Hitachi Heat Pump Frozen Outdoor Unit: Codes, Causes & Fixes

Hitachi freeze & defrost faults guide tile: a white Hitachi Yutaki outdoor unit on a gravel bed beside a modern white house with a timber terrace
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

A frozen Hitachi heat pump usually shows as alarm 104, activation of the low pressure control, because a Yutaki outdoor coil sealed in ice cannot absorb heat and the suction pressure drops. Alarms 105 and 08 can follow. Here is what Hitachi's manuals say, what an owner can safely do and when to call.

At a glance

Get a cover plan here >

  • A Hitachi Yutaki has no single “frozen unit” alarm. A heavily iced outdoor coil most often trips alarm 104, activation of the low pressure control, when suction pressure stays at or below 0.15 MPa for 90 seconds.
  • Alarm 105 follows when the pressure ratio stays below 1.8 for three minutes, and alarm 08 flags an excessively high discharge gas temperature at the top of the compressor.
  • Hitachi’s Yutaki S80 manual displays an alarm when water flow is below 12 litres a minute, and codes 70 and 83 mean no water flow or pump fault and water pressure not detected.
  • Hitachi’s outdoor unit manual allows snow and ice to be removed with warm water of about 50 °C and warns that hotter water damages plastic parts; we advise keeping water off the coil fins altogether.
  • Hitachi asks for a foundation 100 to 300 mm above ground level with drainage, says not to use the drain boss set in a cold area because drain water may freeze, and warns against siting the fan where seasonal wind blows straight at it.
  • Alarms are shown on the Yutaki unit controller (PC-ARFH1E or PC-ARFH2E); Hitachi publishes no homeowner reset sequence.

Why has my Hitachi heat pump frozen?

A Hitachi Yutaki outdoor unit freezes when frost builds on the evaporator coil faster than the defrost cycle removes it, and the alarm you see depends on what the ice does to the refrigerant circuit. A coil sealed with ice cannot absorb heat from the air, so the suction pressure falls. Hitachi’s Yutaki alarm list gives alarm 104 for activation of the low pressure control, with a stop when suction pressure stays at or below 0.15 MPa for 90 seconds, and an immediate stop at 0.1 MPa.

Two more alarms follow the same physics. Alarm 105 trips when the pressure ratio stays below 1.8 for three minutes, and alarm 08 trips on an excessively high discharge gas temperature at the top of the compressor, which a starved evaporator or a shortage of refrigerant can produce. Some third-party lists give alarms 35 and 38 as overload codes for an iced coil; Hitachi’s own Yutaki manual gives those numbers different meanings, so go by the alarm table for your model.

Ice is only one reason for low suction pressure. A refrigerant leak produces the same alarm in any weather, and a Yutaki that shows 104 on a mild day needs a qualified engineer. If the heat pump has stopped without an alarm, start with our guide to a Heat Pump Not Working questions answered; every other Yutaki alarm is listed in our Hitachi heat pump error codes guide.

Is ice on a Hitachi heat pump normal?

A light coating of frost on the Yutaki’s outdoor coil is normal whenever the air is cold and damp, and the unit removes it with a defrost. Hitachi’s installation documents concentrate on siting rather than describing the defrost itself, but they are specific about water: the outdoor unit manual says drain water sometimes turns to ice on a cold morning, and warns installers not to route it where people walk.

What Hitachi treats as a problem is a unit “covered with snow or ice”. Its instruction to installers is to remove it, using water of about 50 °C at most, because hotter water damages the plastic parts. That is a service instruction for a snow-buried unit, not an invitation to pour kettles over the fins, and our advice to owners is to keep water away from the coil and let the defrost do its work.

Ice that encases the fan guard, fills the coil in a solid sheet or grows into a block under the unit means the defrost is not keeping up. Our guide to a Heat Pump Frozen Outside Unit questions answered shows what that looks like compared with normal frost.

How does the Hitachi defrost cycle work?

