Vaillant Heat Pump F.22 & F.73 Error: Low Water Pressure Meaning, Causes & Fixes

Vaillant low water pressure guide tile: a Vaillant uniTOWER indoor unit in a bright utility room beside a washing machine and tumble dryer
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

Vaillant heat pump fault F.22 means the water pressure in the heating circuit is too low, and F.73 means the water pressure sensor or its wiring has failed. Read the pressure gauge first: a low reading points to a leak or air, while a normal reading with F.73 showing points to the sensor, which an engineer needs to test.

At a glance

Get a cover plan here >

  • F.22 (shown as F.022 on some displays) is “Water pressure too low”, cause “insufficient water in the heating system”, per the aroTHERM VWL /2 A installation instructions.
  • F.73 (F.073) is “Fault: Water pressure sensor”, cause “line to water pressure sensor is broken or has a short circuit”.
  • Vaillant UK’s heat pump fault code page gives a normal range of 1 to 1.5 bar and says a competent owner may top up below 1 bar through the filling loop.
  • The aroTHERM VWL /2 A installation instructions list a heating circuit operating pressure of 1.5 to 2.0 bar, so the figure your installer recorded is the one to use.
  • F.532, building circuit flow rate too low, lists low water pressure among its causes alongside air and a blocked dirt filter.
  • Yes, a falling gauge after a top-up means a leak, a failed expansion vessel or a weeping relief valve, and that needs an engineer.

What does F.22 and F.73 mean on a Vaillant heat pump?

F.22 on a Vaillant heat pump is a low water pressure fault, and F.73 is a water pressure sensor fault. Vaillant’s installation instructions for the aroTHERM VWL /2 A series list these as F.022 and F.073, which many displays and homeowners shorten to F.22 and F.73. F.022 is described as “Water pressure too low”, with the cause given as insufficient water in the heating system. F.073 is described as a fault on the water pressure sensor, with the cause given as a broken line or short circuit between the control and the sensor.

The fixes are different. F.22 is a real loss of water. F.73 is an electrical or sensor problem, so the water may be fine but the heat pump can no longer read it. The gauge tells you which. Vaillant UK’s own heat pump fault code page confirms F.22 as “low water pressure in the system” and lists loose or faulty sensor wiring, a faulty sensor and a faulty expansion vessel as further causes, which is why the two codes are so often confused.

Boiler fault code lists are not the same as heat pump lists, so do not rely on a boiler guide for your aroTHERM. We have only used codes we could confirm in Vaillant’s heat pump documentation. If the display shows something else, our Vaillant heat pump error codes guide covers the full list, and the wider Heat Pump Not Working explained walks through the checks that apply to any make.

What pressure should a Vaillant heat pump be?

A Vaillant heat pump heating circuit should normally read between 1 and 1.5 bar cold, according to Vaillant UK’s heat pump fault code page. The manuals disagree slightly between models: the VWL /2 A installation instructions give an operating pressure of 1.5 to 2.0 bar for the heating circuit, and Vaillant’s quick guide for the aroTHERM plus has been quoted at 0.5 bar minimum, a figure we could not confirm in a document we read. We take the cautious reading: treat anything below 1 bar as too low until your engineer confirms the figure for your model.

The pressure sensor that triggers F.22 sits in the heat pump’s hydraulic circuit, so the number on the controller and the number on a separate gauge fitted by the installer should agree. The gauge is usually on the pipework near the hydraulic module or cylinder, next to the filling loop. If the two readings differ by a wide margin, that gap is itself a clue, because it points to the sensor rather than the water. Check the installation manual for your model for the exact gauge and filling point positions, because Vaillant systems are built up from separate components and no two installations are identical.

Why does a Vaillant heat pump keep losing pressure?

Heating systems are sealed, so a drop in pressure always means water or air is going somewhere it should not. The usual reasons on an aroTHERM installation are:

  • A small leak at a radiator valve, pipe joint, underfloor manifold, or the connections around the heat pump itself.
  • A failing expansion vessel that has lost its air charge, so pressure swings wildly between cold and hot and the gauge sinks overnight.
  • Air in the system, often after filling or draining, which can make the gauge read oddly and starve the pump of water.
  • A weeping pressure relief valve that is discharging a little each time the system heats up, usually outside where nobody sees it.
  • Recent radiator work or bleeding, which removes water and drops the gauge until someone tops it up.
  • A faulty water pressure sensor or cable, which is what F.73 points to and can also trigger a false low reading.

Vaillant also lists F.532 (building circuit flow rate too low) with low water pressure as one of its possible causes, alongside trapped air, a missing or clogged dirt filter and a pump fault. Vaillant UK’s fault code page treats F.532 as an installer matter in the first instance, because it depends on how the heat pump was matched to the heating system. A defrost cycle makes the problem visible sooner: during defrost the aroTHERM draws heat from the building circuit, and poor flow at that moment shows up as a fault. The same low-flow condition in freezing weather is covered in our guide to the Vaillant F.741 and F.283 defrost fault.

How do I top up the pressure on a Vaillant heat pump?

Vaillant UK says an owner who is competent to do so may raise the pressure slowly to between 1 and 1.5 bar through the filling loop when the gauge is below 1 bar, at their own risk, and should not open the heat pump casing. These steps need no tools and no panels removed. If you are not comfortable with any step, stop and call an engineer.

