Mitsubishi Ecodan Heat Pump Low Pressure: Causes, Checks & Fixes

Mitsubishi Ecodan low water pressure guide tile: a Mitsubishi Ecodan pre-plumbed cylinder installed indoors
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

Mitsubishi Ecodan heat pumps have no dedicated low water pressure error code. Low pressure shows as a low gauge reading or a flow fault, often L9, and the EHPT20Q cylinder manual sets the primary circuit at 1 bar minimum and 2.5 bar maximum. Read the gauge, top up if below the minimum, and call an engineer if the code returns.

At a glance

Get a cover plan here >

  • No Ecodan error code says “low water pressure”; the installation manual we checked lists pressure limits but attaches no code to them.
  • For the EHPT20Q-VM2EA cylinder unit: minimum primary working pressure 1.0 bar, maximum 2.5 bar, pressure relief valves set at 3.0 bar, expansion vessel charge 1.0 bar, commissioning pressure 1 bar.
  • The manual’s own instruction is “Top up with water as necessary (if pressure is below 1 bar)”.
  • L9 is “Low primary circuit flow rate detected by flow sensor”; L3 is circulation water temperature overheat protection; LF is a flow sensor failure.
  • The manometer (pressure gauge) is a numbered part on the cylinder unit itself, and the filling loop is a supplied accessory whose flexible hose must be removed after filling.
  • Figures differ between Ecodan cylinders and hydroboxes, so check the installation manual for your model before filling.

Why is my Mitsubishi Ecodan heat pump showing low pressure?

A Mitsubishi Ecodan shows low pressure on the gauge rather than on the controller, because Mitsubishi lists no dedicated low water pressure code. In the Ecodan installation manuals we reviewed, the error tables contain no code that says “low water pressure”. The manual for the EHPT20Q-VM2EA cylinder, for example, sets a minimum primary working pressure and tells you to top up the water if the pressure falls below it, but it does not attach an error code to that situation. That is why this is a general low pressure guide rather than a single-code article.

What you are more likely to see is a flow-related code. L9 is defined as low primary circuit flow rate detected by the flow sensor (or flow switch on some models). The manual’s suggested checks are for water leakage, strainer blockage and clogged piping, plus the circulation pump and bleeding air from the primary circuit. A system that has lost water to a leak can easily end up with too little flow, so L9 is a possible knock-on effect of low pressure.

L3 is the circulation water temperature overheat protection. The manual notes that the flow rate may be reduced, and the same causes apply: leaks, a blocked strainer, clogged piping or a pump problem. It also says L3 can appear while the primary circuit is still being filled, in which case the filling should be completed and the error reset. LF is a flow sensor failure, which is a sensor fault rather than a pressure fault. The full list is in our Mitsubishi Ecodan error codes guide, and the broader What to know about Heat Pump Not Working covers symptoms that are not brand-specific.

What pressure should a Mitsubishi Ecodan heat pump be?

An Ecodan primary circuit should sit between 1.0 and 2.5 bar, using the EHPT20Q-VM2EA cylinder unit as the worked example. That manual gives a minimum primary working pressure of 1.0 bar, a maximum of 2.5 bar, two pressure relief valves set at 3.0 bar, a primary expansion vessel charge pressure of 1.0 bar and a commissioning instruction to “adjust water pressure within primary circuit to 1 bar”. Those numbers come from that particular cylinder, which pairs with the QUHZ-W40VA outdoor unit, and other Ecodan units differ, so use your own manual’s figures and take the cautious reading if you are unsure.

On the EHPT20Q the manometer is a numbered component on the cylinder unit, so the pressure gauge is on the unit itself rather than somewhere in the cupboard. On hydrobox installations the gauge is usually on the pipework or the filling loop assembly fitted by the installer. The main controller does not show a pressure figure; it shows error codes and operating data, so the dial is where you read pressure. If your Ecodan is a different cylinder or hydrobox, check the installation manual for your model for the gauge position and the working pressure range.

Why does a Mitsubishi Ecodan heat pump keep losing pressure?

The Ecodan primary circuit is sealed, so a falling gauge means water is escaping or has been absorbed into air pockets. Typical causes are:

  • Leaks at pipe joints, radiator valves, underfloor manifolds or the connections on the cylinder or hydrobox.
  • A failing expansion vessel whose air charge has dropped. Mitsubishi gives 1.0 bar as the charge for the vessel in the EHPT20Q manual, and a vessel that has lost it cannot cushion the pressure swings.
  • Air in the primary circuit, which also raises the risk of an L9 flow fault. The manual says the slightest amount of air can reduce efficiency and even cause the cylinder unit to fault.
  • A pressure relief valve discharging after being over-pressurised or after a vessel failure. The outlet is piped to a tundish and drain, so check there.
  • Recent bleeding, radiator changes or maintenance that removed water without a proper top-up.
  • A leaking automatic air vent on the hydrobox or pipework.

A modest rise in the gauge when the system is hot is normal because water expands, but a gauge that ends up lower after every cycle points to a loss of water or a tired expansion vessel. The manual adds a useful detail: pressurise with the thermal store cold, because if the system is pressurised hot, the drop as it cools can draw air into the pump. In winter the defrost cycle borrows heat from the primary circuit to clear the outdoor coil, and that is when weak flow shows up as a freeze protection code; our guide to the Ecodan L6 and P6 freeze protection errors covers that side.

