Worcester Bosch Heat Pump Pb & Hb Error: Freeze Protection Meaning, Causes & Fixes

Worcester Bosch freeze & defrost faults guide tile: a Worcester Bosch outdoor unit on a patio beside a brick house with shrubs
Myles Robinson
Heating and renewables expert
Updated

Get a cover plan here

Pb on a Worcester Bosch heat pump means antifreeze mode, which the Compress 2000 AWF manual calls normal operation rather than a fault. Hb means three consecutive PP temperature difference faults with the leaving water below 7 °C. A frozen Worcester Bosch heat pump that repeats Hb needs the sensor or valve fault behind it found.

At a glance

Get a cover plan here >

  • Pb on a Worcester Bosch Compress 2000 AWF means antifreeze mode. The manual says it is not a protection, the alarm light does not flash, and the remote control shows the antifreeze icon rather than the code.
  • Hb means three consecutive PP faults with the leaving water temperature (Twout) below 7 °C, and is reset by a power failure. PP is an abnormal temperature difference between entering and leaving water.
  • Worcester Bosch warns that during a blackout or power failure the freeze protection functions cannot be activated, and that if the supply has to be disconnected the water in the circuit must be completely drained.
  • The manual’s rule on resets is to identify and remove the cause first, because repeated resets can lead to irreversible damage.
  • Bosch asks for a raised base at least 100 mm above the maximum snow height, a condensate route that cannot freeze, and a canopy where rain or snow falls on the unit.
  • On the Compress 3400i, de-icing starts when the ice layer impedes airflow through the evaporator and works by reverse circulation of the refrigerant.

What do Pb and Hb mean on a Worcester Bosch heat pump?

Pb means the Worcester Bosch Compress 2000 AWF has entered antifreeze mode. The alarm table in its installation and operating instructions describes Pb as antifreeze, adds that it is not a protection and the alarm light does not flash, and notes that the remote control shows the antifreeze icon instead of the code. The troubleshooting section says the unit will automatically return to normal operation. Pb is the heat pump keeping its own water above freezing, and it needs no action from you.

Hb is different. The same table defines Hb as three consecutive PP faults with Twout, the leaving water temperature, below 7 °C, and says it is reset by a power failure. PP itself is an abnormal temperature difference between the entering and leaving water, and the troubleshooting page explains the detail: the inlet water temperature is higher than the outlet in heating mode, which points to a loose sensor connector, a faulty TW_in or TW_out sensor, or a blocked or faulty four-way valve. Hb is therefore a sensor or valve problem that has repeated while the water was cold, which is where freezing becomes a real risk.

These codes belong to the Compress 2000 AWF (CS2000AWF 4 to 30 kW). The Compress 3400i, 5800i and 7001i use the HPC 410 control unit with a different fault code and sub-code scheme. If the heat pump has stopped with no code, our guide to a guide to Heat Pump Not Working covers the first checks; every other code is in our Worcester Bosch heat pump error codes guide.

Is ice on a Worcester Bosch heat pump normal?

Yes. The Compress 3400i operation manual explains that when the ice layer on the evaporator becomes thick enough to impede airflow, an automatic de-icing process starts, and the Compress 2000 AWF manual warns installers to expect a considerable amount of water from the defrosting cycles. The HMI on the 2000 AWF has a dedicated “Defrosting mode on” icon next to the “Antifreeze mode on” icon, so you can tell a defrost from a Pb at a glance.

The 3400i manual also notes that moisture can form under the outdoor unit because condensate does not always fall into the catch pan, and calls that normal. What Bosch treats as a fault is ice that cannot drain: the 2000 AWF manual warns that condensate “could freeze outside the unit, blocking the flow and generating a gradually increasing build-up of ice”, and its answer is to raise the unit, fit heating cables with an antifreeze function and run the drain below the frost line.

For a brand-neutral picture of frost against a fault, see our guide to a Heat Pump Frozen Outside Unit explained.

How does the Worcester Bosch defrost cycle work?