  1. Read the pressure gauge on the heating circuit when the system is cold. Compare it with the minimum in your manual, and treat anything under 1 bar as low.
  2. Look for visible drips or damp patches around radiators, valves, the cylinder, the hydraulic module and the pipes under the outdoor unit.
  3. Check that radiators and zone valves are open and that nobody has closed a lockshield or isolation valve, which can cause flow faults as well as odd readings.
  4. Find the filling loop, a short braided hose with a valve at each end, usually near the gauge. Open the valves slowly and watch the gauge climb.
  5. Stop between 1 and 1.5 bar, close both valves fully and disconnect the loop if it is the removable type.
  6. Reset once from the controller as your operating instructions describe. If F.22 falls again within days, stop topping up and book a visit.

Our guide to Heat Pump Losing Pressure guide goes into the repressurising process and what a normal rate of loss looks like.

What not to do:

  • Do not attempt any refrigerant work. A low water pressure fault is not a refrigerant fault.
  • Do not remove the outdoor unit or indoor unit panels. Live electrics, moving parts and pressurised components sit behind them.
  • Do not keep over-pressurising to be safe. Pushing the gauge towards the maximum can lift the pressure relief valve and stress joints.
  • Do not ignore repeated top-ups. If you need to refill the system more than once or twice a year, water is escaping somewhere and it needs finding.

Which Vaillant codes appear with low pressure?

These are the Vaillant codes we could confirm in the aroTHERM documentation and on Vaillant UK’s fault code page that relate to water pressure, flow or the pressure sensor.

Code Meaning First step
F.22 (F.022) Water pressure too low. Listed cause: insufficient water in the heating system. Read the gauge, look for leaks, then call an engineer if it falls again after a top-up.
F.73 (F.073) Water pressure sensor fault. Listed cause: broken line or short circuit to the sensor. Check the gauge. If it reads normally, book an engineer to test the sensor and wiring.
F.532 Building circuit flow rate too low. Possible causes include air, a blocked dirt filter, low water pressure and a pump fault. Check the gauge and that valves are open, then book an engineer to bleed and inspect the filter and pump.
F.86 (F.086) Contact thermostat has opened. Listed causes include low heating circuit flow or a closed underfloor circuit. Make sure underfloor and radiator circuits are open, then call an engineer if it repeats.

Codes can be shown with or without the leading zero depending on the display and software, so F.22 and F.022 are the same thing. The myVAILLANT app and the controller both show the active code, and the operating instructions for your model explain the reset.

How can you stop it happening again?

When to call an engineer

  • F.22 or F.73 returns after you have reset the unit once.
  • The gauge drops again within days of a top-up, or you can see water escaping.
  • The pressure relief valve is dripping or has discharged.
  • F.73 appears while the gauge reads normal, which points to a sensor or wiring fault that needs a qualified engineer.
  • Heating or hot water has stopped, or you also see a flow fault such as F.532.

Booking early matters here. A small leak caught in week one is usually a cheap fix, while months of topping up can let air and fresh oxygen into the circuit and cause sludge and corrosion. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. We work on Vaillant aroTHERM systems regularly and will pressure test the circuit, check the sensor and cable if F.73 is showing, and put the system back to the correct fill pressure. Book a book a repair, see our Vaillant heat pump servicing and repairs page, compare service and cover plans if you would rather spread the cost of looking after the system, or check the the towns and cities we cover. If you are weighing up whether a plan makes sense, read Is Heat Pump Cover Worth It explained, and for how the unit compares with rivals see our Vaillant aroTHERM Plus Heat Pump Review explained.

Frequently asked questions

Can I run my Vaillant heat pump with F.22 showing?

The unit will normally lock out or limit operation because it is protecting itself from running with too little water. Repeatedly restarting it does the pump and heat exchanger no favours, so it is better to leave it off, read the gauge, and either top up once if you are competent or get it checked.

Why did the pressure drop after my Vaillant heat pump was serviced or drained?

Any time water is removed, the pressure falls until the system is refilled and bled. A small drop in the first day or two as air works out of the radiators is normal. If it keeps falling days after the work, a joint disturbed during the job may be weeping and should be inspected.

Does an aroTHERM need a different filling pressure in winter?

The cold fill figure comes from your installer and manual rather than the season. What does change is the gauge reading, because water expands as it heats, so always compare readings at the same temperature. A small rise when the heating is running is normal; a large swing suggests the expansion vessel needs checking.

Will a pressure fault affect my warranty?

Unreported leaks and DIY repairs can cause problems with a warranty claim, so keep your service records and avoid altering the system yourself. Topping up through the filling loop is something Vaillant UK describes as an owner task for a competent person. A qualified engineer’s report is the safest evidence if the manufacturer ever asks.

Is F.73 ever caused by low water?

Not directly. F.73 is a sensor or wiring fault, so the heat pump has lost its reading rather than its water. A system that has been drained and refilled can, however, show F.22 and F.73 in quick succession if a connector was disturbed, so tell the engineer about any recent work.

Sources and further reading: Vaillant aroTHERM VWL../2 A 230 V installation instructions, document 0020147164_07, Appendix E overview of fault codes and section 6.11 operating pressure (manualslib copy of the official manual); Vaillant UK heat pump fault codes, entries F.22 and F.532. Checked 30 October 2026.

Myles Robinson

Written by , an expert in heating and renewables with over 15 years in the industry. The guides published here are written and maintained by Myles with input from the company's engineering team, and are reviewed whenever grant schemes, prices or manufacturer advice change.