At a glance
- Vaillant’s aroTHERM plus instructions say that at outdoor temperatures below 5 °C condensation on the evaporator fins may freeze, and that the unit thaws it automatically at intervals by reversing the refrigeration circuit.
- Vaillant states that correct thawing is only possible if the minimum volume of heating water is circulating, which is the condition a de-icing fault code reports.
- F.741 and F.283 are quoted in published code tables as de-icing related faults; we could not verify either in Vaillant’s own aroTHERM plus documents, so read the fault text on your sensoCOMFORT and check the fault table in your indoor unit’s installation instructions.
- Vaillant’s verified cold weather codes include F.733 (evaporation temperature too low), F.718 (fan blocked), F.539 (refrigerant pressure too low, with heavy frosting and a frozen condensate drain among the causes) and F.22 (low water pressure).
- Vaillant’s reset is the round reset button on the heat pump interface, and its winter advice is to keep the outdoor unit switched on, never pour hot water over it and not use any equipment to speed up thawing.
- A heating circuit pressure below 0.5 bar causes a fault shutdown on the aroTHERM plus; the fault clears again above 0.7 bar.
What does F.741 or F.283 mean on a Vaillant heat pump?
F.741 and F.283 are listed in published Vaillant Group code tables as de-icing faults: F.741 is quoted as the return temperature dropping too low during de-icing because the heating system holds too little water, and F.283 as de-icing unsuccessful, taken from the Glow-worm GeniaAir list. We have not been able to confirm either code’s wording in Vaillant’s own aroTHERM plus or sensoCOMFORT documents, and Vaillant’s fault code page does not list them, so treat both as “check your installation manual” codes. The aroTHERM plus instructions say the fault table lives in the installation instructions for the indoor unit, and the sensoCOMFORT shows the fault message text alongside the code.
What Vaillant does state, in the aroTHERM plus instructions, is the condition behind any de-icing fault: “Correct thawing operation is only possible if the minimum volume of heating water is circulating.” A de-icing cycle borrows heat from the heating water to melt the evaporator, so a small system with thermostatic valves closed down, low pressure or a blocked filter runs out of heat before the ice is gone.
Vaillant’s winter advice page adds the owner’s rule: “If you notice the de-icing mode is not working, call your local Vaillant Renewables Partner.” If the heat pump has stopped entirely, start with our guide to a Heat Pump Not Working guide; every verified Vaillant code is in our Vaillant heat pump error codes guide.
Is ice on a Vaillant heat pump normal?
Yes. Vaillant’s aroTHERM plus instructions explain that at outdoor temperatures below 5 °C the condensation on the fins of the evaporator may freeze, and that the unit thaws it automatically at certain intervals. The instructions list a cloud of vapour at the product during a thawing procedure in high humidity as a normal effect, and Vaillant’s winter advice page says you may see steam and water coming from the base of the unit when de-icing runs for a few minutes.
What is not normal is ice that the thawing cycle cannot shift. Vaillant’s fault code page gives the clearest description of that state under F.539, refrigerant pressure too low, whose causes include heavy frosting and a frozen or blocked condensate drain. F.733, evaporation temperature too low, lists dirt or debris on the outdoor heat exchanger and low refrigerant, and F.718 is the fan unit blocked, which snow and ice on the grille will do.
For a brand-neutral comparison of frost against a fault, see our guide to a Heat Pump Frozen Outside Unit guide.
How does the Vaillant defrost cycle work?
The Vaillant aroTHERM plus de-ices by reversing the refrigeration circuit, so the evaporator on the back of the outdoor unit becomes the warm side for a few minutes and sheds its frost. Vaillant’s instructions describe this directly: thawing occurs by reversing the refrigeration circuit, at intervals set by the unit. Its advice page says de-icing activates when the outdoor air drops below about 2.5 °C, while the instructions give 5 °C as the temperature below which frost can form, so expect de-icing to be a routine event from late autumn.
