Ideal Heat Pump 370 F27 & AE Error: Low Water Pressure Meaning, Causes & Fixes

Ideal Heat Pump 370 low water pressure guide tile: a close-up of an Ideal indoor unit on a new-build installation
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

Ideal Logic Air error 370 with sub-code F27 means no water flow, and Ideal's installation guide sets the expected system pressure at 1 to 1.5 bar with a 0.5 bar minimum. Check the gauge and top up if you are competent; if F27 or the outdoor unit's AE low water flow code returns, call an engineer.

At a glance

Get a cover plan here >

  • 370 is the Logic Air’s general heat pump fault; sub-code F27 is “No water flow fault” in Ideal’s installation and maintenance guide UIN 252130 A02 (October 2026).
  • Ideal’s system specification table gives a minimum system pressure of 0.5 bar, an expected pre-charge of 1 to 1.5 bar and a maximum operating pressure of 3.0 bar.
  • Filling is done by opening the filling loop gradually while watching the pressure gauge until the system reads 1 to 1.5 bar.
  • AE on the outdoor unit is “Low water flow error”: flow below the minimum for 10 seconds continuously, one minute after pump start, and the compressor stops.
  • 9B is the circulation pump error and A5 is a refrigerant-side low pressure error, which is engineer work.
  • Yes, a blocked magnetic filter or strainer gives the same F27 message with a perfectly normal gauge reading.

What does F27 and AE mean on an Ideal Logic Air heat pump?

370 F27 on an Ideal Logic Air means the controller has flagged a heat pump fault, 370, whose sub-code F27 is “No water flow fault”. In plain terms, the heat pump has tried to move water around the heating circuit and the flow sensor is not seeing enough of it. The unit then stops the compressor to protect itself. Ideal’s installation and maintenance guide lists every 370 sub-code against a troubleshooting section, and F27 points to Troubleshooting 24, the low water flow procedure.

It is easy to assume F27 is purely a pressure fault, but pressure is only one possible cause. Ideal’s Troubleshooting 24 forecast of causes runs: condenser pump speed too low, closing of the water loop (radiator valves), no sufficient water pressure in the loop, anti-freeze valve opening, valve status between indoor and outdoor unit, sludge filter trap clogged, circulating pump blocked, and the connection between flow rate sensor and PCB. Pressure is the quickest thing to rule out, which is why it comes first on this page.

On the outdoor unit itself, the maintenance manual lists AE as the “Low water flow error”. The unit flags it when, one minute after the pump has started, the flow rate drops below the minimum operating flow for 10 seconds continuously, and the compressor stops. The outdoor unit’s LEDs show it as 10 green blinks and 14 red. The same manual lists 9B as a circulation pump error. Neither of these is a dedicated “low pressure” code, and Ideal does not publish a separate hydraulic low-pressure alarm for the Logic Air that we could find. The Logic Air also has refrigerant-side pressure codes, such as A5, which is a low pressure error on the gas side. That has nothing to do with the water in your radiators and is engineer territory. Our Ideal heat pump error codes guide covers the rest of the list, and the Heat Pump Not Working guide covers checks common to every make.

What pressure should an Ideal heat pump be?

An Ideal Logic Air system should be filled to between 1 and 1.5 bar cold. Ideal’s installation and maintenance guide gives, in its system specification table, a maximum system operating pressure of 3.0 bar, a minimum system pressure of 0.5 bar and an expected system pre-charge of 1 to 1.5 bar. The filling instructions repeat it: “The filling loop is to be gradually opened whilst looking at the pressure gauge. Fill the system to between 1 to 1.5 bar.” The annual service section asks the engineer to re-pressurise the system to 1 bar, “considering the position of the gauge in relation to the heat pump”, and to check the central heating expansion vessel pre-charge of 1 bar.

That last phrase matters. Pressure is measured where the gauge is, and a gauge in a ground-floor cupboard reads higher than one next to an outdoor unit at roof level, because of the weight of water above it. The Logic Air monobloc has no indoor hydraulic unit of its own, so the gauge is usually on the pre-plumbed cylinder or on the filling loop assembly fitted by the installer. The controller shows active faults on its home screen with a bell icon, but it does not display a pressure figure, so the dial is your only reading. If you cannot find the gauge, ask your installer or check the installation manual for your cylinder.

Why does an Ideal heat pump keep losing pressure?

A sealed heating circuit should hold its pressure for months. When it does not, the usual causes are:

  • A small leak at a radiator valve, pipe joint, pump connection or the pressure relief valve.
  • A failed or badly charged expansion vessel, which lets pressure swing and then drop. Ideal specifies a 1 bar pre-charge for the heating vessel.
  • Air in the system that has been released through the automatic air vent, taking pressure with it.
  • The pressure relief valve discharging after pressure spiked, then not reseating properly.
  • Recent bleeding or radiator work, where water was released and not replaced.
  • A blocked magnetic filter or Y-strainer, which causes the same F27 flow message even though pressure is fine.
  • A faulty flow sensor or pump, which can report no flow when there is plenty.
  • A pressure sensor or gauge fault, so the reading does not match the real pressure.

