At a glance
- E15 on a Haier heat pump is listed as “Anti-freeze Abnormality” in the installation manual for the R290 Super Aqua Hydro Split and Hydro All in One.
- Haier’s reset rule for E15 is automatic if it has occurred fewer than three times within 60 minutes, otherwise manual.
- Haier describes a heating-mode defrost as lasting about 2 to 10 minutes, with vapour visible at the outdoor unit and condensate flowing from it.
- Codes appear as an E number on the indoor wired controller and as a plain number on the outdoor unit’s digital display tube; during a protection trip the running LED stays lit.
- Haier’s anti-freezing function heats the water to 15 °C when the outdoor temperature drops below 2 °C and the water temperature is below 7 °C, so the unit needs mains power in a frost.
- Haier gives no cause list for E15 and no owner reset procedure, so the cause has to be found by an engineer; the R290 refrigerant is flammable and the circuit must stay sealed.
What does E15 mean on a Haier heat pump?
E15 on a Haier heat pump means the anti-freeze protection has registered an abnormality: the controller has seen a water temperature low enough to risk ice forming inside the hydro unit’s heat exchanger. Haier’s installation manual for the R290 Super Aqua Hydro Split and Hydro All in One lists the code as “Anti-freeze Abnormality” with a remarks column that reads automatic if fewer than three alarms occur within 60 minutes, otherwise manual.
That remark is a reset rule, not a diagnosis. A single E15 on a bitter night clears itself when the water warms; three in an hour locks the code so that someone has to look at the system. The manual gives no causes, so the reasons further down are drawn from how an anti-freeze trip happens on any air to water heat pump: slow or stationary water through the plate heat exchanger while the refrigerant side is running cold.
On a Haier system the code shows as E15 on the indoor wired controller and as the number 15 on the outdoor unit’s digital display tube. If the heat pump has stopped with no code at all, our guide to a guide to Heat Pump Not Working covers the first checks, and our Haier heat pump error codes guide lists every other E number.
Is ice on a Haier heat pump normal?
Frost on the outdoor coil of a Haier Super Aqua is normal in cold, damp weather, and Haier’s manual describes what happens next: the unit enters defrosting in heating mode automatically, the defrost lasts about 2 to 10 minutes, heating output drops while it runs, vapour appears at the outdoor unit and condensate flows from it. None of that should raise E15.
E15 belongs to the water side, not the air side. You can have a clean, frost-free coil and still get E15 if the water in the hydro unit is barely moving, and you can have a heavily iced coil with no E15 if the water is warm and circulating. The two meet when a failed defrost leaves the coil blocked, the heat pump pulls less heat from the air, and the water in the plate heat exchanger drifts towards freezing.
Ice that stays after the 10 minute defrost window, spreads over the fan guard or builds into a block underneath the unit is a fault in its own right. Our guide to a What to know about Heat Pump Frozen Outside Unit describes what that looks like and what not to do about it.
How does the Haier defrost cycle work?
The Haier Super Aqua defrosts by reversing its refrigerant circuit through the four-way valve, so hot gas warms the outdoor coil for the 2 to 10 minutes Haier quotes, then switches back to heating. The defrosting temperature sensor Te(1) on the coil tells the controller when to start and stop, which is why a sensor fault has its own code, E20-0.
Because the defrost takes heat from your heating water, Haier has a second code for the risky case: E87, “Defrosting with over low water temperature”, which resets automatically. E87 and E15 together tell an engineer the system is running out of warm water during defrosts, usually because of low flow, low volume or a closed-down circuit. Our guide to the What to know about Heat Pump Defrost Cycle explains why water volume matters so much.
Haier’s anti-freezing function is the safety net behind E15. According to Haier’s product page it heats the water to 15 °C when the outdoor temperature falls below 2 °C and the water is below 7 °C. The manual warns that water in the pipes and pump may freeze and damage them if the installer does not keep the water above freezing, and advises adding antifreeze after filling. The compressor also waits about five minutes after power-up before restarting, so do not expect instant heat after a trip.
Why has my Haier heat pump frozen or shown E15?
E15 appears when the hydro unit’s water gets cold enough to threaten ice, and in a UK winter that is almost always a flow or volume problem rather than the weather alone. Haier’s manual lists the related codes below; the causes are our engineers’ reading of what sits behind them.
| Symptom | Haier code | Likely cause | Who acts |
|---|---|---|---|
| Code on the wired controller, unit paused, clears on its own | E15 (fewer than three in 60 minutes) | Water briefly too cold: low flow, closed valves, low setpoint overnight | Owner checks valves and pressure |
| E15 locked, needs manual reset | E15 (three or more in 60 minutes) | Persistent low flow, sludge, air, blocked strainer or low volume | Engineer |
| Flow switch or flowmeter trip | E08 | Pump, strainer, air lock or pressure; same three-in-60-minutes reset rule | Owner checks pressure, then engineer |
| Trip during a defrost | E87 | Water too cold while defrosting; low volume or low return temperature | Engineer |
| Frost not clearing, mistimed defrosts | E20-0 | Defrosting temperature sensor Te(1) fault | Engineer |
| Low pressure or high compression ratio | E39-0, E39-1, E78 | Iced coil, blocked airflow or lack of refrigerant | Engineer |
| Upper fan stopped | E71-0 | Fan motor fault; ice or debris on the blades in winter | Owner clears debris from outside, then engineer |
Low system pressure feeds most of the rows above, because a circuit that has lost water loses flow first. If your gauge is low or the unit shows E08 with E15, read our guide to Haier Heat Pump Low Pressure guide before anything else.