The heat for the cycle comes from the heating water, which is why Vaillant ties correct thawing to the minimum circulating volume and why its limp home mode exists: if the heat pump cannot run, the electric back-up heater supplies the heating installation, at a cost Vaillant describes as expensive. Vaillant does not describe fan behaviour or a precise duration, so the fan pause owners notice is general heat pump behaviour; our guide to the Heat Pump Defrost Cycle guide covers it.
Vaillant’s instructions also warn what not to do: “Do not use any auxiliary equipment to accelerate the thawing process,” and the winter page says “Please do not pour hot water over the heat pump to defrost it.” Those two lines rule out most DIY remedies.
Why has my Vaillant heat pump frozen or shown a de-icing fault?
An aroTHERM plus fails to de-ice when the water side cannot supply enough heat or the air side cannot shed the ice. The table lists the Vaillant codes that appear in a cold snap, with their verification status.
| Symptom | Vaillant code | Cause | Who acts |
|---|---|---|---|
| Fault during or after de-icing | F.741 (check your manual) | Quoted in published tables as return too cold in de-icing from too little system water; not verified in Vaillant’s documents | Installer or engineer; check system volume and back-up heater |
| De-icing does not complete | F.283 (check your manual) | Quoted as de-icing unsuccessful on Glow-worm GeniaAir; not verified for aroTHERM | Engineer |
| Unit stops, heavy frost, drain frozen | F.539 | Refrigerant pressure too low; Vaillant lists heavy frosting and a frozen or blocked condensate drain | Owner clears the drain path, then engineer |
| Poor output in cold weather | F.733 | Evaporation temperature too low; dirt or debris on the outdoor heat exchanger, low refrigerant | Owner clears debris, then engineer |
| Fan not turning | F.718 | Fan unit blocked (fan 1 on a twin-fan unit); snow or ice on the grille | Owner clears snow from the grilles, then engineer |
| Pressure warning | F.22 | Low water pressure in the system; below 1 bar the owner may top up at the filling loop | Owner tops up, engineer if it repeats |
| No circulation | F.788 | Building circuit pump fault | Engineer |
Pressure is the thread through most of these rows: the aroTHERM plus shuts down on a fault below 0.5 bar and will not clear it until the pressure is back above 0.7 bar, and a system that low has little flow for de-icing. Our guide to Vaillant F.22 and F.73 low water pressure covers the filling loop and the Vaillant rule that topping up is at the owner’s own risk.
How do I clear a Vaillant freeze fault safely?
Vaillant allows a reset and gives winter instructions for owners. Follow these in order, and stop at the casing.
- Read the fault text. The sensoCOMFORT or the indoor unit display shows the code with its message text. Write both down, and note the time; the myVAILLANT app may show the same message.
- Keep the outdoor unit switched on. Vaillant’s operating instructions say to ensure the outdoor unit is switched on and remains switched on, because frost damage follows a power cut or a stopped compressor.
- Clear the grilles. Vaillant asks you to regularly remove snow from the air inlet and air outlet grilles and to keep the unit clear of leaves, bushes and branches. Work from outside; do not touch the fins.
- Check the condensate drain. A frozen or blocked drain is one of Vaillant’s listed causes for F.539. Make sure melt water can leave the base; thaw a frozen outlet with lukewarm water only, not on the unit itself.
- Check the heating pressure. If the display shows F.22 or the gauge is under 1 bar, top up via the filling loop as Vaillant allows, then open any radiator or zone valves that were closed.
- Press the reset button once. Vaillant’s method is the round reset button on the heat pump interface, and its page notes that often a reset resolves a fault. If the de-icing fault returns, Vaillant’s instruction is to contact your competent person.
Do not pour hot water over the outdoor unit, do not use a heat gun or any device to speed up thawing, do not chip ice from the evaporator and do not remove panels. F.539 and F.733 sit on the sealed refrigerant circuit, which only a qualified engineer may open.
