At a glance
- F.74: “The heat pump is switched off”, cause “Hydraulic system pressure too low”, measures “Top up with water. Vent the system”, per Viessmann’s service instructions 6194799 (3/2022).
- F.75: heat pump switched off, “No flow in the secondary circuit, or flow sensor faulty”; the pump and the flow sensor are checked and replaced if required.
- F.982: the heat pump does not start because the heating circuit pump is running dry; the measures end with “Fill system”.
- F.87 is the opposite condition, system pressure too high, where the safety valve in the indoor unit has opened.
- Viessmann’s service instructions do not state a pressure in bar; the set system pressure and its range are configured on the system, so ask your installer for the figure.
- The same table applies to the Vitocal 200-S and 222-S, 150-A and 151-A, 250-A and 252-A and 250-AH, all on the Viessmann One Base platform.
What does F.74 and F.75 mean on a Viessmann Vitocal heat pump?
F.74 on a Viessmann Vitocal means the hydraulic system pressure is too low and the heat pump has switched itself off until the cause is fixed. The pressure sensor in the heating circuit has read below the set minimum. Viessmann’s measures are to top up with water and vent the system. If the fault recurs, the service instructions tell the engineer to check the system pressure sensor against an external pressure gauge, check the pre-charge pressure of the expansion vessel, and check the settings for set system pressure and range.
F.75 means no flow in the secondary circuit, or a faulty flow sensor, and again the heat pump is switched off. The measures are to check the secondary pump or heating circuit pump, check the heating and cooling circuit, replace the pump if required, and check the flow sensor. F.982, heating circuit pump running dry, stops the heat pump from starting at all; the listed measures are to check the shut-off valve, check the heating circuit pump connection, and fill the system. That is another way low water shows up.
These entries come from the fault tables in Viessmann’s service instructions for contractors, “System configuration and diagnosis for heat pumps with Viessmann One Base”, which covers the Vitocal 200-S and 222-S, 150-A and 151-A, 250-A and 252-A and the 250-AH. Fault codes and wording can vary between models and control software, so use the table for your unit. If you are not sure which code you are looking at, our Viessmann heat pump error codes guide lists the rest, and the general Heat Pump Not Working questions answered covers checks that apply to any brand.
What pressure should a Viessmann Vitocal heat pump be?
Viessmann’s service instructions do not give a bar figure for the correct Vitocal system pressure. They refer to a set system pressure and a range that are configured on the system by the installer, and the engineer’s follow-up for a repeated F.74 is to check those settings. So the right number for your home is the one your installer recorded at commissioning, and you should note it next to the gauge rather than guessing. Check the installation manual for your model if the figure was never written down.
On a Vitocal 200-S or 222-S the pressure sensor sits inside the indoor unit, and the controller uses that reading for F.74 rather than a separate dial. Many installations also have a mechanical gauge on the pipework near the filling loop, usually by the indoor unit or cylinder. Viessmann’s own advice to test the sensor against an external gauge tells you how to interpret a disagreement: if the dial reads normal while the controller insists the pressure is low, suspect the sensor. The controller shows the code on its display and in the ViCare app, and the warning A.11, room heating for only some rooms, is also listed with “system pressure too low” as the cause and “top up with water” as the measure.
Why does a Viessmann Vitocal heat pump keep losing pressure?
- A leak at a joint, valve, pump connection, radiator or underfloor manifold.
- An expansion vessel with the wrong pre-charge, or a failed diaphragm. Viessmann lists “pressure drop in secondary circuit” and “pressure spikes in secondary circuit” as warnings whose first measure is to check the expansion vessel.
- Air in the system that is vented by the automatic air vent, taking water with it.
- The safety valve discharging after a pressure spike and not closing fully.
- Recent bleeding or radiator work, where water was released and not replaced.
- A faulty pressure sensor, which reads low when the real pressure is fine.
- A closed shut-off valve or blocked filter, leading to F.75 or F.982 faults on top of low pressure.
Underfloor heating systems add a lot of pipework, so a small leak under a screed can lose pressure slowly and quietly. If you top up more than once, treat it seriously.
It is worth understanding why Viessmann switches the heat pump off at all. With too little water in the circuit, the pump can run dry and the heat pump cannot move heat away from the refrigerant circuit. Stopping early protects the compressor and the pump. That is also why F.982, the dry-running fault, is listed alongside F.74 as another sign that the system needs filling. A defrost cycle in winter asks even more of the water side, because the Vitocal briefly takes heat from the building circuit to clear ice; weak flow at that moment is what our guide to the Viessmann 21 error and frozen outdoor unit describes.
If you have had a top-up that cleared F.74 but the fault comes back weeks later, the system is losing water somewhere or the expansion vessel is not doing its job. The service instructions specifically list checking the expansion vessel pre-charge as a follow-up measure for a recurring fault, so it is worth asking your engineer to confirm it was done. A pressure sensor that disagrees with an external gauge is the other classic cause.
How do I top up the pressure on a Viessmann Vitocal heat pump?
Viessmann’s own measure for F.74 is “top up with water” and “vent the system”, written for contractors. Whether you do the first part yourself depends on whether your installer fitted an accessible filling loop and showed you how to use it. If so, and you are competent, the sequence is:
- Look at the pressure gauge on the system and write down the reading. Check whether it is a cold or warm system.