How do I clear a Haier freeze fault safely?
These checks are safe for an owner to make. They stop at the casing: the Super Aqua uses R290, which is propane, so the refrigerant circuit must never be opened by anyone without the right certification.
- Note what the controller shows. Record E15 and any companion code such as E08 or E87, with the time. If the running LED is still lit, the unit is in a protection trip rather than switched off.
- Leave the power on. Haier’s anti-freezing function only heats the water to 15 °C if the unit has mains power. Isolating it in a frost removes the protection E15 is warning you about.
- Open the circuit. Check that radiator valves, zone valves and the isolation valves on the hydro unit are open, so warm water can move through the plate heat exchanger.
- Check the pressure gauge. If it reads below the range your installer marked, top up through the filling loop if your system has one and the manual allows it. Repeated top-ups mean a leak.
- Look at the outdoor unit from outside. Clear snow and leaves from the grilles and from under the unit so defrost water can drain. Do not touch the fins, pour water on the coil or probe the drain holes with anything sharp.
- Give it an hour. Haier resets E15 automatically if there have been fewer than three trips in 60 minutes. If the code stays, or returns, the manual reset is engineer work because the cause has not gone.
Do not chip ice, do not use a heat gun, hairdryer or kettle on the coil, and do not remove covers. If you smell gas near the outdoor unit or hear hissing, keep clear, keep sources of ignition away, isolate the unit at the fused spur if you can do so safely, and call an engineer. R290 work needs an engineer with flammable refrigerant training.
When to call an engineer
Call an engineer if E15 has locked after three trips in an hour, if it returns on the next cold night after clearing, if it appears with E08 or E87, or if a low pressure code such as E39-0 or E78 shows at the same time. Call straight away if the outdoor coil stays iced for hours, if the fan will not turn, if water is leaking from the hydro unit, or if there is no heating or hot water in a frost.
An engineer will check the flow switch and flowmeter reading, clean the strainer, purge air, confirm the system volume and pressure, test the Te(1) defrost sensor and check the anti-freeze settings. A refrigerant-side fault behind E39-0, E39-1 or E78 is work for a qualified engineer, with the extra training that R290 requires.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Book a book a repair for a locked E15, compare heat pump cover plans, or check the find your nearest engineer.
How can I stop E15 coming back?
E15 is prevented by keeping warm water moving through the Haier hydro unit on the coldest nights. That means a clean strainer, correct pressure, no air, radiators left open rather than shut down, and antifreeze in the circuit where Haier’s manual says to add it. An annual service covers each of those, and our article on guide to Why Heat Pump Servicing Is So Important explains how a blocked strainer or weak antifreeze turns into a winter trip.
Setpoints matter too. A deep overnight setback leaves the water sitting cold at the coldest hour, which is when a marginal flow problem shows up as E15. Our guide to guide to Do Heat Pumps Work in Cold Weather explains why steady running suits an air source heat pump better than big swings, and if you want winter call-outs included in a plan, see whether guide to Is Heat Pump Cover Worth It for a Haier system.
Frequently asked questions
Does E15 mean the Haier heat exchanger has frozen and cracked?
Usually not. E15 is Haier’s anti-freeze abnormality, which trips before ice can do damage, and the anti-freezing function then heats the water to 15 °C. A cracked plate heat exchanger shows as water leaking from the hydro unit or pressure that falls with no visible leak. If you see either after a frost, isolate the unit and call an engineer.
Why does E15 reset itself sometimes and not others?
Haier’s manual sets the rule: automatic reset if the code has occurred fewer than three times within 60 minutes, otherwise manual. So a single trip while the water warms up clears on its own, but a system that keeps dipping towards freezing locks the code until an engineer resets it after fixing the cause.
Why does E15 tend to show overnight?
The outdoor temperature is lowest before dawn and many homes set the heating back at night, so the water in the hydro unit is cold and slow at the same time. Haier’s anti-freezing function only intervenes below 2 °C outdoors with water under 7 °C, so an overnight E15 usually means the circuit is losing heat faster than the pump can replace it.
Is an R290 Haier heat pump safe to have outside my home?
Yes. The Super Aqua is designed and tested for R290, the circuit is sealed and the refrigerant stays outdoors. The rules are that nobody opens the refrigerant side without the right qualifications and flammable refrigerant training, that the grilles stay clear, and that any smell of gas or hissing is treated as a leak: keep away and call an engineer.
Does E87 mean the same thing as E15?
No. E87 is “Defrosting with over low water temperature”: the water was too cold while the unit was defrosting. E15 is the anti-freeze abnormality in any mode. Both point to the same weakness, too little warm water in the circuit, but E87 tells the engineer the defrost cycle is where the system runs out of heat.
Sources and further reading: Haier Installation Manual for Split Air-to-Water Heat Pump System, no. 0150579603, R290 Super Aqua Hydro Split and Hydro All in One, fault code table and defrosting section (read as a manualslib copy of the official manual, manualslib.com); Haier R290 Hydro Split air to water product page (haierhvac.eu).