How do I top up the pressure on a Mitsubishi Ecodan heat pump?

Mitsubishi’s instruction in the EHPT20Q manual is plain: “Top up with water as necessary (if pressure is below 1 bar).” The manual also says the filling loop’s flexible hose must be removed after filling and that an old filling loop should not be reused. If your installer fitted the loop where you can reach it and showed you how, the steps are:

  1. Read the pressure gauge with the system cold and compare it with the minimum in your manual. For the EHPT20Q cylinder that minimum is 1.0 bar.
  2. Note any code on the controller, such as L9 or L3, and when it appeared.
  3. Look for visible drips at the cylinder or hydrobox, pipework, radiators and the tundish under the relief valves.
  4. Check radiators and zone valves are open, including any thermostatic valves that may have been turned right down.
  5. Connect the filling loop hose if it is the removable type, open the valves slowly, and stop at the figure your installer recorded, which for this cylinder is 1 bar cold.
  6. Close both valves, remove the hose, and bleed any radiator that has gone cold at the top, then recheck the gauge.

If you have never repressurised a sealed system, read our guide to a Guide to Heat Pump Losing Pressure first; it covers the filling loop and what a normal rate of loss looks like.

What not to do:

  • Do not go near the refrigerant side. On a packaged Ecodan it is a sealed CO2 circuit and on splits it is R32 or R410A; either way it is engineer work and has nothing to do with the water gauge.
  • Leave the cylinder and outdoor unit casings in place. The booster heater, pumps and live wiring sit inside.
  • Do not fill past the 2.5 bar maximum. The two relief valves open at 3.0 bar and will dump water into the tundish.
  • Two refills in a season mean a leak or a flat expansion vessel, not bad luck.
  • Do not open or clean the built-in strainer yourself unless you know how to isolate the circuit. Opening it on a pressurised system will release water quickly.

Which Mitsubishi Ecodan codes appear with low pressure?

Mitsubishi lists no pressure code, so these are the flow-related Ecodan codes most likely to appear when pressure or circulation is poor, taken from the EHPT20Q-VM2EA installation manual.

Code Meaning First step
L9 Low primary circuit flow rate detected by the flow sensor or flow switch. Check the gauge and valves, then book an engineer to check for leaks, strainer blockage, air and the pump.
L3 Circulation water temperature overheat protection. Flow may be reduced by leaks, a blocked strainer, clogged piping or a pump fault. If the system was just refilled, let the filling finish and reset. Otherwise book an engineer.
LF Flow sensor failure. Leave this one to an engineer, who will test the sensor and cable.
LU Water circulation pump failure. Do not keep resetting. Book an engineer.

Code letters and numbers can vary between Ecodan generations and controllers, so match yours against the manual for your exact cylinder or hydrobox.

How can you stop it happening again?

When to call an engineer

  • L9 or L3 appears more than once, or the heat pump stops heating altogether.
  • The gauge falls within days of a top-up.
  • The pressure relief valve is dripping or has blown.
  • You can see water around the cylinder, hydrobox or pipework.
  • The pressure jumps up sharply when heating starts, which suggests the expansion vessel has failed.

Act on it early. Each refill brings in fresh oxygenated water, and over a winter that is enough to start corrosion and sludge in a primary circuit that Mitsubishi asks to be kept clean and air-free. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We repair Mitsubishi Ecodan systems, clearing strainers, recharging expansion vessels and putting the primary circuit back to the correct pressure. Book a our repair service, visit our Mitsubishi Electric heat pump servicing and repairs page, compare a heat pump service plan if you would rather spread the cost of looking after the system, or check the local heat pump engineers. For the wider picture, what to know about Is Heat Pump Cover Worth It and our Guide to Mitsubishi Ecodan Heat Pump Review are good next reads.

Frequently asked questions

What pressure should an Ecodan be at?

It depends on the model. The EHPT20Q-VM2EA manual gives a 1.0 bar minimum and 2.5 bar maximum working pressure, with 1 bar set at commissioning, but always use the figures in your own installation manual or the label your installer left next to the gauge.

Why does my Ecodan pressure rise when the heating is on?

Water expands as it warms, and the expansion vessel absorbs the extra volume. A gentle rise is normal, but a big jump or a pressure that never recovers when cold means the vessel needs checking. Mitsubishi specifies a 1.0 bar charge for the EHPT20Q’s vessel.

Is L9 always a leak?

No. L9 is a flow fault, and a blocked strainer, trapped air, a seized pump or a faulty flow sensor can all cause it. The manual’s own L9 actions include discharging air from the primary circuit and running the pumps manually to flush debris off the flow sensor. A drop in pressure is one possible cause among several.

Can I reset an Ecodan error myself?

You can acknowledge a code through the main controller if your manual allows it, but resetting does not fix the cause. The manual notes that L3 can appear during filling and should be reset once filling is complete. If any code comes back, stop resetting and book an engineer.

Does a low pressure fault stop hot water too?

It can. If the primary circuit flow drops, the unit may lock out and stop heating the cylinder as well as the radiators, because the same primary pump serves both. An engineer should look at it promptly before a cold snap.

Sources and further reading: Mitsubishi Electric, Cylinder Unit EHPT20Q-VM2EA Installation Manual for Installer, technical data table, section 3 water pipework, commissioning and error code tables (Mitsubishi Electric UK document library). Checked 30 October 2026.