The Hitachi Yutaki defrosts by reversing the refrigerant circuit so the outdoor coil becomes the warm side for a few minutes, melting the frost, while heat is drawn from the heating water in the indoor unit. Hitachi’s published installation and operation manuals for the Yutaki S80 and the RAS outdoor units do not describe what the owner will see, so the steam and dripping water you may notice are general heat pump behaviour; our guide to the Heat Pump Defrost Cycle questions answered explains it.

What Hitachi does specify is the water the defrost depends on. The Yutaki S80 manual states that if the water flow is below 12 litres a minute an alarm is displayed on the unit, and gives a working water pressure of roughly 1.5 to 2.0 bar, with 1.8 bar as a proper value. It also warns that water in the pipes may freeze when the system is stopped in very low ambient temperatures, and that the installer must activate the unit’s self-protection.

The S80 is unusual: it has a second, indoor refrigerant stage that lets it deliver 80 °C water, and Hitachi says no antifreeze is to be added to the water circuit on a split system. Keep that in mind if an installer suggests glycol; follow the manual for your model.

Which Hitachi alarms point to ice, and who fixes them?

The table below sets out the Yutaki alarms that cold weather brings on, with Hitachi’s meaning and the usual cause behind each one.

What you notice Yutaki alarm Hitachi meaning and usual cause Who acts
Unit stops, coil iced or frosted solid 104 Low pressure control activated: suction pressure at or below 0.15 MPa for 90 seconds; iced coil, blocked airflow or refrigerant loss Owner clears airflow from outside, then engineer
Unit stops shortly after starting in heating 105 Pressure ratio below 1.8 for three minutes; weak evaporation or low charge Engineer
Repeated stops, compressor hot 08 Excessively high discharge gas temperature at the top of the compressor; starved evaporator or refrigerant shortage Engineer
Cold radiators, pump noise 70 (P70) Water flow not detected or pump defective; air, sludge or a blocked strainer Owner checks valves and pressure, then engineer
Pressure gauge low or zero 83 (P83) Water pressure not detected; leak or expansion vessel Owner checks gauge, then engineer
Fan stalls, scraping noise No alarm until a protection trips Ice or debris on the fan; strong wind driving the fan backwards Owner clears debris from outside, engineer if the fan stays still

If pressure is the weak point on your system, our guide to Hitachi heat pump alarm 70 and low water pressure explains the filling and expansion vessel checks in detail.

How do I clear a Hitachi freeze fault safely?

Hitachi publishes no homeowner reset for a Yutaki alarm, so the owner checks below are about restoring airflow, drainage and water flow, then letting the unit recover.

  1. Record the alarm. Note the number on the unit controller and the time. Alarm 100 is Hitachi’s compressor protection and trips when alarms 02, 07, 08, 45 or 47 occur three times within six hours, so a pattern matters.
  2. Leave the mains on for now. Hitachi’s manual says to switch off the main switch only when the system is being stopped for a long period, because the compressor oil heater draws power; in a cold spell a Yutaki that is powered can protect itself, one that is isolated cannot.
  3. Clear snow and leaves. Working from outside the casing, free the air inlet and outlet. Hitachi’s siting rule is that the fan must not face a seasonal wind, so a windbreak may be the long-term fix.
  4. Check the drain. Make sure melt water can leave the base. Hitachi says not to use the drain boss set in a cold area because the water freezes in it; if the outlet has iced, thaw it with lukewarm water only and keep the water off the fins.
  5. Check the water side. Look at the pressure gauge against Hitachi’s 1.5 to 2.0 bar range and confirm isolation and radiator valves are open, so the defrost has water to draw on.
  6. Wait, then try one restart. If the alarm has not cleared once the coil is free of ice, a single restart at the controller is reasonable. A second alarm is an engineer’s job.

Do not chip or scrape the fins, do not pour hot water over the coil, do not remove any panel of the RAS outdoor unit, and never touch the refrigerant pipework. Alarms 104, 105 and 08 all sit on the sealed refrigerant side, and work on it is restricted by law.

