leave the mains on. The base tray heater and the frost protection pump runs only work with power. Grant also notes that resetting by switching the mains off and on is possible but not recommended.
  2. Note the code and the icons. Write down C1, C3 or A7 and whether the “Defrost cycle is active” or “Frost protection is active” icon is showing. The unit stores its last ten codes for the engineer to read.
  3. Clear the airflow. Working outside the casing, remove snow and leaves to restore Grant’s 600 mm front and 300 mm rear clearances. Use a soft brush on the fins; Grant’s service instructions allow a soft brush or low-pressure spray on the evaporator, never a pressure washer.
  4. Check the condensate. Grant says it is essential that condensate can drain away. If the outlet has frozen, thaw it with lukewarm water only, well away from the fins.
  5. Check system pressure and valves. Confirm the gauge is in the range your installer set and that radiator and zone valves are open, so defrost has warm water to draw on.
  6. Wait for an automatic reset. C1 and A7 clear themselves once the fault goes. If the fan still does not turn with nothing blocking it, or C3 is showing, book an engineer rather than pressing the reset buttons.

Do not chip ice from the fan or fins, do not pour hot water over the unit, and do not remove covers to reach the fan or fuses. Fuse checks, fan voltage tests and defrost sensor resistance readings are engineer work, and anything involving the R32 refrigerant circuit is restricted to qualified engineers.

When to call an engineer

Call an engineer if C3 is showing, if C1 or A7 stays on once the unit is clear of ice, if the fan is still with nothing blocking it, if the outdoor unit remains a solid block after the defrost icon has cleared, or if A2, A4, FU or P1 appear in the same cold spell. Call straight away if heating or hot water has stopped in freezing weather or if system pressure keeps falling.

An engineer follows Grant’s fault finding section: checking fuses CF6 and CF7, testing the fan motor and main PCB, measuring the defrost sensor’s resistance against Grant’s table and reading the stored code history on the terminal PCB. If the defrost heater, 4-way valve or refrigerant charge is suspected, the refrigerant side is work for a qualified engineer.

UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. See our Grant heat pump servicing and repairs page, book a a repair engineer visit, or look at annual cover with servicing included and the engineers across England, Scotland and Wales.

How can I stop my Grant Aerona icing up again?

Grant’s own annual service list is the best prevention: clearing debris from the evaporator, checking the condensate drain, flexible hoses and insulation, the expansion vessel and system pressure, the antifreeze concentration, the magnetic filter and the electrical connections. A service also confirms the defrost sensor reads correctly before winter. Our article on Why Heat Pump Servicing Is So Important explains what each check prevents.

Installation details matter as much. Grant asks for the unit to be raised about 100 mm off its base and level, with condensate draining away from paths and driveways, and the full clearances kept so the fan does not pull its own cold exhaust back through the coil. Keep the Grant HPC concentration at the level your installer set, because weak thermal fluid removes the frost margin. For running tips in a cold spell read our guide to Do Heat Pumps Work in Cold Weather, and if you would like winter faults covered, see whether Is Heat Pump Cover Worth It. Our Guide to Grant Aerona Heat Pump Review covers the range as a whole.

Frequently asked questions

Is a C3 code on a Grant Aerona always caused by ice?

No. Grant’s table links C3 to a blown CF6 or CF7 fuse, a faulty fan motor or a faulty main PCB, none of which depends on the weather. Ice is simply the most common winter trigger, because a frozen blade stalls the motor. If C3 appears in mild weather, the fan motor or its fuse is the first suspect.

Why does C3 need a manual reset but C1 and A7 do not?

Grant marks C1 and A7 as automatic, so they clear once the fan runs or the sensor reads correctly again. C3 is marked manual, which means the engineer must press the minus and plus buttons together for three seconds on the remote controller, or the reset switch on the terminal PCB, after fixing the cause. Grant’s support page asks homeowners not to do this themselves.

What is the base tray heater on a Grant Aerona?

It is an electric element in the base of the outdoor unit that stops defrost condensate freezing in the tray. Grant’s manual says it turns on when the ambient temperature reaches 2.5 °C and off at 5.5 °C, and that it cannot be adjusted or switched off. It is one reason to keep the mains on through a cold spell.

How does an engineer test the A7 defrost sensor?

The engineer disconnects the sensor, measures its resistance with a meter and compares the reading with the resistance table in Grant’s manual at a known temperature. A value far from the table, or an open circuit, means a faulty sensor or cable. The live reading can also be checked as monitor display d5 on the remote controller.

Can I put a cover over my Grant Aerona in winter?

Not a wrap or tarpaulin, because the fan needs Grant’s full clearances to pull air through the coil and to defrost. A canopy that keeps 300 mm above the unit and the 600 mm front clearance can keep roof snow off, but ask your installer first and never block the air inlet or outlet.

Sources and further reading: Grant Aerona3 R32 Installation and Servicing Instructions, UK DOC 0136 Rev 2.4, February 2024, sections 2.3, 3.5, 3.11, 8.4, 10.1 and 11 (grantuk.com); Grant UK support pages on Aerona error codes and resetting fault codes (grantuk.com/support).