A Worcester Bosch Compress heat pump de-ices by reversing the flow direction of the refrigerant, which the 3400i manual calls reverse circulation, so the evaporator warms for a few minutes and sheds its ice while heat is drawn from the heating water. Bosch does not state how long the cycle runs or whether the fan stops, so those details are general heat pump behaviour; our guide to the Heat Pump Defrost Cycle explained explains them.

Antifreeze mode is separate. The 2000 AWF manual says that in antifreeze mode the unit heats the water by activating the circulation pump or the additional electric heater, which is why Pb can appear on a cold night with no fault at all. The limit is power: the manual states that in a blackout or power failure the freeze protection functions cannot be activated, and that if the supply must be disconnected the circuit must be completely drained. The 3400i manual puts it more simply: there is no frost protection during a shutdown.

The outdoor unit is designed for cold. The 3400i switches off only below about minus 20 °C on most sizes, and the 5800i has a short heating cable integrated in its drip tray and asks for pipe trace heating wherever ice is likely to form in the condensate hose.

Why has my Worcester Bosch heat pump frozen or shown Hb?

Hb and the codes around it come from the Compress 2000 AWF alarm table, and the table below pairs Bosch’s meaning with the usual winter cause.

Symptom Compress 2000 AWF code Bosch meaning and cause Who acts
Antifreeze icon on the HMI, unit running on a cold night Pb Antifreeze mode: pump or electric heater keeping the water warm; not a fault Nobody
Alarm with inlet warmer than outlet in heating PP Abnormal temperature difference: sensor connector, TW_in or TW_out sensor, four-way valve blocked or faulty Engineer
Unit locked after repeated PP in the cold Hb Three consecutive PP with Twout below 7 °C; reset for power failure Engineer; find the cause before any reset
Unit stops, coil iced or dirty P0 Low pressure protection: no refrigerant in the system, or the external heat exchanger dirty or clogged Owner clears the coil surroundings, then engineer
Fan stops, strong wind H6, HH DC fan failure, which Bosch links to wind driving the fan backwards; HH is ten H6 in 120 minutes Owner checks for ice or debris, then engineer
Cold radiators, flow alarm E0, E8 Water flow failure: shut-off valves, filter, air, pressure above 1 bar, pump speed, expansion tank Owner checks valves and pressure, then engineer
Ice growing under the outdoor unit None Condensate freezing outside the unit and blocking the drain Owner clears debris, engineer for heating cables

Pressure sits behind E0 and E8 and weakens every defrost. If your gauge is low, our guide to Worcester Bosch heat pump low pressure explains the top-up and the checks Bosch lists for E8.

How do I clear a Worcester Bosch freeze fault safely?

Bosch’s instruction before any reset is to identify and remove the cause, so these steps come first and the reset comes last.

  1. Read the HMI. Note whether you see the antifreeze icon (Pb), the defrosting icon, or an active alarm symbol with a code. The 2000 AWF stores eight error codes under Menu, Service Information, and the Error Code menu shows their meaning.
  2. Keep the power on. Bosch says freeze protection cannot run in a power failure, so do not isolate the unit in a frost to clear a code; a unit that must be disconnected has to be drained.
  3. Clear airflow and check for wind. Remove snow and leaves from outside the casing. Bosch links H6 to strong wind spinning the fan backwards, so note whether the unit faces the weather.
  4. Check the condensate route. Make sure melt water can leave the base and is not freezing into the build-up Bosch warns about. Thaw a frozen outlet with lukewarm water only, not on the coil.
  5. Check the water side. Bosch’s E8 list applies to every flow problem: shut-off valves open, filter clean, no air, pressure above 1 bar. Open any radiator or zone valves that were closed.
  6. Reset once, if at all. Pb needs no reset. For Hb, which Bosch says is reset by a power failure, interrupt the supply once and restore it straight away only after the checks above; the manual warns that repeated resets can cause irreversible damage, so if Hb returns, stop.