When to call an engineer

Call an engineer if alarm 104 returns after the coil is clear, if 105 or 08 appears at all, if the fan stays still with nothing blocking it, if the outdoor unit remains a block of ice several hours after you cleared around it, or if the water pressure keeps falling. Call straight away if you have no heating or hot water in freezing weather.

An engineer will measure the suction pressure and the pressure ratio the alarms are built on, check the fan motor and the defrost sensors, confirm the 12 litre a minute water flow and look for a refrigerant leak.

UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. See our Hitachi heat pump servicing page, book a our repair service, compare breakdown cover and annual servicing or find the where we work.

How can I stop my Hitachi heat pump freezing again?

Most repeat icing on a Yutaki comes down to siting and maintenance. Hitachi asks for a foundation 100 to 300 mm above the ground with drainage, sufficient clearance around the unit, and a position where the fan is not driven by the prevailing wind, which Hitachi warns can spin it backwards and damage the motor. If your unit sits low, in a wind tunnel or under a dripping gutter, that is where to start.

Hitachi recommends yearly maintenance by qualified technicians, and an annual service is when the water flow, pressure, strainer, fan and defrost sensors get checked before the first frost; our article on More on why heat pump servicing is so important explains why those checks matter more on a heat pump than on a boiler. For running tips through a cold spell read our guide to More on do heat pumps work in cold weather, and if a mid-winter refrigerant fault would be a financial shock, see whether Is Heat Pump Cover Worth It questions answered.

Frequently asked questions

Does alarm 104 always mean my Hitachi is low on refrigerant?

No. Alarm 104 means suction pressure fell to 0.15 MPa or below for 90 seconds, and an iced or blocked coil does that just as surely as a leak. The difference is the weather: 104 on a frosty morning that clears once the coil is free points to icing, while 104 in mild weather points to the refrigerant charge, which only a qualified engineer can test.

Can I pour hot water on my Hitachi outdoor unit to clear ice?

Hitachi’s outdoor unit manual tells installers to remove snow or ice with water of about 50 °C and never hotter, because the plastic parts are damaged above that. We do not recommend it for owners: water on the fins refreezes, and the fan and electrics sit behind them. Clear snow by hand from outside, keep the drain free and let the defrost cycle work.

Why does my Yutaki ice up more just above freezing than in a hard frost?

Air at 2 to 5 °C holds more moisture than air at minus 5 °C, so frost forms on the coil faster and the unit defrosts more often. In a dry, hard frost there is less water vapour to freeze, so the coil may stay cleaner even though it is colder. Damp, still days near freezing are the hardest work for any air source heat pump.

Should I turn my Hitachi off at the isolator during a cold snap?

Not unless an engineer tells you to. Hitachi’s manual reserves switching off the main switch for long stops, and warns that water in the pipes can freeze when the unit is stopped in very low ambient temperatures. A powered Yutaki can run its pump and protections; an isolated one is simply a cold box of water.

Will the backup heater keep my home warm while the unit is iced?

Many Yutaki systems include an electric heater in the indoor unit or cylinder, and whether it steps in depends on how your installer configured the controller. It can keep some heat or hot water going while a coil defrosts, but it costs more to run than the heat pump and it does not fix the icing. Treat it as a stopgap.

Sources and further reading: Hitachi Yutaki S80 Installation and Operation Manual PMEN0648 (documentation.hitachiaircon.com); Hitachi Yutaki Series Outdoor Unit Instruction Manual PMML0372B (documentation.hitachiaircon.com); Hitachi Yutaki Series Installation and Operation Manual PMML0510, alarm code table (read as a manualslib copy of the official manual, manualslib.com).

Myles Robinson

Written by , an expert in heating and renewables with over 15 years in the industry. The guides published here are written and maintained by Myles with input from the company's engineering team, and are reviewed whenever grant schemes, prices or manufacturer advice change.