At a glance
- NIBE alarm 228 (shown as 236 on S-series systems) means “10 failed consecutive defrostings. Defrosting fault”: the outdoor unit has tried ten times in a row to clear its evaporator and failed.
- NIBE’s listed causes for alarm 228 are system temperature and/or flow too low, insufficient available system volume, and significant wind effect.
- A NIBE active defrost runs with the compressor on and the fan off; a passive defrost (compressor off, fan on) is used when the outdoor temperature is above 4 °C, and the countdown to the next defrost is shown on the indoor module.
- Alarm 183 simply means defrosting is in progress and is not a fault.
- NIBE says there is no harm in acknowledging an alarm, but it recurs if the cause remains; on the F2040, switching the power off and on too quickly can itself bring up alarm 220.
- NIBE’s siting rules put the lower edge of the evaporator at least 300 mm above the ground or above the average local snow depth, on a base at least 70 mm high, sheltered from direct wind.
What does alarm 228 mean on a NIBE heat pump?
Alarm 228 on a NIBE heat pump means the outdoor unit has failed to defrost ten times in a row. NIBE’s installer manual for the S2125 gives the alarm text as “10 failed consecutive defrostings. Defrosting fault”, numbered 236 on S-series control modules and 228 on F-series ones, and states separately that after failing to defrost ten times the heat pump must be checked. The alarm is NIBE’s way of saying that ice on the evaporator, the finned coil on the outdoor unit, is winning.
NIBE lists three things that may be behind it: system temperature and/or flow too low, insufficient available system volume, and significant wind effect. The first two are about the heating water that the defrost borrows its heat from; the third is about cold wind blowing through the evaporator while it is trying to warm up, which is why NIBE insists the unit is sheltered from direct wind.
On an SMO 40 control module the alarm shows with a red status lamp and a bell symbol; on an SMO S40 or VVM S-series indoor module the status lamp shines a steady red and the smart guide explains the alarm. If the whole system has stopped instead, start with our guide to a Heat Pump Not Working guide; for every other alarm number see our NIBE heat pump error codes guide.
Is ice on a NIBE heat pump normal?
Yes. Frost on the evaporator of a NIBE F2040, F2120 or S2125 is expected in cold, damp weather, and NIBE builds the defrost around it. The F2040 service manual lists 183, “Defrosting in progress”, as an information message with no alarm status, so seeing 183 on the display is the unit working as designed, not a reason to call anyone.
NIBE also has a “fan de-icing” function on the S2125: when ice or snow sticks to the fan, grille or cone, the unit blows warm air from the evaporator across them, and NIBE’s user manual says you may notice abnormal fan noise while it runs. Melt water from all of this can reach 50 litres a day, which must drain to a frost-free outlet, and NIBE asks owners to check that the drain holes in the bottom panel are free of dirt and leaves and that condensate is routed away correctly through the condensation pipe.
What is not normal is ice that outlasts the defrost countdown, spreads across the fan guard or builds into a slab under the unit. NIBE’s answer to that is a separate alarm, 291 or 341 “Recurring safety defrosts”, which it links to poor airflow “because of leaves, snow or ice”. Our guide to a Heat Pump Frozen Outside Unit explained shows the difference across brands.
How does the NIBE defrost cycle work?
A NIBE outdoor unit defrosts on a timer that starts when the evaporator sensor BT16 drops below the defrost start temperature, which the installer can set between minus 3 and 0 °C. The countdown to “active defrosting” is shown on the indoor module or control module, so you can watch it approach. When the count reaches zero NIBE runs one of two routines:
- Active defrost, with the compressor on and the fan off: the four-way valve reverses so hot gas warms the evaporator, drawing the heat from your heating water.
- Passive defrost, with the compressor off and the fan on, used when the outdoor sensor BT28 reads above 4 °C and the air alone can melt the frost.
NIBE’s S2125 manual states the fan stops and the compressor continues to run during an active defrost; it does not mention steam or a whoosh, so those are general heat pump sounds rather than NIBE wording. Our guide to the Heat Pump Defrost Cycle explained covers them.
Because an active defrost pulls heat from the system, NIBE requires the installer to design in a minimum defrosting flow at 100 percent pump speed and enough system volume, and it adds a safety defrost if the evaporator gets too cold. An installer can also start a manual defrost from the installer menu. The F2040 has a drain pan heater (EB11) with a thermostat that switches on at 25 °C and off at 35 °C to keep melt water from refreezing in the base.
Why has my NIBE heat pump failed to defrost?
Ten failed defrosts in a row means the evaporator never got warm enough to shed its ice, and NIBE’s three causes are the place to start. The table puts alarm 228 alongside the other cold weather alarms NIBE documents.
| Symptom | NIBE alarm | Cause | Who acts |
|---|---|---|---|
| Ice stays on the evaporator, alarm after a cold night | 228 (F-series) / 236 (S-series) | System temperature or flow too low, insufficient system volume, significant wind effect | Owner checks pressure and valves, engineer for flow, volume and wind shelter |
| Display shows a defrost message, no alarm | 183 | Defrosting in progress | Nobody; wait for it to finish |
| Repeated safety defrosts | 291 / 341 | Poor airflow from leaves, snow or ice on the evaporator | Owner clears the unit from outside, then engineer |
| Fan will not start | 224 | Fan blocked or not connected after five unsuccessful start attempts; NIBE asks whether foreign material is obstructing the propeller | Owner clears debris, engineer if it persists |
| Low pressure trips | 221 | Low pressure transmitter reading too low three times within 60 minutes; iced coil or refrigerant loss | Engineer |
| Low evaporation alarm | 232 (F) / 240 (S) | Five low evaporation alarms within four hours; lack of refrigerant, blocked expansion valve or wind effect | Engineer |
| Heat pump will not run in deep cold | 271 | Outdoor temperature at BT28 below the value that permits operation | Nobody until it warms; engineer if it shows in mild weather |
Low flow and low volume both get worse when the system has lost pressure, so if your NIBE gauge reads low, work through our guide to NIBE heat pump low pressure before acknowledging the alarm.