When to call an engineer
Call an engineer if a de-icing fault returns after one press of the reset button, if F.539 or F.733 appears, if ice stays on the evaporator for hours after the grilles are clear, if the fan does not turn, or if pressure keeps falling below 1 bar after a top-up. Call straight away if the house is losing heat or hot water in freezing weather, and remember Vaillant’s own advice to call your Renewables Partner if de-icing is not working.
An engineer will confirm the heating water volume and flow Vaillant requires for thawing, check the back-up heater is enabled, clean the filter, test the condensate drain, read the fault history on the controller and, where F.539 or F.733 is logged, test the refrigerant charge.
UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. See our Vaillant heat pump servicing and repairs page, book a fault diagnosis and repair, compare cover plans or find the areas we cover.
How can I stop my Vaillant heat pump freezing again?
De-icing faults are prevented by giving the aroTHERM plus the circulating water volume Vaillant specifies, a filter that is clean, pressure held above 1 bar and a back-up heater that is enabled. An annual service covers each of those and tests a thawing cycle; our article on Why Heat Pump Servicing Is So Important guide explains how a blocked filter in autumn turns into a failed de-icing in January.
Siting advice comes from Vaillant itself: fit a snow spacer at installation, because Vaillant says they cannot be added to an existing unit; a canopy or free-standing cover is acceptable only if it keeps good ventilation and airflow; and the outdoor unit must be protected against frost if it is ever decommissioned or disconnected. Vaillant says its heat pumps are tested to minus 25 °C, so the unit copes with cold; the water circuit is what needs looking after. Our guide to Do Heat Pumps Work in Cold Weather guide explains why, and if you would like winter faults covered, read whether Is Heat Pump Cover Worth It guide. Our Vaillant aroTHERM review looks at the range as a whole.
Frequently asked questions
Why can you not confirm F.741 and F.283 for my Vaillant?
Because Vaillant’s public fault code page and the aroTHERM plus and sensoCOMFORT documents we checked do not list them. The codes appear in third-party tables and, for F.283, in Glow-worm GeniaAir material. The fault table for your system is in the installation instructions for your indoor unit, and the sensoCOMFORT shows the message text next to the code, so that is the wording to trust.
Will my Vaillant still heat the house with a de-icing fault showing?
Possibly, through limp home mode. Vaillant’s operating instructions say that when the heat pump cannot run, the electric back-up heater supplies the heating installation, and they warn that generating heat with only the back-up heater is expensive. Use it as a stopgap and have the de-icing fault diagnosed.
Can I pour warm water over my aroTHERM plus to clear the ice?
No. Vaillant’s winter page says plainly not to pour hot water over the heat pump to defrost it, and the aroTHERM plus instructions say not to use any auxiliary equipment to accelerate thawing. Clear snow from the grilles, keep the drain free and let the thawing cycle work; if it cannot, call an engineer.
Why does the aroTHERM plus need a minimum water volume?
Because thawing takes its heat from the heating water. Vaillant’s instructions state that correct thawing operation is only possible if the minimum volume of heating water is circulating. A small system with radiators closed down leaves the de-icing cycle short of heat, which is the condition the published F.741 description refers to.
Does a Vaillant reset clear the fault for good?
Only if the cause has gone. Vaillant says a reset at the round reset button on the heat pump interface often resolves a fault, but its sensoCOMFORT instructions also say to always contact your competent person in the event of a fault message. One reset after clearing snow and checking pressure is sensible; a returning code needs an engineer.
Sources and further reading: Vaillant UK, Heat pump fault codes (vaillant.co.uk); Vaillant UK, How to look after your heat pump in winter (vaillant.co.uk); Vaillant UK, Can my heat pump defrost itself? (vaillant.co.uk); Vaillant Operating instructions, heat pump system with sensoCOMFORT, 8000044890_01 (vaillant.co.uk); Vaillant aroTHERM plus VWL 35/6 to 125/6 A S2 operating and installation instructions, English section (read as a manualslib copy, manualslib.com).