Homeowners are often surprised that a blocked filter is such a common cause. Installers report that the filter mesh next to the unit is the first place to look when low flow errors appear, particularly in the first year after installation when debris is still working its way out of the pipes. Ideal’s own filling caution says the same thing from the other direction: if pressure is difficult to achieve, or drops after it has settled, the circuit should be checked for leaks. Winter adds a defrost cycle, when the outdoor unit briefly reverses to melt ice and needs good flow from the house; our guide to a frozen Ideal outdoor unit and the F15 and F17 codes covers what happens when it does not get it.

How do I top up the pressure on an Ideal heat pump?

Ideal’s filling procedure is written for the installer, but a competent owner can repeat the top-up part if the filling loop is accessible and the installer has shown you how. Work through these steps in order.

  1. Look at the pressure gauge on the system. Note the reading, and whether it is cold or hot, as pressure rises a little when the water warms up.
  2. Look for visible drips or damp patches around the unit, the cylinder, pipework, radiator valves and under floors.
  3. Check the radiator valves and any zone valves are open, so water can circulate.
  4. Make sure the outdoor unit has power and write down the full code from the controller’s home screen, for example 370 F27.
  5. Only if you are competent and the manual allows it, open the filling loop gradually while watching the gauge, stop between 1 and 1.5 bar, then close it fully and disconnect it. Never leave the loop connected.
  6. Reset the fault once as the user guide describes. If it comes back, stop there.

Read our guide on a Heat Pump Losing Pressure guide for more on what is normal and what is not.

What not to do:

  • Do not touch any refrigerant pipework or connections.
  • Do not remove panels or covers on the outdoor unit or cylinder.
  • Do not keep over-pressurising the system to make the error go away. High pressure can lift the relief valve and damage components.
  • Do not ignore repeated top-ups. If you are adding water more than once, something is wrong.
  • Do not remove or clean the filter unless you know how to isolate it, as water will escape.

Which Ideal codes appear with low pressure?

These are the water-side and related codes we could verify from Ideal’s installation and maintenance guide and the Logic Air maintenance manual. Code meanings can differ between models and software, so check your own manual.

Code Meaning First step
370 F27 No water flow fault Check the gauge reads 1 to 1.5 bar, top up if low and competent, then call an engineer if it returns
AE Low water flow error on the outdoor unit; flow below minimum for 10 seconds, one minute after pump start Check pressure and valves, then book an engineer to check the filter and flow sensor
9B Circulation pump error Do not keep restarting. Book an engineer to check the pump and filter
F24 Primary circulation pump sub-code under 370 Same as 9B: engineer to test the pump
A5 Low pressure error on the refrigerant side Switch off if advised and call an engineer. Not a water pressure fault

How can you stop it happening again?

When to call an engineer

  • The pressure drops again within days or weeks of a top-up.
  • 370 F27 returns after you have restored the pressure to the right range.
  • You can see water on the floor, around the unit or from the relief valve discharge pipe.
  • The filter or strainer needs cleaning and you are not sure how to isolate it safely.
  • The pressure gauge reads normal but the code persists, which suggests a sensor, pump or flow switch fault.
  • Any refrigerant-side code, such as A5, appears.
  • You have no heating or hot water.

Book early. A slow leak is much cheaper to find than a flooded floor, and a heat pump that keeps tripping on low flow is working harder than it should, which is one reason Do Heat Pumps Work in Cold Weather guide suffers. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Our engineers find the leak, check the expansion vessel and air vent, clear blocked filters and re-pressurise to Ideal’s figure. Book a book a repair, see cover plans so small faults get caught before they stop your heating, or check the areas we cover. If you are weighing a plan up, Is Heat Pump Cover Worth It guide sets out the sums.

Frequently asked questions

Can low water pressure damage an Ideal heat pump?

Running with too little water can stress the circulation pump and cause the unit to lock out repeatedly. The compressor is protected by the flow check, which is why you see the fault, but repeated trips are not good for any heat pump. Get it looked at rather than resetting it again and again.

Will the heat pump restart by itself after F27?

Sometimes the unit retries once the flow returns, but if the cause is still there it will fault again. Constant restarting just hides the problem and wears the pump. If it has locked out more than once, note the time and code each time and book an engineer.

Is it normal for pressure to go up when the heating is on?

Yes, a small rise as the water warms is normal, because the expansion vessel absorbs it. Ideal specifies a 1 bar pre-charge for that vessel. A big jump, or water coming from the discharge pipe, points to a vessel or relief valve problem that needs checking.

Does the Ideal warranty cover a pressure fault?

That depends on the cause and the terms of your warranty. Faults caused by poor installation or lack of servicing may not be covered, so keep your Benchmark service records and check the paperwork that came with the unit before anyone works on it.

How long does an engineer take to fix low pressure?

A filter clean or top-up and re-pressurise can be done in one visit. Finding a slow leak can take longer, as the engineer may need to pressure test sections of pipework, and underfloor circuits add time because the pipe runs are hidden.

Sources and further reading: Ideal Heating, Logic Air Monobloc Heat Pump System installation and maintenance guide with user guide, UIN 252130 A02 (10/2026), Table 9 system specification, section 5 filling, section on annual servicing and fault code list (PDF); Ideal Heating, Logic Air 8-10 Maintenance Manual U0753484_2451_EN_1 (24/05/2023), error code table and Troubleshooting 24 (PDF); both listed on Ideal’s Logic Air guides page. Checked 30 October 2026.