How do I clear a NIBE freeze fault safely?
NIBE lets owners acknowledge alarms, and its manuals are clear that doing so is harmless but only useful if the cause has gone. Work through these first.
- Read the alarm and the smart guide. Note whether it is 228 or 236 and what the display suggests. The SMO 40 keeps an alarm log under menu 3.4, and the SMO S40 an extended alarm log, so the engineer can see the history.
- Keep the power on. NIBE’s protections, the drain pan heater and the defrost itself all need mains power. On an F2040, NIBE warns that switching the supply off and on too quickly can display alarm 220.
- Clear the evaporator’s airflow from outside. Remove snow, leaves and anything stacked against the unit, keeping NIBE’s clearances of 1,000 mm in front and above and 350 to 500 mm to the wall behind.
- Check the drain holes and condensate pipe. NIBE asks for the bottom panel drain holes to be free of dirt and leaves and for condensate to run to a frost-free outlet. Thaw a frozen outlet with lukewarm water only, away from the fins.
- Check the heating system. Confirm the pressure is in the range your installer set and that radiator and zone valves are open, so the defrost has warm water and flow to draw on.
- Acknowledge the alarm once. Select reset alarm on the display. If 228 comes back within a day or two, stop and book an engineer; each repeat means ten more failed defrosts.
Do not chip or knock ice off the evaporator or fan, do not pour hot water over the unit, and do not remove any panel. Alarms 221 and 232 sit on the sealed refrigerant side, and that is work for an engineer only.
When to call an engineer
Call an engineer if alarm 228 returns after one acknowledgement, if the evaporator stays encased in ice after you have cleared around it, if 291 or 341 shows repeatedly, if 221 or 232 appears, or if the fan grinds or will not turn. Call straight away if the house is cold or hot water has stopped in freezing weather, or if the system pressure keeps dropping.
An engineer will measure the flow and return temperatures and the flow rate during a forced defrost, check the system volume against NIBE’s requirement, test BT16 and BT28, inspect the fan and the drain pan heater, and assess whether wind is reaching the evaporator. If a refrigerant problem is behind 221 or 232, only a qualified engineer may open the circuit.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Visit our NIBE heat pump servicing and repairs page, book a a repair engineer visit, compare cover plans or find the areas we cover.
How can I stop alarm 228 coming back?
Alarm 228 is prevented by giving the defrost what NIBE says it needs: warm water, enough flow and volume, and an evaporator sheltered from the wind. An annual service checks the particle filter, pump speed, pressure and the defrost itself, and our article on Why Heat Pump Servicing Is So Important guide explains how each of those protects the outdoor unit. NIBE’s own user manual notes that insufficient maintenance can cause serious damage to the S2125.
Siting fixes are permanent fixes. NIBE wants the evaporator’s lower edge at least 300 mm above the ground, or above the average local snow depth if that is higher, on a base at least 70 mm tall, with a protective roof where snow could slide off a building onto the unit. If your unit faces the prevailing wind, ask an engineer about a windbreak that keeps the clearances. For running advice in a cold spell read our guide to Do Heat Pumps Work in Cold Weather guide, and if you would like winter faults covered, see whether Is Heat Pump Cover Worth It guide. Our guide to Nibe Heat Pump Review looks at the range as a whole.
Frequently asked questions
Does cold weather cause alarm 228 on its own?
Cold, damp air is what frosts the evaporator, but a healthy NIBE clears that frost every cycle. Ten failed defrosts in a row means something is stopping the coil warming up: NIBE names low system temperature or flow, too little system volume and wind through the evaporator. The weather is the trigger; the cause is in the installation.
What is the difference between alarm 228 and alarm 183?
Alarm 183 is an information message meaning a defrost is in progress, with no alarm status, and it disappears when the defrost finishes. Alarm 228 is a fault raised only after ten consecutive defrosts have failed. If you see 183 regularly and 228 never, the defrost is working.
What does alarm 83 mean on a NIBE?
We could not verify alarm 83 in the NIBE manuals we checked for the F2040, S2125 and SMO control modules, so we do not give a meaning here. If your F750 or other indoor unit shows 83, read the alarm text on the display and check the installer manual for that model, or ask an engineer to read the alarm log.
Does acknowledging alarm 228 wipe it from the log?
No. The SMO 40 keeps an alarm log in menu 3.4 and the SMO S40 keeps an extended alarm log, so an engineer can still see when 228 appeared and how often. NIBE says there is no harm in acknowledging an alarm, but note the date and the weather so the pattern is clear when the engineer visits.
Will my heating still work while alarm 228 is showing?
The heat pump may be blocked until the alarm is dealt with, and the indoor module can switch to aid mode or auxiliary operation, where the electric additional heater produces heat and hot water. That keeps the house warm but costs more per kilowatt hour than the compressor, so treat it as a stopgap while the defrost fault is fixed.
Sources and further reading: NIBE S2125 Installer Manual, IHB EN 2525-1, alarm list and defrosting sections (assetstore.nibe.se); NIBE S2125 User Manual, UHB EN 2421-1 (assetstore.nibe.se); NIBE F2040 Service Manual, SEM GB 1503-1 (assetstore.nibe.se); NIBE SMO 40 and SMO S40 installer manuals, alarm handling (nibe.eu).