- Look for visible drips, damp walls or ceilings, and wet floors near manifolds and pipework.
- Check all radiator valves, zone valves and shut-off valves are open.
- Note the full fault code and anything else showing on the controller.
- Open the filling loop valves slowly, watch the gauge climb to the figure your installer gave you, then close the loop and disconnect it afterwards.
- Acknowledge the fault on the controller if your operating instructions say so, and watch the gauge over the next week.
See our guide to a Guide to Heat Pump Losing Pressure for what to expect and when to worry.
What not to do:
- Do not touch refrigerant circuits.
- Do not remove panels or covers from the indoor or outdoor unit.
- Do not keep over-pressurising the system. That can lift the safety valve and trigger F.87.
- Do not ignore repeated top-ups.
- Do not change the system pressure or range settings in the controller unless you are an engineer.
Which Viessmann codes appear with low pressure?
These are the pressure and flow faults we could verify from Viessmann’s service instructions for the Vitocal range on Viessmann One Base.
| Code | Meaning | First step |
|---|---|---|
| F.74 | Hydraulic system pressure too low; heat pump off | Check the gauge and top up if competent, vent, then call an engineer if it returns |
| F.75 | No flow in the secondary circuit or flow sensor faulty | Check valves are open and book an engineer to check the pump and sensor |
| F.982 | Heating circuit pump running dry; heat pump will not start | Check shut-off valves and pressure, then book an engineer |
| F.87 | Hydraulic system pressure too high; safety valve has opened | Do not top up. Book an engineer to reduce the pressure safely |
| F.797 / F.799 | Secondary pump or heating circuit pump 1 off | Isolate power, restart once, and call an engineer if it persists |
| A.11 | Warning: room heating for only some rooms, system pressure too low | Top up with water, then watch for a repeat |
How can you stop it happening again?
- Have an annual service. Our Guide to Heat Pump Annual Service Checklist covers pressure, the expansion vessel, filters and pumps, and More on why heat pump servicing is so important explains what a missed year costs.
- Have drips investigated early. Our guide to a Guide to Heat Pump Leaking Water helps you decide what to look for.
- Make sure the system was filled and vented properly at installation. Our Guide to Heat Pump Commissioning sets out what should have been done.
- Look at your heating before winter. Our heat pump winter tips cover what to check before the cold weather arrives, and More on do heat pumps work in cold weather explains how defrost loads the water circuit.
- Check the gauge monthly and keep a note of readings.
When to call an engineer
- F.74 returns after a top-up.
- You are topping up more than once a month, or more than once at all in a short period.
- F.75, F.982 or F.87 appears.
- You can see water where it should not be.
- The gauge looks normal but the fault remains, suggesting a sensor problem.
- You have no heating or hot water.
Book early. Pressure faults often start as a nuisance and end as a shutdown at the coldest time of year. UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. Our engineers find the leak, check the expansion vessel and air vent, and test the pressure sensor against a reference gauge as Viessmann’s instructions describe. Book a fault diagnosis and repair, see our Viessmann heat pump servicing and repairs page, look at breakdown cover and annual servicing, or check the where we work. Not sure a plan is for you? Read Is Heat Pump Cover Worth It questions answered, and for the unit itself see our Viessmann Vitocal Heat Pump Review.
Frequently asked questions
Will the heat pump restart after I top up the pressure?
It should, once the pressure is back in range, though some units need the fault acknowledged on the controller. Viessmann’s measures for F.74 are to top up and vent, so trapped air may also need clearing before the flow sensor is happy. If it does not restart, leave it and call an engineer rather than trying repeated resets.
Can the pressure sensor be wrong?
Yes. Viessmann’s own measures for a repeated F.74 include checking the sensor against an external pressure gauge. A reading that does not match the gauge points to a sensor fault, not a leak. An engineer can also check the set system pressure and range settings, which decide the point at which F.74 is raised.
Does cold weather lower the pressure?
Cold water contracts, so a cold system can read lower than a warm one. A small seasonal change is normal, but a steady fall over weeks is not. The expansion vessel is there to absorb these swings, so a gauge that moves a long way between cold and hot is a sign its pre-charge needs checking.
Why did the safety valve open after I topped up?
The system was probably over-filled, or the expansion vessel cannot absorb the expansion when the water heats. Viessmann lists this as F.87, hydraulic system pressure too high, with the measure “reduce the system pressure”. Do not add more water, and have the vessel checked by an engineer.
Is a Vitocal fault covered by my Viessmann warranty?
That depends on the cause and the terms. Keep your service records, because skipped servicing can affect cover. A leak in field pipework is usually an installation matter rather than a product fault, so the installer may be the first call while the system is under their care.
Sources and further reading: Viessmann service instructions for contractors, “System configuration and diagnosis for heat pumps with Viessmann One Base”, 6194799 GB 3/2022, fault and warning messages for the Vitocal 200-S/222-S, 150-A/151-A, 250-A/252-A and 250-AH (copy hosted by Viessmann Direct). Checked 30 October 2026.