Do not chip ice from the evaporator, do not remove panels and never touch the refrigerant circuit; P0’s “no refrigerant in the system” is work for a qualified engineer. One Bosch manual, for the Compress 3400i, says hot water can be used to rinse ice off the top of the unit. We advise against it on any model: water on the fins refreezes, and the fan and electrics sit behind them.

When to call an engineer

Call an engineer if Hb returns after one reset, if PP keeps appearing, if P0 shows at all, if the fan stops in calm weather, if ice remains under or on the unit after you have cleared the drain, or if pressure keeps falling below 1 bar. Call straight away if the house is losing heat or hot water in freezing weather. Bosch’s own advice when in doubt is to contact a service centre.

An engineer will test the TW_in and TW_out sensors and their connectors, check the four-way valve behind PP, clean the external heat exchanger and filter, confirm the flow and pressure Bosch lists for E8, and test the refrigerant charge where P0 is logged.

UK Heat Pump Servicing provides annual servicing, fault diagnosis and repair, cover plans and new installations for heat pump owners across England, Scotland and Wales. See our Worcester Bosch heat pump servicing and repairs page, book a book a repair, compare heat pump cover plans or find the find your nearest engineer.

How can I stop my Worcester Bosch heat pump freezing again?

Bosch’s installation rules are the prevention list. The 2000 AWF manual asks for a raised base at least 100 mm above the maximum snow height, a canopy where rain or snow falls on the unit, unobstructed airflow, and a condensate route that is heated or runs below the frost line. The 5800i manual adds pipe trace heating wherever ice can form in the hose, a frost-free drain, and enough system water volume to avoid incomplete defrosting and unnecessary alarms. An annual service checks the sensors behind PP, the filter and pressure behind E8, and the drain; our article on Guide to Why Heat Pump Servicing Is So Important explains what each check prevents.

Keep the unit powered all winter, because Bosch is explicit that antifreeze mode and freeze protection stop without electricity. Our guide to Guide to Do Heat Pumps Work in Cold Weather explains why steady running protects the system, and if you would like winter faults covered, read whether guide to Is Heat Pump Cover Worth It. Our Worcester Bosch Heat Pump Review covers the Compress range as a whole.

Frequently asked questions

Why does my manual not list Pb or Hb?

Because they are Compress 2000 AWF codes. The Compress 3400i, 5800i and 7001i use the HPC 410 control unit, which shows a fault code with a sub-code and asks you to quote both, plus the ID number of the user interface, when you call. Always go by the manual for the model on your data plate.

What does Twout mean on a Worcester Bosch heat pump?

Twout is the leaving water temperature, the water flowing out of the heat pump to your heating. Hb watches it because three PP faults while Twout is below 7 °C means the sensors or four-way valve have misbehaved three times with cold water in the unit, which is when ice inside the heat exchanger becomes possible.

Does antifreeze mode use extra electricity?

Yes. Bosch says antifreeze mode heats the water by activating the circulation pump or the additional electric heater, so a cold night with Pb showing costs a little more than usual. That is far cheaper than a frozen heat exchanger, and the mode switches itself off when the water is warm.

Can I rinse ice off my Worcester Bosch unit with hot water?

The Compress 3400i operation manual does allow a hot water rinse of ice on the unit after clearing snow from the top. We do not recommend it on any model, because water on the evaporator fins refreezes and runs onto the fan and electrics. Clear snow by hand, keep the condensate route free and let de-icing do the work.

Is Hb dangerous for my home?

No. Hb is a protective lockout for the heat pump, not a safety risk for the house. The risk is to the unit if the PP sensor or valve fault behind it is ignored and the water inside freezes. Have it diagnosed rather than repeatedly resetting it, which Bosch warns can cause irreversible damage.

Sources and further reading: Worcester Bosch Compress 2000 AWF Installation and operating instructions 6721859133, alarm table, troubleshooting, freeze protection and installation sections (worcester-bosch.co.uk); Worcester Bosch Compress 3400i AWS Operation manual 6721852787, defrosting, faults and snow and ice sections (worcester-bosch.co.uk); Worcester Bosch Compress 5800i AW outdoor unit Installation instructions 6721866761 (worcester-bosch.co.uk).